Mitsubishi - Melsec A-Q, Communication fails when polling variables in the File register on iQ-F FX5
Description
When a variable has been added in the in the Channel type 70 file register for iQ-F FX5 systems, the communication with the PLC fails for all variables.
To fix this issue a new driver object type called "File-Register (R)"has been implemented, that is using the supported command 0xAF. The already existing driver object type was renamed to "File-Register (ZR)".
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 12 or higher.
Item ID: 281297
Version: 14.00 Build: 257014
Version: 12.00 Build: 272744