15
zenKeyBlock.exe does not cover multiple monitors (besides primary) while Service Engine is starting up
Description The zenKeyBlock.exe showed its dialog only on the primary monitor, leaving other monitors accessible and allowing OS access because zenKeyBlock.exe did not cover multiple monitors when configured for Service Engine. The issue has been ...
PDF Corruption: Fails on all 32-bit configs and 64-bit 'Print Variable' Deactivated (Doosan Project)
Description In zenon Logic the PDF generation for a customer project failed due to PDF corruption across all 32-bit and 64-bit configurations when using the Print Variable option. This has been addressed and works as expected. To benefit from this ...
SO - no alarm/event group, class or area can be added to a smart object template
Description The alarm/event groups were created in the project but then could not be added to the Smart Object template (SOT) variables because a bug prevented the template from linking to the project's alarm definitions, causing the selections to be ...
ES sporadically crashes after PGW configuration
Description Engineering Studio was sporadically closed after PGW configuration when the logging thread of the DNP3_SG Process Gateway kept running after the gateway's main instance was deleted. The issue has been addressed and the behavior is now as ...
[MSI Interface] Authorization levels variable is overwritten
Description The MSI Interface Authorization levels variable was saved initially but its setting was overwritten to an empty string after opening and saving the Configuration dialog and then reopening the Authorization dialog. The issue has been ...
“Do not include user data for login in CEL entry” does not work in combination with cached credentials
Description With Property Do not include user data for login in CEL entry active the AD-specific login message ‘@Domain Controller not reachable. Attempting login with cached credentials.’ contained the user name. The issue has been addressed and the ...
Orchestration Studio mixes up the configured password in any OPCUA32 driver connection after each new orchestration
Description After re-orchestration the zenon OPCUA32 driver lost the saved password, entered a rapid reconnect loop and quickly exhausted the OPC UA server's session limit. The issue has been addressed and now the behavior is as expected and the ...
AML: Inconsistency in Stop/Continue button behavior regarding cursor reset
Description The behavior of the screen type specific function Stop/Continue of the screen Alarm Message List regarding setting of the focus on a list entry was not consistent with previous versions. It used to jump to the newest entry after clicking ...
CNET: increased heartbeat timeout and application request timeout - changed defaults
Description [Feature]: Configurable heartbeat timeout, application request timeout and reconnect delay, for the CNet driver with increased default values for the timeouts and the reconnect delay. To benefit from this fix: Update your zenon Software ...
Unhandled exception happens when repeating Start and Stop OPC UA driver
Description When stopping communication with a server that had not yet responded to pending requests, the OPCUA32 driver sometimes failed to close the connection properly. This ultimately resulted in an access violation and triggered an exception. ...
Orchestration Studio is crashing on random orchestration state / Generating zenon Logic program error (>64 KB)
Description The Orchestration Studio was closed unexpectedly due to a random orchestration state. The issue has been addressed and the Orchestration Studio works now as expected. To benefit from this fix: Update your zenon Software Platform to the ...
Orchestration of cdpol backup fails: missing Engineering Studio driver OpenDcs and insufficient log message
Description The backup file could not be orchestrated due to a missing Engineering Studio driver OpenDcs. The the log message did not provide sufficient information. The issue has been addressed and the orchestration of the backup file works now as ...
Orchestration Studio Project Synchronisation is not working with a duplicate cleaned project after a new generation
Description The Orchestration Studio Project synchronization did not work with a project with many screens after a new generation. The issue has been addressed and the Orchestration Studio Project synchronization works now as expected. To benefit ...
Orchestration Studio deadlock while generating a specific project with a lot of devices and HMI screens and 2 IOT projects
Description During the generating procedure with a lot of devices and HMI screens and two IOT-projects the Orchestration Studio runs into a deadlock. The issue has been addressed and the generating behavior of the Orchestration Studio is now as ...
Orchestration Studio does not generate a screen if it does not contain an assembly / Project opening HMI synch fails / no HMI screen switch possible
Description Under specific circumstances, like the screen contained no assembly, this screen was not generated by the Orchestration Studio. As a follow up failure, the Orchestration Studio project synchronization failed with this project, because ...
Message Control: messages are queued up due a 10 second delay in the communication process
Description A 10 seconds delay was caused when Message Control messages were sent without authentication and encryption. This is because corresponding mailservers do not expect messages without authentication and encryption. The issue has been ...
variables from subprograms not recognized - syntax changed
Description In zenon Logic, the input and output variables of subprograms are displayed in Fieldbus configurations with "/" but the compiler didn't recognise "/" as a valid symbol. The issue has been addressed and the behavior is now as expected. To ...
OPC_UA client bug with STRING TYPE
Description The OPC UA Client driver was updating STRING variables periodically, instead of on value change. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest ...
API, MultiBinary REMA: First SubCondition can not be directly created by API
Description The first SubCondition of an MultiBinary REMA could not be created using the following API commands: State.CreateSubState(); (COM) / ICondition.Create(); (Addin) (Replied an empty State/ICondition object) ...
Potential reading buffer overrun in lot filter
Description When using the Time/Lot/Shift filter to filter Historian data with separated lots using seperation-characters, the filter was sometimes including more lot-data than intended. The issue has been addressed and the behavior is now as ...
zenon logging server isn't used in IIoT Docker Agent+SE
Description In the zenon6.ini the logging system entry was missing and due to this in the Linux docker Service Engine the logging from Service Engine to the zenon logging server did not work. The issue has been addressed and the logging from Service ...
IEC61850 Server - No integrity reports sent by the stack after dynamic update of Integrity Period.
Description When a IEC61850 Server incl. GOOSE was communicating with a client via enabled RCB, the trigger option integrity was not regarded and the expected integrity reports were not sent. The issue has been addressed and the behavior is now as ...
SOT: Moving folder structure of SOTs leads to Engineering Studio Crash
Description Moving an Smart Object Template main folder into a subfolder was causing the Engineering Studio to close unexpectedly and render the SOT main folder unavailable. The issue has been addressed and the behavior is now as expected. To benefit ...
zenKeyblock shortcut 'WIN + L' locks Win Key
Description The Tool Keyblock Service Engine Start locked the Windows key after the combination Windows + L was used. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to ...
PROFINET IO Controller: Configuration of specific modules with datatype "Octetstring" is not possible. Error: "Unsupported: This module contains Parameter data with unsupported data types."
Description The PROFINET IO Controller driver configuration of specific modules with datatype "Octetstring" was not possible. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software ...
License could not be found, invalid or empty when LOG_CONFIG=DEVICE=TCP/IP;HOST=<host>;PORT=<port>; is added in zenon6.ini
Description A License error occurred when LOG_CONFIG=DEVICE=TCP/IP;HOST=<host>;PORT=<port>; was added to the zenon6.ini. The issue has been addressed and now the official wait method for the start of Codemeter is used before starting the Service ...
The display in AML/CEL does not match the lot selected in the “lot selection dialog.”
Description Selecting specific lots in the lot selection dialog of AML or CEL screens caused additional lots to be displayed that were not selected. This also caused wrong timestamps to be displayed. The issue has been addressed and the behavior is ...
SOT: after XML import of screens, released parameter are getting lost
Description When exporting and importing content via XML from an Smart Object Template, some released properties were missing in the import. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon ...
ETM cursor output list displays incorrect value for minimum and maximum
Description The values for variable minimum and maximum were not correctly displayed in the ETM screen element cursor output list. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software ...
Context menu with Display Ext Trend action, doesn't apply the Style group to the Ext Trend screen when using Smart Client
Description When using the action type Diplay Extended Trend in a network project with a Smart Client, the Smart Client was not properly applying the Syle group linked in the Syle group chart property of the Extended Trend. The issue has been ...
SQL Azure Linked server does not appear in Linked Server-selection of the SQL-Connector
Description The linked SQL Azure server did not appear in the Linked Server-section of the SQL Connector. The issue has been addressed and the inked SQL Azure server is now available. To benefit from this fix: Update your zenon Software Platform to ...
ServiceEngine crashes at archive evacuation with Oracle ODBC driver
Description The Service Engine closed unexpectedly at archive evacuation with Oracle ODBC driver. The issue has been addressed and the Service Engine behavior during archive evacuation is now as expected. To benefit from this fix: Update your zenon ...
Import of DBC file refused due to whitespace character
Description The import of a DBC file did not work due to whitespace character. The issue has been addressed and the import behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 15 or ...
AML: always selects the last item when new item is added regardless of sorting order
Description In the AML always the last item was selected when a new item was added, regardless of sorting order. The issue has been addressed and the sorting behavior is now as expected. To benefit from this fix: Update your zenon Software Platform ...
Remote Transport "Transfer changed Service Engine Files" stops working over 8192 Files
Description The Remote Transport "Transfer changed Service Engine Files" stopped working over 8192 files without any error Message. The issue has been addressed and the Remote Transport works now as expected. To benefit from this fix: Update your ...
PR: Configurable Preloaded WVS Instances for Improved Startup Performance
Description [Feature]: The WVS Ops Manager only started one WVS Client in advance. The functional gap has been addressed and the WVS Ops Manager Controller now offers a configuration how many WVS clients should be started in advance. The Ops-Manager ...
MSI Interface: Message handling part 2
Description [Feature]: The processing of MSI Interface messages has been further improved. The functional gap has been addressed and the MSI Interface Message handling has been improved: trigger values on startup/restart can be ignored, a reset value ...
MSI Interface: Extended Error Handling For Material Flow Messages
Description [Feature]: The MSI Interface error handling for material flow messages has been improved. The functional gap has been addressed and the Error Handling for the following Material Flow Messages has been enhanced: Stock Creation Message, ...
MSI Interface: Language table support
Description [Feature]: The MSI Interface did not support Language tables The functional gap has been addressed and the MSI Interface now supports Language tables in a way that it is possible to configure the desired language in which the content of ...
SPA: Driver does not handle new line continuation with "&" correctly
Description The zenon SPA driver did not handle responses with the New line continuation character (&) correctly. The issue has been addressed and the SPA driver behavior is now as expected. To benefit from this fix: Update your zenon Software ...
Next page