BACnetNG: Driver does not finish reading trendlog object before starting to read another trendlog with maxconcurrentrequest=1

BACnetNG: Driver does not finish reading trendlog object before starting to read another trendlog with maxconcurrentrequest=1

Description

The BACnetNG driver did not finish reading the reading the first trendlog file when the setting for the maximum concurrent requests is set to 1. With specific configurations this can lead to multiple trendlog files being read by the driver, while using no concurrent requests, that can cause performance issues with some devices. The issue has been fixed and the driver now finishes reading one trendlog before starting to read a next trendlog.

 

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 11 or higher.




Item ID: 285024
Version: 14.00 Build: 275981
Version: 12.00 Build: 272744
Version: 11.00 Build: 272743
    • Related Articles

    • The BACnetNG driver should support TrendLog variables.

      Summary TrendLog variables should be supported by the BACnetNG driver. DescriptionTrendLog variables should be supported by the BACnetNG driver. Solution The BACnetNG driver now supports TrendLog variables. Issue Number: 36601 Fixed on Date: ...
    • zenon Changesets Excel

      Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
    • zenon Changesets CSV

      Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
    • Checklist: Driver(s) cannot establish a reliable communication

      Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • OPCUA driver crashes when reading variables in background

      Summary The OPC UA driver is terminated unexpectedly. This error has been fixed. Description The OPC UA driver is terminated unexpectedly when reading the PLC variables in the Engineering Studio via the command “Read PLC variables in background”. The ...