ProfiNet IO RT Controller: Configure slots with Turck GSDML file not possible. Error: "Unsupported: This module contains Parameter data with unsupported data types."
Description The PROFINET IO RT Controller did not support the slots configuration with Turck GSDML file. The issue has been addressed and the slot configuration behavior now works as expected. To benefit from this fix: Update your zenon Software ...
K5B: document the PRJTOUTF8 call in help
Description In zenon Logic the PRJTOUTF8 call was missing in the help and has been added. The issue has been addressed and K5B PRJTOUTF8 <ProjectPath> call has been converted to UTF8. To benefit from this fix: Update your zenon Software Platform to ...
STRATONRT: established broken TCP connections are not closed correctly causing a denial of service when the maximum number of 16 connections is reached
Description The zenon Logic Service on Linux did not accept new TCP connections to the main port for a period of two hours as broken TCP connections were not correctly recognized under specific circumstances and were kept in a half closed state and ...
T5BEVServer: not initialized memory causing random values to be stored
Description The Logic Service communicating changes via the buffered event server sent incorrectly formatted events under specific circumstances following a reconnect of the stratonNG driver. This issue has been addressed and in addition the Logic ...
IEC870_103 driver does not set value, status and timestamp when there is no connection after Service Engine start
Description The IEC870_103 driver did not set the value, status or timestamp when no connection was established after the Service Engine started. The issue has been addressed and the IEC870_103 driver behavior is now as expected. To benefit from this ...
T5BEV : IOT2050 lost on localhost connection after Buffered connection is lost
The IOT2050 Device with Siemens Industrial OS lost on localhost Unbuffered connection after remote Buffered connection was lost. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software ...
Beckhoff NG driver: Import does not work correctly in Version 11
Description The BeckhNG driver variable import did not work correctly. The import dialog did not display all variables available in the *.TPY file. The issue has been addressed and the variable import behavior now works as expected. To benefit from ...
Duplicate equipment group links break metadata synchronization to Asset Modeling
Description When an equipment group was linked more than once to a variable, archive, ... this resulted in the error message "the object to add is already used in this association" in metadata synchronization to Asset Modeling. The issue has been ...
stratonNG driver loses status information of variables which are not BEV Buffering active after Server and IoT (Logic Server) network breakdown
Description The stratonNG driver lost the status information of variables which were not BEV buffered after a network breakdown between the Server and the IoT (Logic Server). The issue has been addressed and the status information is now transmitted ...
CDProtDrv: zenon Logic Studio cannot access CDProtDrv (Can not connect CDProtDrv driver!) in Engineering Studio x64
Description In zenon Engineering Studio x64 the zenon Logic Studio could not connect to CDProtDrv driver. The issue has been addressed and the connection now works as expected. To benefit from this fix: Update your zenon Software Platform to the ...
Deadlock cancelling remote transport in network topology view
Description When a large project was transferred via Remote transport using the network topology, and the Cancel button was clicked in the progress bar during this process, a deadlock could occur. The issue has been addressed and the project transfer ...
Active Directory: Not possible to change user password when password expires
Description The user password in the Active Directory could not be changed after expiration. The issue has been addressed and the password can be changed now after expiration. To benefit from this fix: Update your zenon Software Platform to the ...
T5BEV: data loss of buffered events with T5MRT.exe with -evlatency=10 and T5BevClient.exe
Description The stratonNG driver lost connection with smaller evlatency as a default to Logic Service. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build ...
T5BEV: data loss of ~ 20 seconds after ethernet connection is lost and re-established
Description The stratonNG driver using the "Buffered Event Server" lost buffered data by detection connection was lost. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to ...
Bad copy with drag&drop of a POU having action blocks
Description When action blocks were copied from the main FBD program to another program using drag&drop, the action blocks were not copied correctly. The issue has been addressed and the copying behavior now works as expected. To benefit from this ...
FBD - Print a program using Print Setup other than "Default" leads to unexpected variable "TAG" and "Description" display results
Description Printing an FBD program with a print setting other than Default resulted in unexpected display results for the TAG and Description variables. The issue has been addressed and the printing behavior is now as expected. To benefit from this ...
Equipment model linking for variables is inconsitent due to duplicate key entries - even on new Metadatabases
Description The Equipment Models/Groups from the global project were not consistently linked to variables. Variables and Equipment groups were both present in the metadatabase. The issue has been addressed and the linking behavior is now as expected. ...
Trend Graphic Corruption When Using Cursor with Multiple Archive Variables(4+) and Zoom Out
Description If a zoom out function has been executed in a Trend Graphic Screen with activated cursor and four or more archive variables added the Trend display was graphically corrupted. The issue has been addressed and the zoom behavior is now as ...
Keycombination Does Not Work on Login Screen When Opened via Keycombination and Authorized Function
Description The key combination did not work on a Login Screen if the screen was opened via a key combination and an authorized function. The issue has been addressed and now the key combination works on the Login Screen regardless of how it was ...
Unreachable SQL evacuation server-> SE hang, opening Report Viewer lot selection
Description Due to an unreachable SQL evacuation server, the Service Engine became blocked whenever the Report Viewer’s lot selection was opened in wildcard view. This blockage occurred because the serial list of archives timeouts had to expire. This ...
Bug: Write Error to setVal[SP] on IEC 61850 Server
Description The IEC 61850 Server fieldbus driver accepts the write requests for read-only ('RO') data attributes (variables) with FC=SP; e.g. */setVal[SP]. And it refuses the write requests for data attributes with FC=CF, if SCL-configured as 'Set' ...
Performing eSignature for SetValue ends with a crash
Description When eSignature was executed for a SetValue operation and the last button was clicked, the ESignature screen was successfully closed. However, the execution of the SetValue operation was terminated by an unexpected closure of the Service ...
WVS: SysDrv variables for Set value input not working
Description In the Web Visualization Service opening a keyboard screen for set value input from a dynamic element and using the following system driver variables produced empty results: [Project summary] Variable for set value input [Project summary] ...
Memory leak at API function "SoVariableCollection.ItemByName" at Engeneering Studio
Description The usage of the API function "SoVariableCollection.ItemByName" in projects with a big amount of variables led to massive increase of the required RAM and slowed down the performance of the zenon Engineering Studio. The issue has been ...
Pop Up is Shown twice on WVS
Description When in the Web Visualization Service, a screen switch function was triggered via the screen type specific Action “execute functions” in the Equipment Model Screen, the Pop-up was shown twice in the Web Visualization Service. This problem ...
client in hang state after server ends during file alignment
Description Client got stuck after the server shut down during file alignment. This occoured when: a network project with a single server was used and a variable from intern driver with calculation "local" and a limit that is violated at start up. ...
zenone32.exe does not terminate when closing the Engineering Studio
Description The zenon32.exe was not terminated when the Engineering Studio was closed. The issue has been addressed and the zenon32.exe behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
ETM in WVS: Using PARAM for indexbased substitution of curves is not working
Description The index-based replacement of variables in the Web Visualization Service to replace curves in the extended trend using the PARAM keyword did not work. The curve was not replaced. The issue has been addressed and the curve replacement via ...
Runtime crash after login in migrated projects
Description After the login in migrated zenon projects the Service Engine closed unexpectedly. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of ...
DCS process library (TIA, Logic, Rockwell): Activating SafePosition of *AnaDrv (V1) does incorrectly set drive to maximum speed
Description The OpenDCS function blocks (TIA, zenon Logic and Rockwell) AnaDrv and MonAnaDrv incorrectly set the drive to maximum speed when “Safe Position” was triggered and “SafePos” was set to 1. The issue has been addressed and the function block ...
[MSI Interface] Exception Messages created by using the options available when right-clicking on the data grid, do not open via double-click
Description Exception messages created by using the available options after right-clicking on the data grid could not be opened by double-clicking. The issue has been addressed and the Exception Messages behavior is now as expected. To benefit from ...
[MSI Interface] Double-clicking on the data grid header opens the message
Description With the exception of the Order Parameter Message a click to one of the Message tabs and the selection of one of the messages created/available led to an issue. A subsequent double-click on the data grid header opened the selected ...
[MSI Interface] 'Export XML...' and 'Export all as XML' options are not disabled when the authorization level is set
Description The following MSI options was not disables when the authorization level was set: Export XML Export all as XML Reload The issue has been addressed and the export options behavior is now as expected. To benefit from this fix: Update your ...
[MSI Interface] New/Duplicate options not working for the new message types
Description The New/Duplicate options in the MSI Interface did not work for the following Message types: Material Usage Check Message Stock Consumption Message Stock Creation Message The issue has been addressed and the New/Duplicate behavior is now ...
deleting a structure datatype needs much time
Description Deleting Structure datatypes took a lot of time. The issue has been addressed and now the items are deleted from the highest index to lowest to reduce the number of items to adapt. To benefit from this fix: Update your zenon Software ...
Check for object belonging to EQM model is broken causing unrelated function executions in EQM screen
Description The check for objects, if they belong to an Equipment Model, was broken. This led to the issue with the with the "Execute functions" function of Equipment Model screens, that also functions unrelated to the currently selected model were ...
User can be deleted in the Service Engine User List with the "DEL" key even with no rights
Description The user could be deleted from the Service Engine User List without any rights by pressing the “DEL” key. The issue has been addressed and now the corresponding user rights are required to delete a user from the Service Engine User List. ...
WVS - Combobox: Set values via touch is not possible
Description When a ComboBox was selected on Web Visualization Service via touch gestures, the list with entries was shown, but it was not possible to select an entry. For this reason, it was not possible to carry out any set value actions. The issue ...
OPCUA32 Client Driver: Write Request is sent from Server and Standby after a change in Variables is Reloaded
Description The OPCUA32 Client driver sent a Write Request from the Server and the Standby Server after a change in variables was reloaded. The issue has been addressed and now only the active Server sends a Write Request. To benefit from this fix: ...
SAP: Maintenance Reports cannot be created (on certain days)
Description Because of incorrect date formats, Maintenance reports could not be created via the zenon SAP interface. When an alarm occurred that was configured to trigger a Maintenance report, an error message appeared in the Chronological Event List ...