8.00
61850 GOOSE cannot be received if several adapters are listed
Summary When a IEC61850 Server incl. GOOSE specified multiple Ethernet adapters for a GOOSE subscriber, the received values only on the first valid specified adapter where accepted. Description When a IEC61850 Server incl. GOOSE specified multiple ...
Variables with a comma in the name (multi-dimensional arrays) can no longer be used in the OPC UA Gateway
Summary Variables with a comma in the name (multi-dimensional arrays) can no longer be used in the OPC UA Gateway Description Variables with a comma in the name (multi-dimensional arrays) can no longer be used in the OPC UA Gateway Solution Variables ...
Set Value from a webclient, thats name cannot be resolved, are executed with time delay
Summary Server does not resolve clients hostname on set-value operation Description Server does not resolve clients hostname on set-value operation Issue Number: 138485 Fixed on Date: 7.6.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
SICAM230 comand 61850: SEL â telegram 2x sent
Summary Additional activation of select when in the time where the select command is transferred to the driver a value change of the command data point happens denied Description Additional activation of select when in the time where the select ...
zrsConnector.exe leads to RT-Crash
Summary Within 1 second a runtime-wise maximum of 50 BulkChange-events are fired before all subsequently incoming values are buffered. These outstanding values than are dispatched together at the end of this 1 second interval. Description Within 1 ...
ETM: When you display the last open& finished lots and you start, stop AND restart a lot again, the restarted lot is not considered any more (searching for new archives is deactivated then)
Summary For lot filter there's an option available to display the last X lots. If this filter was active for a screen, the screen was already opened and during the open screen new lots were created it was happening, that the newly created lots were ...
MODBUS_ENERGY: Variables remain without value / status under specific circumstances
Summary Under specific circumstances, the MODBUS_ENERGY driver configured to bundle connections has connections for which variables remain without value and without status, due to connectivity issues for another connection using the same IP address. ...
MODBUS_ENERGY: invalid modbus response to read holding register request does not set INVALID status for variables but uses random value with SPONT instead
Summary When a Modbus Slave returns a response with an invalid error code "00", according to the modbus specification, the MODBUS_ENERGY driver does not consider this an error and sends random values to the variables with status SPONT to the runtime. ...
Process Gateway 870 Slave: Cannot accept connections when Select Routing is activated
Summary When a master does a connect now no longer the zenon configuration is verified. This verification is now done at the gateway startup and when a reload of the zenon project is performed. The error was caused by the expiration of the t0 ...
Runtime stop working with dynamic limit text longer than ~1015 characters
Summary When writing a dynamic limit text based on string variable (e.g. via REMA) the runtime stops working if the string exceeds ~1024 characters. Description When writing a dynamic limit text based on string variable (e.g. via REMA) the runtime ...
PFS API crash when shift points are read from timetables with subordinate timetables
Summary New Methode was implemented for API: GetParentSchedule in PfsSchedules This Methode Returns the parent schedule if the schedule collection is in a child parent. In this case the Parent property is null. The parent of the object "PfsSchedule" ...
OPCUA32: importing variables from a specific OPC UA server fails due to exceeding the max. length of 128 characters for the variable name
Summary OPCUA32: When the concatenated browsepath and the browsename of the variable nodes in the OPC UA address space exceeds the maximum length of variable names (128 characters) the variables cannot be imported through online browsing. The ...
UDFB variables go missing
Summary The variables, which had no relation to zenon, were deleted from groups/programs . Description The variables, which had no relation to zenon, were deleted from groups/programs . Information Yet i do not really see a workaround, when you ...
The number of unacknowledged alarms of a variable associated to a alarm area changes value also if an alarm status without acknowledge will be acknowledged
Summary Counting respects now if alarm has to be acknowledged Description Counting respects now if alarm has to be acknowledged Issue Number: 136794 Fixed on Date: 16.5.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
The web engine delpoyment tools does not accept hostnames that ntart with a numerical
Summary Textbox validation (on keypress) for connector host name / address has been removed. Validation of this setting is done afterwards at deployment step "Validation of settings") Description Textbox validation (on keypress) for connector host ...
When having a project in zenon logic with a local variable which has the STRATON Profil activated and then copying the zenon logic program, an error message appears
Summary When a zenon Logic Program containing variables with profiles is copied, these variables were copied correct without misleading error message. Description When a zenon Logic Program containing variables with profiles is copied, these ...
MODBUS_ENERGY: driver stops communication with all slaves when one slave does not accept TCP data anymore (connection is alive, but received data is not consumed by the slave)
Summary MODBUS_ENERGY driver stops communicating with all slaves when one slave does not accept TCP data anymore (connection is alive, but received data is not consumed by the slave) Description MODBUS_ENERGY driver stops communicating with all ...
Zenon RT chrashes if a time grid is created in PFS
Summary Times can be created. Description Times can be created. Information - Issue Number: 136327 Fixed on Date: 8.5.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
zenon Logic: Weihenstephan Standard Client driver not available any more
Summary Added missing entries. Description Added missing entries. Information With zenon 8.0 there was a change made to use the file "%cd_programdata8000%\straton\IODList_EN.xml" (or IODList_DE.xml, depending on the language of the Logic Editor), in ...
Process Recorder chrash after start with emty records in recorder file
Summary The replay can handle files without any value (image and change). Description The replay can handle files without any value (image and change). Information Do same records for process recorder. Issue Number: 127160 Fixed on Date: 21.6.2018 ...
Not all curves of Block Arrays are displayed in ETM
Summary Curves were not reset correctly. Therefore while drawing them, they were not handled correctly. Description Curves were not reset correctly. Therefore while drawing them, they were not handled correctly. Issue Number: 139498 Fixed on Date: ...
Propose current value" does not work for dynamic text element with "Write set value via: Element""
Summary Actual value is now displayed correctly. Description Actual value is now displayed correctly. Issue Number: 139503 Fixed on Date: 15.6.2018 Versions: 8.00 0 BUILD 48821
Alarm classes assignment gets lost
Summary Global Alarm Classes/Groups in Remas are saved correctly. Was an coding error. during last years changed in the Alarm Class/Group Selection. Remark: New Feature from last year: If Alarm class/Group in global and local Project have the same ...
RT crash after switching from process recording into simulation mode and replay data from a mulit project
Summary The runtime crashed at beginning of process replay if the start time is earlier than what the earliest file contains (including time from image data), which where transferred to the replaying client. In this case only the files of a specific ...
Screen type Time/Lot/Shiftfilter: If you have many lots, screen open takes a long time
Summary Done as wanted . Description Done as wanted . Issue Number: 139407 Fixed on Date: 13.6.2018 Versions: 8.00 0 BUILD 48821
WebEngine: Property 'ParentOfRelatedPicture' of entity type 'RtMdiFilterPartSource' does not exist in meta model.
Summary Because of improvement of Faceplate identification 2 properties were inserted. These properties should be ignored by the Webengine but the problem was that their flags were not set to ignore. Therefore it was not possible to compile projects ...
GIS does not work with the last demo version EE_PRO_SUBSTATION_Energy_8.00_2018-03-19.zip from intranet
Summary Now the GIS configuration made for a 7.60 project is correctly loaded in a newer zenon version in the Editor and also in the Runtime. Description Now the GIS configuration made for a 7.60 project is correctly loaded in a newer zenon version ...
Set value with poke acknowledgment reports some times a false failure in cel
Summary When the set value fail a log message is created Msg: Set value failed! Error: Datapoint:() Error codes: 2 Parameters wrong 3 Negative acknowledge 4 Timeout happens 5 Poke terminated 6 Poke expired 7 Interlocking condition deny poke 8 ...
PFS: delete time could lead to a crash
Summary The times can be deleted correctly. Description The times can be deleted correctly. Information at least there is a different behaviour in zenon 7.60 B 43885 64-Bit An error Message appears instead. Issue Number: 133788 Fixed on Date: ...
Bulk connection transfers initial value twice
Summary Initialize value is for a bulk connection is now only transferred once Description Initialize value is for a bulk connection is now only transferred once Issue Number: 136598 Fixed on Date: 30.5.2018 Versions: 8.00 0 BUILD 48821
AML / CEL display of users that have been deleted leads to the freeze of the runtime
Summary Issue Number: 135083 Fixed on Date: 30.5.2018 Versions: 8.00 0 BUILD 48821
61850 Client - zenon Logic Editor crashes if it loses focus during editing RCB Assignment
Summary Focus loss on edit fields into non-parented windows are handled properly. Description Focus loss on edit fields into non-parented windows are handled properly. Issue Number: 133754 Fixed on Date: 15.5.2018 Versions: 8.00 0 BUILD 48821
Can't start Runtime if editor and runtime are in demo mode and language is French
Summary correct rfrance_u.rc - translation included wrong interpretation of placeholder changes will be merged to 8.10 by using the corrected French VisLoc file Description correct rfrance_u.rc - translation included wrong interpretation of ...
StratonNG Variable has invalid flag for unknown reasons
Summary Variable has invalid flag for unknown reasons Description Variable has invalid flag for unknown reasons Information In the driver configuration on the connection page - set the number of concurrent connections to 1. Issue Number: 142523 Fixed ...
zenon Alarm Management: Explicit detection of Active/Unacknowledged" Alarms from Alarm Status Variable"
Summary Issue Number: 142121 Fixed on Date: 7.8.2018 Versions: 8.00 0 BUILD 50155 | 7.60 0 BUILD 50324
Alarm causes do not work with redundancy
Summary Now alarm causes should continue to work correctly on the Standby when the server goes down Description Now alarm causes should continue to work correctly on the Standby when the server goes down Issue Number: 145857 Fixed on Date: 20.7.2018 ...
OPCUA32: Sampling Interval setting is ignored
Summary The driver setting "sampling interval" has no effect in the runtime. Always the value "0" is used. Description The driver setting "sampling interval" has no effect in the runtime. Always the value "0" is used. Solution The configured sampling ...
zensyssrv crashes during remote transport after rebuilding the connection
Summary deleting memory twice under Special Timing conditions omitted Description deleting memory twice under Special Timing conditions omitted Issue Number: 133326 Fixed on Date: 19.7.2018 Versions: 7.60 0 BUILD 49532 | 8.00 0 BUILD 50155
IEC850: driver stuck while reading ctlModel (CF) for sending command (because data object is a structure?)
Summary reading ctlModel works again with structured DATA Description reading ctlModel works again with structured DATA Issue Number: 142968 Fixed on Date: 17.7.2018 Versions: 7.60 0 BUILD 49532 | 8.00 0 BUILD 50155
OPCUA32: writing a structure variable with a RGM recipe containing a larger amount of variables, causing two write requests for the structure, results in first variables being overwritten with the old" value"
Summary n.a. Description n.a. Solution Writing structure variables now correctly writes all values when multiple write requests are required. Issue Number: 142627 Fixed on Date: 12.7.2018 Versions: 7.60 0 BUILD 49532 | 8.00 0 BUILD 50155