AML: Comment for Alarm disappears in Data Storage

AML: Comment for Alarm disappears in Data Storage

Summary

The reason for the disappearing comments (and also alarm causes) was that the ringbuffer was not correctly synchronized with historic data when binary files were disabled. Also acknowleding and confirming acknowledge was not correctly updating the ringbuffer in this case. Now, the ringbuffer is correctly kept synchronized and all actions (setting comments, setting alarm causes, acknowleding, confirming acknowledge) work as expected.

Description

The reason for the disappearing comments (and also alarm causes) was that the ringbuffer was not correctly synchronized with historic data when binary files were disabled. Also acknowleding and confirming acknowledge was not correctly updating the ringbuffer in this case. Now, the ringbuffer is correctly kept synchronized and all actions (setting comments, setting alarm causes, acknowleding, confirming acknowledge) work as expected.

Information

Enable local service engine file storage



Issue Number: 241907
Fixed on Date: 0.0.0
Versions: 10 0 BUILD 85877