8.00
Description Tooltip in GIS Integration Tool does not works
Description GIS Integration does not display tooltips with details of the fault location in the Service Engine. The "Fault marker tooltip text" property has been activated in the Engineering Studio. This should display tooltips for fault markers with ...
Alarm classes assignment gets lost
Description Alarm groups and alarm classes from the global project can also be selected in a reaction matrix of a local project. However, after selection via the "Alarm/event group" or "Alarm/event class" option, the selection is discarded when the ...
AddinFramework Bug (Packing of zip files)
Description If a project is built several times, the results for Add-Ins may vary: Sometimes a valid *.scadaAddin file is created, sometimes a corrupted one and sometimes no *.scadaAddin file at all. Cause: If packaging takes longer than 8 seconds, ...
"set value" function in HTML Web Engine
Description When compiling a project for the HTML Web Engine, an error message is displayed for a set value function: "Variable not found." In the HTML Web Engine, the set value cannot be set via a button with this function. The button is not ...
After XML Export and Import the Filter Parameters not correct
Summary If the filter "Linked screens" is used in a screen switch function for a screen of type Faceplate and a screen of a screen container is linked then this is not properly stored with XML expor. This issue has been fixed. Description During XML ...
Empty .txt file is not saved with project backup
Description Empty files are not backed up during a project backup. This behavior was the default behavior for project backups until version 8.20. This resulted in configuration files that had no content not being backed up. This behavior has been ...
Datei32 driver crashes if write folder is set to a file instead of a folder
Summary The File Driver is terminated if a file is specified as the destination instead of a folder. This has been fixed. Description Paths for reading and writing are configured for the FileDriver in the "Settings". The selection dialog only offers ...
Editor crash on RT changeable files import with customer project
Description When importing Service Engine changeable data from the Service Engine into the Engineering Studio, the EngineeringStudio closes unexpectedly if specific detailed views like “users” are open during the import. This issue has been fixed. ...
Editor crash when creating a workspace backup during a couple of screens from more than 1 projects are open
Description When creating a workspace backup in a zenon version from 7.50 to 8.10, the Engineering Studio (aka Editor) may close unexpectedly if screens are open. This occurs, for example, if an open screen contains a .Net ActiveX control or the ...
COLOR_ACKN_MARKER overlay the whole AML entry
Description The COLOR_ACKN_MARKER entry in the project.ini enables the display of two rectangles in the first column of the AML. These flash when alarms are not acknowledged. After acknowledgement, these change to a continuous light. In zenon 7.60 ...
Can't start Runtime if editor and runtime are in demo mode and language is French
Description If zenon is used in demo mode and in French, the Service Engine (aka "Runtime") cannot be started from the Engineering Studio (aka "Editor"). Just an error message is displayed, the start is prevented. This error has been fixed. The ...
SICAM230 Conversion wizard: IEC61850 cannot be converted to IEC850 variables
Description When converting a SICAM® 230 project to a zenon project with the SICAM® Conversion Wizard, IEC61850 variables are not converted to IEC850 variables. A warning is displayed. This behavior has been changed. IEC61850 variables are now ...
SICAM230 Conversion wizard: Siemens IEC61850 driver(s) cannot be converted
Description When converting a SICAM® 230 project to a zenon project using the SICAM® Conversion Wizard, the Siemens IEC61850 driver is not converted correctly. No driver connections are created. Variables are not linked to the new IEC850 driver ...
SICAM230 Conversion Wizard: AK_DRV connections are not converted to IEC870
Description When converting a SICAM® 230 project to a zenon project with the SICAM® Conversion Wizard, the connection to the AK driver is not converted to IEC870. The project contains all needed variables but no connections. This behavior has been ...
SICAM230 Conversion Wizard: Variables cannot be displayed in screen
Description When converting a SICAM® 230 project into a zenon project with the SICAM® Conversion Wizard, some variables are not displayed in the screen. Cause: These variables contain the character #. This character is forbidden for zenon variable ...
SICAM230 Conversion Wizard: ErrorOutput - Unable to convert Command Processing symbols
Description When converting a SICAM® 230 project to a zenon project using the SICAM® Conversion Wizard, command processing symbols are not converted correctly. Therefore, no command processing groups are created. This behavior has now been changed. ...
SICAM230 Conversion Wizard: Command Processing group contains empty conditions
Description When converting a SICAM® 230 project into a zenon project with the SICAM® Conversion Wizard, the project contains empty conditions for command group actions. This behavior has been changed. Command groups actions are converted correctly ...
SICAM230 Conversion Wizard: Command Processing group interlocking link is empty causing the command group not being built
Description When converting a SICAM® 230 project into a zenon project with the SICAM® Conversion Wizard, the interlocking link remains empty. Thus, the command group cannot be created by the wizard. This behavior has been changed. Command groups are ...
SICAM230 Conversion Wizard: Command Processing element actions Command ON/OFF or set value should not be created when unused in SICAM230
Description When converting a SICAM® 230 project into a zenon project with the SICAM® Conversion Wizard, commands for actions are set to ON or OFF in the zenon project, although they are not used in SICAM® 230. This behavior has been changed. Unused ...
SICAM230 Conversion Wizard: Command Processing element interlockings are not converted correctly
Description When converting a SICAM® 230 project into a zenon project with the SICAM® Conversion Wizard, interlocking in Command Processing is not converted correctly. Cause: Variables are not correctly associated with interlocking and are not taken ...
SICAM230 Conversion Wizard: SICAM230 Command Processing element not converted if inside a symbol
Description When converting a SICAM® project to a zenon project with the SICAM® 230 Conversion Wizard, some screen elements are not converted. Cause: Elements that are located in a symbol are not considered during the conversion. This behavior has ...
Scheduler in compatibility mode isnt working
Description Creating schedules does not work in compatibility mode. For example, Service Engine files (Runtime files) are created in version 7.60 for 6.22 SP1. The server is started in version 6.22 SP1, and the client is started in version 7.60. If ...
zenon crashes using Scheduler in Compatibility Mode
Description When using the Scheduler, the Service Engine (Runtime) crashes in compatibility mode. For example, Service Engine files are created in version 7.60 for 7.11. The server is started in version 7.11, the client in version 7.60. If an entry ...
Under specific circumstances the recipe value list element of the recipe group manager screen does not show the correct value in the Runtime.
Summary The recipe value list element in the recipe group manager screen may show values with the decimal digits truncated after executing a measuring unit conversion function in the Runtime. DescriptionThe recipe value list element in the recipe ...
The system variables of Process Recorder may not have any value in the Runtime.
Summary System variables of Process Recorder may not display any value in the Runtime after they have been added to the project and the Runtime was reloaded online. DescriptionSystem variables of Process Recorder may not display any value in the ...
It may happen that a change in the reaction matrices node in the Editor is not applied in the Runtime.
Summary A new version of the remas.cmp file may not be created after copy and pasting a reaction matrix in the Editor, so that the change is not applied in the Runtime. DescriptionA new version of the remas.cmp file may not be created after copy and ...
Diagnosis Viewer should provide more information when a screen switch function cannot be executed in the Runtime.
Summary There is not enough information to the user when a screen switch function cannot be executed in the Runtime, so that is not possible to identify the target screen. DescriptionThere is not enough information to the user when a screen switch ...
The Editor may close unexpectedly when renaming a project with VBA disabled.
Summary The Editor may close unexpectedly after renaming a project through the project tree or the properties window when VBA is disabled in the zenon6.ini file. DescriptionThe Editor may close unexpectedly after renaming a project through the ...
The Editor may not display the preview of WPF files.
Summary The Editor may not display the preview of WPF files in the project graphics list. DescriptionThe Editor may not display the preview of WPF files in the project graphics list. Solution The issue has been fixed. Issue Number: 37446 Fixed on ...
It may happen that the "Export selected XML..." option is missing in the context menu of the Interlockings module in the Editor.
Summary It may happen that the "Export selected XML..." option is missing in the context menu of the Interlockings module when selecting a single interlocking in the Editor. DescriptionIt may happen that the "Export selected XML..." option is missing ...
zenPG ICCP TASE.2: when remote ICCP-Server refuses association then the Client constantly attempts to reconnect.
Summary zenon Process Gateway ICCP TASE.2: If remote ICCP-Server is available via TCP but rejects the socket connection, then the Client constantly attempts to reconnect (every ~50ms). When succesfully associated connection is broken then the zenPG ...
Under specific circumstances the Runtime increases the memory usage after reloading.
Summary The memory consumption of the Runtime may increase when reloading the project online after adding a new driver and variable to the project. DescriptionThe memory consumption of the Runtime may increase when reloading the project online after ...
When importing a screen in XML format the message box "Name already exists!" pops-up in inadvertently.
Summary When importing a screen in XML format in the Editor containing elements with the same name the message box "Name already exists!" pops up. DescriptionWhen importing a screen in XML format in the Editor containing elements with the same name ...
The preview of EMF image files may not be displayed in the Editor.
Summary The preview of EMF image files may not be displayed in the project Graphic files detailed view and in the file selection dialog in the Editor. DescriptionThe preview of EMF image files may not be displayed in the project Graphic files ...
In specific circumstances the system driver variables may not be updated in the Runtime.
Summary System driver variables may show wrong or outdated values in the Runtime when they are added by executing the "Reload project online" function. DescriptionSystem driver variables may show wrong or outdated values in the Runtime when they are ...
COMTRADE Viewer should be able to open disturbance files with any start index.
Summary COMTRADE Viewer WPF should be able to open disturbance DAT files with any start index. DescriptionCOMTRADE Viewer WPF should be able to open disturbance DAT files with any start index. Solution COMTRADE Viewer can now open disturbance files ...
Pipe screen element may disappear in the Editor.
Summary Pipe elements with two points, no curves, and shadow may disappear in the Editor when setting the rounding property to a value higher than 0. DescriptionPipe elements with two points, no curves, and shadow may disappear in the Editor when ...
On XML import of the functions "Close frame" and "Close screen" may be shown ??? in the detail list in the Editor.
Summary The parameter "Calling frame (screen)" may be lost when importing via XML the function "Close frame (screen)", being displayed ??? in the detail view in the Editor. DescriptionThe parameter "Calling frame (screen)" may be lost when importing ...
COMTRADE Viewer may display incorrectly specific curves in the Runtime.
Summary COMTRADE Viewer (WPF Element) may display incorrectly specific curves in the Runtime. DescriptionCOMTRADE Viewer (WPF Element) may display incorrectly specific curves in the Runtime. Solution The issue has been fixed so that the curves are ...
COMTRADE Viewer does not display Umlauts correctly in the Runtime.
Summary COMTRADE Viewer does not display Umlauts correctly in the Runtime. DescriptionCOMTRADE Viewer does not display Umlauts correctly in the Runtime. Solution The issue has been resolved. Issue Number: 37279 Fixed on Date: 16.11.2016 Versions: ...