Runtime stop working with dynamic limit text longer than ~1015 characters

Runtime stop working with dynamic limit text longer than ~1015 characters

Summary

When writing a dynamic limit text based on string variable (e.g. via REMA) the runtime stops working if the string exceeds ~1024 characters.

Description

When writing a dynamic limit text based on string variable (e.g. via REMA) the runtime stops working if the string exceeds ~1024 characters.

Information

Workaroud: limit string legth of a variables used in dynamic limit texts to less than 1000 characters. If written external, limit the character length in external source.



Issue Number: 135502
Fixed on Date: 7.5.2018
Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821