15
MTP - Support Standard v2.0
The following V2 Services function blocks are now available: AnaServParamV2 TIA BinServParamV2 TIA DIntServParamV2 TIA ProcedureHealthViewV2 TIA ServiceControlV2 TIA StringServParamV2 TIA Manifest 2.0.0MTP files Orchestration now also supports MTP ...
IEC 61850 Configurator: Provide solution in zenon 15
Description [Feature]: The IEC 61850 Configurator was not available in zenon 15. The functional gap has been addressed and now the IEC 61850 Configurator is available in zenon 15. To benefit from this fix: Update your zenon Software Platform to the ...
AccessDNP3_SG: enhanced support for CSV import / CSV export
Description [Feature]: The AccessDNP3_SG Process Gateway CSV export/import function did not support double bit binary inputs. The functional gap has been addressed and the handling of double bit binary inputs is now supported in CSV export/import ...
SNMP Driver crashes due to mismatched agent configuration
Description The SNMP driver closed unexpectedly in some cases. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or higher. Item ID: 305311 ...
Systemvariable Computername displayed in lowercase
Description If the name of the computer was changed to lowercase letters in the Windows settings and a “Computer Name” system variable was created, the name was displayed in uppercase letters in the Service Engine in version 14. The issue has been ...
ETM: Y-Axis automatic scaling changes value range
Description In the ETM the Y-axis changed automatically the scaling range, if the value of the variables was changed a few times. This happened because no value change was found and so the default scale of +- 10% of the variable value range was ...
AD user is not assigned all permission levels with certain configurations
Description The Active Directory user was not assigned to all permission levels with certain configurations. The issue has been addressed and now also the primary user group from the Active Directory, which is also configured in zenon, can be used to ...
zenon SQL driver is not working with PostgreSQL ODBC driver since zenon 14
Description Since zenon version 14 the zenon SQL driver was not working with the PostgreSQL ODBC driver. The issue has been addressed and the driver behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the ...
StratonNG does not treat connection to STARTONRT is redundant Logic Service has switch
Description The stratonNG driver did not treat the connection to STARTONRT as redundant. Under certain circumstances, the driver never switched to the redundant connection, even though one connection had failed and the other was working. The issue ...
Comparison default with protected programs
Description The comparison of two projects did not detect the difference between two Main programs, if the project contains a password-protected subprogram. The issue has been addressed and the comparison behavior is now as expected. To benefit from ...
Limitation to 15 unique characters in long FB Names
Description In Logic Studio, if in the Library a function block name consisted of more than 15 characters and a second function block used the same first 15 characters in its name, an error occurred, creation refused. The issue has been addressed, ...
XML export/import looses some properties
Description During the zenon Logic XML export/import some properties were lost. The issue has been addressed, and the XML export/import behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
Logic Service / StratonNG driver - for specific StratonNG driver zenon versions with a different Logic Service zenon version, reconnects fail
Description In zenon project manually created stratonNG driver fails to reconnect with an older zenon Logic Service version; e.g.: zenon 15 stratonNG driver after the connection loss was unable to reconnect to a Logic Service version below 15. The ...
The editor does not call the OEM editing of K5IOEdit.dll
Description Due to the migration to UNICODE the OEM entry point of custom K5IOEdit.dll was not called anymore since version 14. The issue has been addressed. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon ...
Num_to_string function bad results
Description The NUM_TO_STRING function for float values returned incorrect results in certain cases. The issue has been addressed and the resulting string is filled with “*” now if the REAL/LREAL value is too big or too small. In these cases the ...
BEV Log-Messages get written on stdout instead of using VMPrintf or VMTrace methods
Description When the BEV server was started under Linux and variable events were generated, the LOG message for the connection and for every variable subscription was written into the terminal output, instead of the logging service (controlled via ...
Using FTP Function Block with Windows 10, If the Inferface of the network isn't listed in 1° position doesn't work properly
Description When an FTP function block was used with Windows Server 16 (or higher) or Windows 10 (or higher), the Interface did not work properly if it was not listed first. The issue has been addressed and the Interface works now as expected ...
SQL zenon native driver (SQLDRV) not writing ACK_SRV and ACK_SB in redundancy mode
Description The zenon SQL driver (SQLDRV) did not write ACK_SRV and ACK_SB in redundancy mode. The driver has a "Redundancy" flag in its configuration that has to be activated if it’s supposed that both server and standby have access to the database ...
Secondary empty message box on Batch MR deletion
Description When a Master Recipe which has one or more Control Recipes has been deleted from the Master Recipe List, a secondary empty message box "" was shown. The issue has been addressed and the behavior is now as expected. To benefit from this ...
S7TIA secure connection is not possible
Description The S7TIA secure connection did not work anymore after the update with the zenon 15 Build version "SoftwarePlatform15FinalBuild470206.exe". The issue has been addressed and the S7TIA secure connection works now as expected. To benefit ...
In "IOT2050 docker" LOGIC Service redundancy can not be set
Description In the IOT2050 Docker it was not possible to set the Logic service redundancy. The issue has been addressed and the redundancy can be used now. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 15 ...
Service Engine crash after forcing eSignature multiple times in customer project
Description The Service Engine closed unexpectedly after eSignature was forced multiple times. The issue has been addressed and eSignature now works as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
Combi element does not display symbol in Engineering studio for default value
Description The Combi element did not display the symbol for the default value anymore in the Engineering Studio preview, even though it was displayed correctly in the Service Engine. The issue has been addressed and the Combi element behavior is now ...
Multiuser: Changes in Smart Object Template (Functions) are only applied once, subsequent changes are ignored
Description In distributed engineering projects (Multiuser projects) function changes in the Smart Object Template were only applied once subsequent changes were ignored. The issue has been addressed, and now all changes made in Smart Object Template ...
Switch Palette does not work on screen assign to larger frame in WVS
Description If the screen had higher Width/Height pixels than the frame and Use screen size from frame was disabled, the toggle button for switching the palette did not work in Web Visualization Service. The issue has been addressed, and palette ...
It is not possible to change an expired Active Directory password.
Description If the Active Directory password expired, it could no longer be changed. The issue has been addressed, and the expired password can now be changed again. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
T5BEV - Proposed solution: Add check for Sock != INVALID_SOCKEt in T5BEVFrame_SendEventList or _T5BEVFrame_Send
Description The Service Engine under Linux closed unexpectedly in a test scenario. The issue has been addressed and a check for Sock != INVALID_SOCKET has been added. The behavior is now as expected. To benefit from this fix: Update your zenon ...
Zenon 15 - Command Sequencer triggers undesired ALC interlockings
Description The Command Sequencer triggered randomly undesired ALC interlockings. The issue has been addressed and the behavior is now as expected. It is guaranteed that when interlocking is started, at least one complete ALC calculation cycle (incl. ...
SOT Saving a specific symbol, crashes the Engineering Studio
Description The Engineering Studio could unexpectedly close when there are changes to screen elements of a SOT are getting saved. The issue has been addressed and the SOT symbol can be saved now. To benefit from this fix: Update your zenon Software ...
Profinet Master - the configuration sent to the ET200SP with Profinet S2 is refused by the device
Description When the Profinet Master sent the configuration to the ET200SP with Profinet S2 it was refused by the device. The issue has been addressed, and the communication behavior is now as expected. To benefit from this fix: Update your zenon ...
SQLDRV: Reading an empty string from a database leads to communication loss for all variables of the driver, if the driver is in redundant mode
Description In redundancy mode the SqlDrv driver lost communication to all variables of the driver when an empty string was read from a database. The issue has been addressed and reading behavior now meets expectations and no longer affects ...
DNP3_TG: driver closes unexpectedly on attempt to communicate with UDP communication when an IP address is used containing a leading 0
Description When using the DNP3_TG driver with UDP and an IP address containing a leading 0 (e.g., 192.168.251.048), the driver closes unexpectedly when establishing communication. The issue has been addressed and the driver no longer closes ...
[CHINESE] Bad values during monitoring of chinese symbols
Description If the PC was configured with the language Chinese simplified the Workbench displays incorrect online values of array variables. The issue has been addressed and now the correct variable values are returned. To benefit from this fix: ...
Abnormal General Request Frequency After zenon Redundant Switch in CNet Driver
Description The CNetDrv driver General Request Frequency after a zenon Redundant Switch differed from the selected General Period (200 ms) time. The CNetDrv driver on the PC newly promoted to primary PC sent the general queries every 15 ms. The issue ...
CNet driver recording incorrect values
Description The CNetDrv driver recorded incorrect values (e.g. 0 instead of 1) because the receive buffers in the driver were not reset correctly when the connection was terminated. The issue has been addressed and the recording behavior is now as ...
sporadic crash of Engineering Studio when checking in/out the Project or saving SmartObjectsTemplates in MultiUser projects
Description The Engineering Studio was sporadically unexpected closed, if projects were checked in/out or Smart Objects Templates were saved or updated in multi-user projects. The issue has been addressed and the corresponding behavior is now as ...
Scheduler: After converting from 6.51 to 14, changes to entries are not saved if switch point has no ending time
Description The scheduler did not save the changes to the entries after converting from zenon version 6.51 to zenon version 14 if the switching point did not have an end time. The issue has been addressed and saving changes after converting the zenon ...
SIGMALASAL32: Driver runs into timeout if many variables are configured
Description The SigmaLasal32 driver ran into a timeout if many variables were configured. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 ...
The engineering studio process does not stop completely under specific circumstances.
Description It was not possible to switch between different Engineering Studio versions, as the Engineering Studio appeared to be running in the background under certain conditions. The issue has been addressed and the switching behavior is now as ...
AML/CEL column names are wrong when compiling for a lower version
Description Issues occurred if a zenon project has been compiled to a lower version: In the screen switch function to AML/CEL: the column name for "Alarm/event group" was actually using the column name from "Alarm/event group number". This issue ...