Process Gateway IEC870Slave created in a subproject does not support command direction variables (e.g. T46)

Process Gateway IEC870Slave created in a subproject does not support command direction variables (e.g. T46)

Description

The Process Gateway AccessIEC870Sl, when configured to run in a sub project, failed to accept ASDUs with commands (e.g. T46). It logged them as linked to unknown project variables even though the variables exist in the project. This occurred because there was no ProjectID reference added in the configuration. In the command direction, the Gateway tried to resolve the variables in the scope of the integration project (start project), not of the sub project.

The issue has been addressed and the behavior is now as expected. 

 

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 15 or higher.


Item ID: 318312
Version: 15.00 Build: 646946