BACnetNG: Driver does not finish reading trendlog object before starting to read another trendlog with maxconcurrentrequest=1
Description
The BACnetNG
driver did not finish reading the reading the first trendlog file when the setting for the maximum concurrent requests is set to 1. With specific configurations this can lead to multiple trendlog files being read by the driver, while using no concurrent requests, that can cause performance issues with some devices. The issue
has been fixed and the driver now finishes reading one trendlog before starting to read a next trendlog.
To benefit from this fix:
- Update
your zenon Software Platform to the latest build of zenon 11 or higher.
Item ID: 285024
Version: 14.00 Build: 314355
Version: 12.00 Build: 301428
Version: 11.00 Build: 314353