15
T5BEV: data loss of ~ 20 seconds after ethernet connection is lost and re-established
Description The stratonNG driver using the "Buffered Event Server" lost buffered data by detection connection was lost. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to ...
Bad copy with drag&drop of a POU having action blocks
Description When action blocks were copied from the main FBD program to another program using drag&drop, the action blocks were not copied correctly. The issue has been addressed and the copying behavior now works as expected. To benefit from this ...
FBD - Print a program using Print Setup other than "Default" leads to unexpected variable "TAG" and "Description" display results
Description Printing an FBD program with a print setting other than Default resulted in unexpected display results for the TAG and Description variables. The issue has been addressed and the printing behavior is now as expected. To benefit from this ...
Equipment model linking for variables is inconsitent due to duplicate key entries - even on new Metadatabases
Description The Equipment Models/Groups from the global project were not consistently linked to variables. Variables and Equipment groups were both present in the metadatabase. The issue has been addressed and the linking behavior is now as expected. ...
Trend Graphic Corruption When Using Cursor with Multiple Archive Variables(4+) and Zoom Out
Description If a zoom out function has been executed in a Trend Graphic Screen with activated cursor and four or more archive variables added the Trend display was graphically corrupted. The issue has been addressed and the zoom behavior is now as ...
Keycombination Does Not Work on Login Screen When Opened via Keycombination and Authorized Function
Description The key combination did not work on a Login Screen if the screen was opened via a key combination and an authorized function. The issue has been addressed and now the key combination works on the Login Screen regardless of how it was ...
Unreachable SQL evacuation server-> SE hang, opening Report Viewer lot selection
Description Due to an unreachable SQL evacuation server, the Service Engine became blocked whenever the Report Viewer’s lot selection was opened in wildcard view. This blockage occurred because the serial list of archives timeouts had to expire. This ...
Bug: Write Error to setVal[SP] on IEC 61850 Server
Description The IEC 61850 Server fieldbus driver accepts the write requests for read-only ('RO') data attributes (variables) with FC=SP; e.g. */setVal[SP]. And it refuses the write requests for data attributes with FC=CF, if SCL-configured as 'Set' ...
Performing eSignature for SetValue ends with a crash
Description When eSignature was executed for a SetValue operation and the last button was clicked, the ESignature screen was successfully closed. However, the execution of the SetValue operation was terminated by an unexpected closure of the Service ...
WVS: SysDrv variables for Set value input not working
Description In the Web Visualization Service opening a keyboard screen for set value input from a dynamic element and using the following system driver variables produced empty results: [Project summary] Variable for set value input [Project summary] ...
Memory leak at API function "SoVariableCollection.ItemByName" at Engeneering Studio
Description The usage of the API function "SoVariableCollection.ItemByName" in projects with a big amount of variables led to massive increase of the required RAM and slowed down the performance of the zenon Engineering Studio. The issue has been ...
Pop Up is Shown twice on WVS
Description When in the Web Visualization Service, a screen switch function was triggered via the screen type specific Action “execute functions” in the Equipment Model Screen, the Pop-up was shown twice in the Web Visualization Service. This problem ...
client in hang state after server ends during file alignment
Description Client got stuck after the server shut down during file alignment. This occoured when: a network project with a single server was used and a variable from intern driver with calculation "local" and a limit that is violated at start up. ...
zenone32.exe does not terminate when closing the Engineering Studio
Description The zenon32.exe was not terminated when the Engineering Studio was closed. The issue has been addressed and the zenon32.exe behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
ETM in WVS: Using PARAM for indexbased substitution of curves is not working
Description The index-based replacement of variables in the Web Visualization Service to replace curves in the extended trend using the PARAM keyword did not work. The curve was not replaced. The issue has been addressed and the curve replacement via ...
Runtime crash after login in migrated projects
Description After the login in migrated zenon projects the Service Engine closed unexpectedly. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
DCS process library (TIA, Logic, Rockwell): Activating SafePosition of *AnaDrv (V1) does incorrectly set drive to maximum speed
Description The OpenDCS function blocks (TIA, zenon Logic and Rockwell) AnaDrv and MonAnaDrv incorrectly set the drive to maximum speed when “Safe Position” was triggered and “SafePos” was set to 1. The issue has been addressed and the function block ...
[MSI Interface] Exception Messages created by using the options available when right-clicking on the data grid, do not open via double-click
Description Exception messages created by using the available options after right-clicking on the data grid could not be opened by double-clicking. The issue has been addressed and the Exception Messages behavior is now as expected. To benefit from ...
[MSI Interface] Double-clicking on the data grid header opens the message
Description With the exception of the Order Parameter Message a click to one of the Message tabs and the selection of one of the messages created/available led to an issue. A subsequent double-click on the data grid header opened the selected ...
[MSI Interface] 'Export XML...' and 'Export all as XML' options are not disabled when the authorization level is set
Description The following MSI options was not disables when the authorization level was set: Export XML Export all as XML Reload The issue has been addressed and the export options behavior is now as expected. To benefit from this fix: Update your ...
[MSI Interface] New/Duplicate options not working for the new message types
Description The New/Duplicate options in the MSI Interface did not work for the following Message types: Material Usage Check Message Stock Consumption Message Stock Creation Message The issue has been addressed and the New/Duplicate behavior is now ...
deleting a structure datatype needs much time
Description Deleting Structure datatypes took a lot of time. The issue has been addressed and now the items are deleted from the highest index to lowest to reduce the number of items to adapt. To benefit from this fix: Update your zenon Software ...
Check for object belonging to EQM model is broken causing unrelated function executions in EQM screen
Description The check for objects, if they belong to an Equipment Model, was broken. This led to the issue with the with the "Execute functions" function of Equipment Model screens, that also functions unrelated to the currently selected model were ...
User can be deleted in the Service Engine User List with the "DEL" key even with no rights
Description The user could be deleted from the Service Engine User List without any rights by pressing the “DEL” key. The issue has been addressed and now the corresponding user rights are required to delete a user from the Service Engine User List. ...
WVS - Combobox: Set values via touch is not possible
Description When a ComboBox was selected on Web Visualization Service via touch gestures, the list with entries was shown, but it was not possible to select an entry. For this reason, it was not possible to carry out any set value actions. The issue ...
OPCUA32 Client Driver: Write Request is sent from Server and Standby after a change in Variables is Reloaded
Description The OPCUA32 Client driver sent a Write Request from the Server and the Standby Server after a change in variables was reloaded. The issue has been addressed and now only the active Server sends a Write Request. To benefit from this fix: ...
SAP: Maintenance Reports cannot be created (on certain days)
Description Because of incorrect date formats, Maintenance reports could not be created via the zenon SAP interface. When an alarm occurred that was configured to trigger a Maintenance report, an error message appeared in the Chronological Event List ...
AccessIec870Sl: specific 870 master times out communicating to the 870 Process Gateway when a large number of variables are used in a sector
Description A specific IEC 60870 master timed out while waiting for the GI activation confirmation and interrupted communication with the AccessIEC870Sl Process Gateway when a large number of variables were used in one sector. The issue has been ...
User group name displayed unnormaly in the user related screen.
Description When a user was edited in the zenon Service Engine and User Groups were repeatedly assigned and unassigned the User Group name became corrupt in some cases and displayed as unreadable characters followed by “(del)”. The issue has been ...
Refresh Stop State Not Retained When Using Screen-Specific Action 'Step back' on Trend Screen
Description When a trend screen was opened that used a relative time with a configured refresh rate, the refresh was still active after stopping the refresh and using twice the drag zoom border function. The issue has been addressed and the screen ...
SO : Centralised group of released properties does not correctly propagate the selection made
Description When any FinalBuild higher than 314353 of zenon 11 was used, in the Smart Object Template when properties from different symbols are grouped into a centralized property group, values assigned in the SOT instance were not propagate ...
Sprecon870: ALT_VAL Bit behaves different depending on used Driver Object Type (PLC Marker vs Group)
Description The behavior of the SPRECON870 driver ALT_VAL bit differed depending on the used Driver Object Type. The issue has been addressed and the ALT_VAL bit behavior is now as expected. To benefit from this fix: Update your zenon Software ...
Service Engine Freeze after creating a user in the Service Engine
Description The zenon Service Engine was frozen after a user was created in the Service Engine. The issue has been addressed and the creation of a user works now as expected. To benefit from this fix: Update your zenon Software Platform to the latest ...
rezepturen.cmp is not created when generating changed SE files
Description The *.CMP file for standard recipes was not created when the changed Service Engine files were generated. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to ...
SE on Client, with network delay to the Server, crashes when opening the Command Processing Screen.
Description The Service Engine on a Client with a network delay to the Server closed unexpectedly when the Command Processing Screen was opened. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your ...
MSI Interface: Extending Exception Messages II
Exception Messages can contain additional information. To this end, the Exception Message Configuration dialog has been enhanced: New Append to system description option group. The following information can also be added to the system description: ...
UA - Case-insensitive usernames on login
New Case sensitive user name property makes it possible to take case sensitivity into account for Users. This concerns: Login Temporary login eSignature If duplicate user names are found when generating Service Engine data, corresponding warning ...
WVS: Support eSignature
The WVS now supports eSignature screens. Limitations: No temporary login No calling up of the Login screen if there is not yet a user for the eSignature signed in. Attention eSignature in WVS does not support screen type-specific actions, such as ...
Seperator for CEL-categories is wrong: "; " instead of ";" is used
Description The categories in the API interface were separated by “ ;” instead of the commonly used “;”. This resulted in an incorrect CEL category and an unsuccessful trigger in the MSI interface. The issue has been addressed and the separator ";" ...
PGW AccessIEC870Slave in 101 balanced, after TF1.2 ack (e.g. E5 char) looses next ASDU if it is already in the reception buffer
Description The zenon Process Gateway AccessIEC870Sl as an IEC 60870-5-101 slave with balanced transmission discarded the serial receive buffer when processing confirmation frames (or single character control). If there were already other frame ...