14
Faulty XML Unit Import in the Batch Module
Description When creating and importing an XML file with defined units and the phases from external Tool into the batch module, some imported phases was sporadically not created correctly. Additionally the Engineering Studio crashed sometimes. The ...
MU project becomes corrupted if Synchronize is executed immediately after creating a SOT
Summary The Multi User project cannot be loaded anymore after the creation of a new Smart Object Template and the start of Synchronize. The issue has been fixed and the behavior is as expected now. To benefit from this fix: Update your zenon Software ...
Report Viewer does not display filter parameter correctly in specific cases
Description The Report Viewer screen switch function was unable to load the time of the filter parameter (filtered data) in certain cases. If an element with a time stamp is present in the data set, the time of the filter parameter is now displayed ...
[Edge Gateway] Editing a variable with "BOOL" data-Type will cause said variable to not be shown until a service reboot
Description When a Edge Gateway Frontend driver connection with the variable data type BOOL has been created, the variable became invisible after saving. The behavior has been fixed and the variables with the data type BOOL are available after saving ...
[EdgeGateway Setup] Missing start parameter when installing "Gateway Services" causing EdgeGateway to crash
Description The Edge Gateway crashed, even if is installed as a service. The crash is caused by the absence of the "-c" in the corresponding zenon6.ini entry (should be: PARAM_2 = -c -se). The issue has been fixed and the Edge Gateway runs as a ...
[Edge Gateway] During variable creation, chosen connection will be always overrided by the first connection defined of the related driver.
Description During variable creation, the selected connection was always overwritten by the first connection defined of the related driver. Now the selected connection will not be overwritten anymore during the variable connection. How to benefit ...
Hostname can no longer be used with S7TCP32 instead of using the IP Address
Description In zenon 14, the connection via the “Hostname” no longer works for the S7 TCP-IP driver. Only the “IP address“ is accepted. Thus, when converting from earlier versions that establish the connection via “Hostname”, a connection is no ...
Specific Soft Licenses not working correctly under Linux
Description Local licenses do not work correctly under Linux. Although the version and validity period are correct, they are not accepted by the Service Engine under Linux. However, the same license works under Windows. As soon as a local license is ...
OPCUA driver crashes when reading variables in background
Summary The OPC UA driver is terminated unexpectedly. This error has been fixed. Description The OPC UA driver is terminated unexpectedly when reading the PLC variables in the Engineering Studio via the command “Read PLC variables in background”. The ...
BATCH CONTROL - Function authorization for export of recipes
Summary Batch Control now has a new function authorization for exporting recipes. Description The export of recipes in Batch Control also allows access to the device's file system. This can now be restricted. For this purpose, the setting "Batch ...
[Edge Gateway] Password change functionality always returns "Unable to change password"
Description In the Edge Gateway frontend, the user password can no longer be changed. Despite correctly entering the previous password and the new password including password retype, an error message is displayed: “Unable to change password”. This ...
WVS: Input misplaced when using RGM in a worldview
Summary In WVS, the input field for values in the worldview screen is placed incorrectly under certain conditions. This has been fixed. Description In WVS, the input field for values in a worldview screen may be positioned incorrectly. In this case, ...
Fieldbus configuration: uncomplete display in the tree for the root node
Summary In zenon Logic, some values are not displayed when reopening the Fieldbus configuration. This error has been fixed. Description In the "Fieldbus Configurations" editor, for entries in the tree of the root node, the names and values of the ...
Scheduler: It is not correctly ignoring functions on Mondays when a special day is scheduled
Summary In the Scheduler, entries on a Monday are not handled correctly if a “special day” has also been created for it. This bug has been fixed. Description If a “special day” is created in the Scheduler using the “Create special schedule” context ...
Unexpected error when compiling UDFB in FFLD
Description In zenon Logic, an unexpected error occurs when compiling a UDFB in FFLD. This has been fixed. Compiling works as expected again. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or higher. ...
Batch Control - Phase edit dialog is no longer resizable
Description In Batch Control, the "Edit phase" dialog can no longer be resized. In certain constellations, the dialog is opened in such a way that the gripper icon cannot be operated correctly. This mainly occurs when the dialog is opened on a ...
OPCUA Process Gateway deadlocks after reload
Summary The OPC UA Process Gateway does not work as expected after a full reload of the Service Engine. This problem has been fixed. Description If endpoints or communication parameters for the OPC UA Process Gateway are changed in the Engineering ...
TREND: Multi-select changes to curves renames all curves to the same name as the first curve.
Summary In the Extended Trend, curves are erroneously renamed when multiple selections are made. This bug has been fixed. Description In the screen switch dialog to an Extended Trend, when editing multiple curves the static curve names are ...
Alarm Filter Issue When Using Reactivated Time Option in AML
Summary The AML filter does not work as expected in the Service Engine for alarms with active project property "Use reactivated time". This has been modified. Description If an alarm occurs within the set filter time, it is indicated correctly. If ...
Command "Copy" does not work in the output window
Description After building a zenon Logic project, the information from the output window should be copied. The "Copy" command is available in the context menu and is selected. When pasting into another document, no content is available. The "Paste" ...
Logic: communication error after making changes in the logic project while the online change feature was active
Description In zenon Logic, the execution of "Online change" leads to an unexpected termination of the Logic Service. This bug is caused by the EIP driver, which does not react correctly to the execution of the online change. This bug has been fixed. ...
DNP3_TG: INVALID timestamp is updated when there is no connection to the outstation
Description The DNP3 Third Generation driver updates the timestamp for the "INVALID" status even if there is no connection to the outstation. This behavior is undesirable as it might mislead events such as runback operated. This behavior has been ...
Changing scaling of a monitor cause checkboxes in the engineering studio to be invisible upon restart
Description When the scaling of a monitor has been modified, in the Engineering Studio the checkboxes for activating or deactivating properties are no longer displayed. The checkboxes are only displayed again after a restart of the Engineering ...
Library Manager - Comment field is available when creating a new Type while it is not supported
Description In the Logic Library Manager, when creating a new entry in the "Types" tab, the "Comment" field is also offered for configuration. However, this should be disabled and not available for "Types". This behavior has been modified. The ...
Monitoring tool wizard crash (wizard for generating K5M file)
Description In the zenon Logic assistant "Generate Monitoring Application", an error message with a white X in a red circle is displayed on the "Select typeof tree" page when clicking on ">Next". If this error message is acknowledged with "OK", the ...
Report Viewer: Values are displayed as "#Error" after switching to another page.
Description In the Report Viewer screen, values retrieved in the Service Engine are displayed correctly when the report is opened. After a page change, however, the previously correctly displayed values are shown as "#Error". This was caused by ...
Vulnerability in third party component skiasharp.2.88.3 used in File Inspector
Summary Vulnerability in File Inspector dependency fixed. Description A vulnerability has been detected for the 3rd party component skiasharp.2.88.3.nupkg that is used by the File Inspector. The vulnerability in the 3rd party component has been ...
Project description lost with XML export/import
Description In zenon Logic, the project description is not imported correctly when importing a complete project from the XML export file. This remains empty. This bug has been fixed. When importing a project from XML, the project description is also ...
Output window: "Report Viewer: export/print" function provides incorrect warning in the output window
Summary The "Report viewer: export/print" function issues incorrect warnings in the output window. This has been fixed. Description Under certain conditions, the "Report viewer: export/print" function issues incorrect warnings in the output window. ...
Linux runtime - bad implementation of the "parameter registry"
Description In the Logic Service under Linux, the parameter registry cannot be opened from the registry host. Cause: The file "t5regoem.c" is not implemented correctly. This bug has been fixed. Parameter registration works again as expected. To ...
MQTT - segmentation fault when the you connect to a brocker with bad certificate.
Description In the Logic Service, if a connection to a broker with an invalid certificate is established, the Logic Service is terminated unexpectedly with a segmentation fault. This bug has been fixed. The Logic Service is no longer terminated ...
straton strings with special characters are broken in force value dialog
Description In zenon Logic, strings with special characters are not displayed correctly in the Spy and in the Force value dialog. String values that are forced are not correctly written. This bug has been fixed. The value is displayed and written ...
OPCUA32: Fallback to ConditionRefresh should also occur when the OPC UA Server returns 0x80400000 - BadNotImplemented on the Call of ConditionRefresh2
Summary Fallback to ConditionRefresh does not work correctly for specific OPC UA Server. This has been fixed. Description When the OPCUA32 driver creates monitored items for event notifier variables, it calls the ConditionRefresh2 method after ...
For a client advised variables are not disconnected
Description Under Linux, variables that have been advised are not released when the Service Engine is terminated. This behavior has been changed. Advised variables are released again when the Service Engine is shut down. To benefit from this fix: ...
Process Recorder: Archive data creation during active playback mode
Summary ARX files are created in the playback mode of the process recorder. This behavior has been modified. Description The Service Engine creates archive files (*.arx) during the playback mode of process recorder. But during active playback mode no ...
Logic Studio creates files in %Temp% folder which does not get deleted
Description In Logic Studio, files are created in the %Temp% folder for an Add-In that opens the Studio via k5pi.dll. However, these files are never deleted. Each use of the Add-In adds new files. This behavior has been modified. No more files are ...
LOGIC: Shared Memory driver generates a wrong timestamp after conversion from v12 to v14
Description After converting a project from zenon version 12 to version 14, the Shared Memory driver in zenon Logic generates incorrect timestamps. This bug has been fixed. In zenon 14, the correct timestamp is displayed again after the conversion. ...
Process Recorder: Time Control active in simulation and in playback mode
Summary Time control is disabled when process recorder is in simulation or playback mode Description In the process recorder, the configured time control functions remained active even after switching to simulation or playback mode. Configured ...
SE: Crash if making the CEL column bigger in the SE
Description If the size of a column is changed in the Service Engine in a screen of type CEL that has been defined as the start screen, this leads to an unexpected termination of the Service Engine. This bug does not occur in the WVS. This bug has ...
SCL Editor [IEC61850-6]- the scl must not handle an error when checking a private types
Description When importing an SCL file with Private tags into the SCL Editor for IEC61850 in zenon Logic, a syntax error is indicated. However, according to the standard, errors for Private tags should not be indicated during validation. This ...