Service Engine can no longer be reloaded via Remote Transport
Summary Service Engine isn't reloading if reload is triggered via Remote Transport Description Service Engine isn't reloading if reload is triggered via Remote Transport Issue Number: 240617 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0
Summary Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0 Description Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0 Issue ...
Driver programmed simulation - strings do not work (all strings contain 1" as text) "
Summary When using simulation programmed, all strings contain the value "1". Description When using simulation programmed, all strings contain the value "1". Information no workaround Issue Number: 240334 Fixed on Date: 0.0.0 Versions: 10 0 BUILD ...
Service Engine crashes with data storage evacuation and SG API query
Summary Variable count was not set when reading archive data from Data Storage. This led to arithmetic underflow when decrementing the counter (inside CSGGHistorianRequest::AddArchive2Payload), which in turn led to a memory exception due to ...
SIC: Out of memory Exception, when large files are available in Log folder
Summary The Lines to be displayed on screen were capped to 1000 Description The Lines to be displayed on screen were capped to 1000 Issue Number: 240066 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
System Information Collector (SIC): Does not include installation logs of zenon 10 (software platform)
Summary Software platform setup logs are now collected. Description Software platform setup logs are now collected. Issue Number: 239758 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Setup zenon Software Platform 10 don't installed Engineering Studio via Customize Egde Serices option
Summary Engineering Studio is installed as expected. Description Engineering Studio is installed as expected. Issue Number: 239993 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
system time change CEL entry only contains new time
Summary CEL entry created by function "Read time from variable" is wrong Description CEL entry created by function "Read time from variable" is wrong Issue Number: 239678 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
IEC850 Driver Configuration Wizard: does not work and has unhandled exception
Summary IEC850 Driver Configuration Wizard: does not work and has unhandled exception Description IEC850 Driver Configuration Wizard: does not work and has unhandled exception Issue Number: 239094 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
The AccessDNP3_SG DNP3 Outstation does not correctly set the value of the variable linked for a binary output with control model activation and deactivated command routing
Summary With the AccessDNP3_SG DNP3 Process Gateway and a binary output, configured for the control model "activation" and command routing deactivated, the process gateway sets the value to "0" and does not build a pulse when the master performs a ...
The OPC UA client driver does not allow configuration of the queuesize. A queuesize of 1 is always used, which may result in loss of value changes coming from the OPC UA server
Summary The OPC UA client driver uses a fixed queuesize of 1, which may result in a loss of value changes coming from the OPC UA server. Description The OPC UA client driver uses a fixed queuesize of 1, which may result in a loss of value changes ...
service engine crashes randomly by AD login (while process gateway is active)
Summary ServiceEngine sometimes crashes while processing CEL API event containing user name of AD user Description ServiceEngine sometimes crashes while processing CEL API event containing user name of AD user Information No Workaround. With a ...
SNMPNG: SNMPv3 (Authentication + Encryption) lost communication after device power off
Summary SnmpNg32-V3: Communication is lost and can't be re-established after a device power loss, if Snmp V3 (Authentication + Encryption) is active. Description SnmpNg32-V3: Communication is lost and can't be re-established after a device power ...
IEC850: Sporadic crash when using remote paths for File Transfer
Summary An error message is written, when the file could not be written. Description An error message is written, when the file could not be written. Information To use local paths only and use File Operations function to move the files later. Issue ...
Report viewer: the shift filter will be not applied, if you select Absolute time period" or "Realtive time period""
Summary Internal time filters of a report filter will be validated correctly . Description Internal time filters of a report filter will be validated correctly . Issue Number: 242181 Fixed on Date: 2.7.2021 Versions: 8.20 0 BUILD 85568 | 10 0 BUILD ...
Windows 10 20H2 Update breaks Keyboard Screen
Summary The keyboard will be rendered correctly . Description The keyboard will be rendered correctly . Information Move the Dialog Window, then everything gets rendered correctly Issue Number: 240972 Fixed on Date: 1.7.2021 Versions: 8.20 0 BUILD ...
Editor Crashes by using cross referenz list with Symbols
Summary Sometimes deleting a symbol causes subsequent crashes when refreshing cross-refrence list or editing screens Description Sometimes deleting a symbol causes subsequent crashes when refreshing cross-refrence list or editing screens Issue ...
It should be possible to specify bounds for the cycle time
Summary Issue Number: 241961 Fixed on Date: 30.6.2021 Versions: 8.20 0 BUILD 85568 | 10 0 BUILD 85877 | zenon Analyzer 3.40 0 BUILD 87645
EUROMAP63: improve behavior for empty files
Summary EUROMAP63 - high CPU load with many connections Description EUROMAP63 - high CPU load with many connections Issue Number: 240933 Fixed on Date: 24.6.2021 Versions: 8.20 0 BUILD 85568 | 10 0 BUILD 85877 | zenon Analyzer 3.40 0 BUILD 87645 | ...
IEC870 Master Redundancy according to Ed. 2.0 - send only TestFR Act/Con between Master and Slave
Summary Master doesn't recognize connection loss, if both redundant connections fail simultaneously. Thus no general interrogation is requested and further no spontaneous value changes are transmitted. Description Master doesn't recognize connection ...
IEC60870-5-104 drivers (master and slave) are loosing redundant connection because of errors in START/STOP procedure implementations
Summary When triggering a manual redundancy switch the IEC60870-5-104 master acknowledges outstanding dl-frames after sending STOPDT. This may cause the slave to ignore the ack or even close the master connection. Description When triggering a manual ...
GDI Leak: Batch Control Recipe Editor
Summary Each time Batch Control Recipe Editor is opened 6 GDI objects are leaked Description Each time Batch Control Recipe Editor is opened 6 GDI objects are leaked Issue Number: 242796 Fixed on Date: 15.7.2021 Versions: 8.20 0 BUILD 86192 | 8.00 0 ...
SPRECON870 driver is crashing if more than 22 IOA are communicated in a Reverse Direction Telegram
Summary - Description - Issue Number: 242750 Fixed on Date: 15.7.2021 Versions: 8.20 0 BUILD 86192 | 8.00 0 BUILD 86400 | zenon Analyzer 3.40 0 BUILD 87645 | 8.10 0 BUILD 86641 | 10 0 BUILD 87728 | 7.60 0 BUILD 95308 | 8.10 0 BUILD 95414 | 8.00 0 ...
GDI Leak: Modal dialog & Highlight frame settings leads to a GDI leak after closing the frame
Summary Opening a modal dialog with highlighting screen causes a GDI leak Description Opening a modal dialog with highlighting screen causes a GDI leak Issue Number: 243041 Fixed on Date: 23.7.2021 Versions: 8.00 0 BUILD 86400 | 8.20 0 BUILD 87225 | ...
S7TIA: Variables cannot be imported from TIA project when CPU name contains dots (.)
Summary All Version do not resolve dots (.) as part of CPU-name properly. This leads to problem with importing variables from TIA-projects or pre-compiled projects. With the current bugfix CPU-names containing dots are quoted to recognise it and to ...
RGM: Runtime may crash when variables in a recipe are linked to a visibility variable
Summary Runtime crashes if RGM visbility changes while a set-value keyboard is open Description Runtime crashes if RGM visbility changes while a set-value keyboard is open Issue Number: 242794 Fixed on Date: 21.7.2021 Versions: 8.00 0 BUILD 86400 | ...
S7TIA: improved communication performance
Summary Issue Number: 214306 Fixed on Date: 7.7.2021 Versions: 8.00 0 BUILD 86400 | 10 0 BUILD 85877 | zenon Analyzer 3.40 0 BUILD 87645 | 8.10 0 BUILD 86641 | 7.60 0 BUILD 88730
Systemtext wizard doesn't create 43 systemtexts in different languages
Summary The separator for strings used was "space %d space" this was making wrong string splits. It was fixed by using "%d" as string separators. Description The separator for strings used was "space %d space" this was making wrong string splits. It ...
User duplication is not verified in Customised Edit user screen.
Summary Fixed, i.e. in MDI user screen a user cannot be added twice any more. Description Fixed, i.e. in MDI user screen a user cannot be added twice any more. Information Using PWD_Validate password API function, we have checked list of users and ...
EthernetIP Scanner overloads logic runtime when no connections are established
Summary Ethernet IP Scanner with lost Connection leads to a cycle time increase until the Connection is reastablished. Description Ethernet IP Scanner with lost Connection leads to a cycle time increase until the Connection is reastablished. ...
Crash happens when deleting more than one graphic file in a SOT
Summary Now user is able to delete multiple files from graphics, help, mutlimedia.. etc. of File Manager. Crash is resolved now. Description Now user is able to delete multiple files from graphics, help, mutlimedia.. etc. of File Manager. Crash is ...
Merge Abstraction Layer to zenon 10
Summary Issue Number: 241022 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 85877
T5Bus870Slave - Incorrect response if information in Select and Execute is different
Summary - Description - Issue Number: 214031 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 85877
Wrong SOT version number displayed after update
Summary SOT version number will be persisted after the SOT update, and after closing and reopening the engineering studio it should still be the same as after the update Description SOT version number will be persisted after the SOT update, and after ...
snmp32 driver does not work in version 10
Summary SNMP32 driver does not work in version 10. Description SNMP32 driver does not work in version 10. Information no workaround Issue Number: 242073 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 85877
Sigmatek Lasal Driver cannot read data in zenon 10
Summary Sigmatek Lasal Driver not working in version 10. Description Sigmatek Lasal Driver not working in version 10. Information / Issue Number: 241474 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 85877
Smart Object Update causes unhandeld exception when exiting the Engineering Studio
Summary Crash is not happening anymore when closing the engineering studio after updating a SOT Description Crash is not happening anymore when closing the engineering studio after updating a SOT Information No Workaround found. Issue Number: 241750 ...
AML: Comment for Alarm disappears in Data Storage
Summary The reason for the disappearing comments (and also alarm causes) was that the ringbuffer was not correctly synchronized with historic data when binary files were disabled. Also acknowleding and confirming acknowledge was not correctly ...
Sporadic crash in Service Engine when Identity Service user administration is combined with alarm management via Web Engine
Summary The crash has been fixed by reducing the lock time. Now, the generation of the alarm update via service hub (calls user administration to retrieve the full user name) is done outside the lock. Description The crash has been fixed by reducing ...
Changing Alarms/Events via ServiceGrid API fails if the alarm/event is no longer available in binary files
Summary The read-back-single-item-mechanism was repaired for external storage of AML and CEL. Setting comments on alarms and events, setting alarm causes and acknowleding alarms works now as expected when only external storage is active (except for ...