8.10
3D Configurator cannot open .STEP files that contain japanese characters in their path
Summary It is now possible to open a * .step file in a folder with Japanese characters Description It is now possible to open a * .step file in a folder with Japanese characters Information Move to a folder that doesn't contain japanese characters or ...
zenon function Move Focus" dont set the focus on all native Element types in a picture"
Summary IElement.hWnd returned 0 for ComboListbox and WPF screen element Description IElement.hWnd returned 0 for ComboListbox and WPF screen element Information The only possible workaround is work with Handles and with WindowsAPI in order to set ...
Command Processing: the command interlocking text will not be translated
Summary The Text is now Translateable Description The Text is now Translateable Issue Number: 186585 Fixed on Date: 24.6.2019 Versions: 8.00 0 BUILD 59775 | 8.10 0 BUILD 59911
&" symbol is displayed as _ in CEL and AML list"
Summary The '&' character will be drawn correctly . Description The '&' character will be drawn correctly . Information If you use "&&" it will be displayed with one "&". Example: in the editor: in the runtime: Issue Number: 186609 Fixed on Date: ...
Importing elements from XML loses leading and trailing spaces.
Summary Whitespaces are preserved when importing. Description Whitespaces are preserved when importing. Issue Number: 149933 Fixed on Date: 7.6.2019 Versions: 8.00 0 BUILD 59775 | 8.10 0 BUILD 59911
Combi element set as momentary switch does not reset his state with multitouch gesture
Summary Combi element is not reset if in multitouch configuration a second touchpoint is hit. Description Combi element is not reset if in multitouch configuration a second touchpoint is hit. Information With a zenon standard button the behaviour is ...
Shift Management : silent crash with VSTA Code
Summary The passed interfaces of the event parameters will be released correctly by zenon . Description The passed interfaces of the event parameters will be released correctly by zenon . Information We are testing mixed solution : - Events in Addin ...
Azure Process Gateway is sending out-dated data after RT reload
Summary If VBA is reloaded Azure process gateway stops updating variable values. Description If VBA is reloaded Azure process gateway stops updating variable values. Information Restart Process Gateway after Runtime Reload. Issue Number: 189108 Fixed ...
AccessICCP: unusually high CPU load of the AccessICCP process gateway (doing nothing)
Summary An issue was addressed that resolves a high CPU load in idle mode. Description An issue was addressed that resolves a high CPU load in idle mode. Issue Number: 187563 Fixed on Date: 23.7.2019 Versions: 7.60 0 BUILD 59794 | 8.00 0 BUILD 59775 ...
Beckhoff NG driver imports arrays wrong
Summary BeckhNG driver - symbols from tpy file imported with wrong data type Description BeckhNG driver - symbols from tpy file imported with wrong data type Issue Number: 183004 Fixed on Date: 18.7.2019 Versions: 7.60 0 BUILD 59794 | 8.00 0 BUILD ...
WebClient always shows the PFS athough the Scheduler is licensed
Summary WebClient has a hardcoded PFS license even if server runs with scheduler Description WebClient has a hardcoded PFS license even if server runs with scheduler Issue Number: 187929 Fixed on Date: 7.8.2019 Versions: 8.00 0 BUILD 59775 | 8.10 0 ...
Restore a backup of a global project causes corruption of the project when there are present symbols with released properties
Summary The graphic files are closed as soon as they have been read . Description The graphic files are closed as soon as they have been read . Issue Number: 190038 Fixed on Date: 26.7.2019 Versions: 8.00 0 BUILD 59775 | 8.10 0 BUILD 59911
STRATONRT: T5BusIec850s: zenon logic runtime closes unexpectedly on receipt of an invalid request
Summary All incoming MMS messages are now length checked so no beyond the application assured memory is accessed. Description All incoming MMS messages are now length checked so no beyond the application assured memory is accessed. Issue Number: ...
zenon Webclient stuck/doesn't synchronise if started with Internet Explorer
Summary WebClient cannot connect to server if it is started a second time in same Internet Explorer tab. Description WebClient cannot connect to server if it is started a second time in same Internet Explorer tab. Information Use ...
IEC870 Driver reject commands depending on successfull general interogation
Summary driver allows send of a command already while initial general interrogation. Description driver allows send of a command already while initial general interrogation. Issue Number: 185708 Fixed on Date: 16.7.2019 Versions: 8.00 0 BUILD 59775 | ...
Extended Trend: Mouse/Touch zoom/scroll does not load other archive data if theres a data gap
Summary If zoomed out or scrolled by mouse historic data is not re-loaded. Description If zoomed out or scrolled by mouse historic data is not re-loaded. Issue Number: 187773 Fixed on Date: 15.7.2019 Versions: 8.00 0 BUILD 59775 | 8.10 0 BUILD 59911
Exceptions (Alarms) cannot be processed by the 3S_V3 driver with PLCHandler 3.5.12.0 when communicating to ABB AC500 PM5650
Summary Exceptions (Alarms) cannot be processed by the 3S_V3 driver with PLCHandler 3.5.12.0 when communicating to ABB AC500 PM5650 Error log: ERROR: : '' has invalid Size (Size = 110 Bytes, Buffer Size = 112 Bytes) Description Exceptions (Alarms) ...
CD_SVA_2019_5: COPA-DATA editor - security vulnerabilty addressed
Summary Solution COPA-DATA has received a report by Yongjun liu of nsfocus security team, through a COPA-DATA OEM customer, detailing a security vulnerability in the COPA-DATA zenon editor software and OEM versions of this software. The following ...
State Name table is empty
Summary Due to a problem in reading out binary and multi-binary reaction matrices, the Analyzer Export Wizard for 2.10 - 3.40 could not process state lists from binary or multi binary reaction matrices. Now, they are treated correctly. Description ...
some texts of system language are not translated
Summary The header and combobox entries will be translated . Description The header and combobox entries will be translated . Issue Number: 192015 Fixed on Date: 20.8.2019 Versions: 8.10 0 BUILD 59911
Alarms with delay are trigged before delay is elapsed
Summary The delays times will be calculated more accurate . Description The delays times will be calculated more accurate . Issue Number: 191799 Fixed on Date: 14.8.2019 Versions: 8.10 0 BUILD 59911 | 8.00 0 BUILD 60081 | 7.60 0 BUILD 60281
Archive Export function shows time filter dialog unexpectedly in the runtime
Summary If a time period filter in archive export function is configured then it can be that the options to enable or disable the runtime dialog are both diabled in the editor. Also there is a dialog showing up in the RT even though it was not ...
AccessICCP: process gateway as ICCP server - 8.10 and 8.20 no longer correctly save variable settings for command variables
Summary AccessICCP: process gateway as ICCP server - 8.10 and 8.20 no longer correctly save variable settings for command variables Description AccessICCP: process gateway as ICCP server - 8.10 and 8.20 no longer correctly save variable settings for ...
AccessModbus: Process Gateway closes unexpectedly on receiving an invalid request
Summary When the AccessModbus Process Gateway receives a specific invalid modbus request, the process gateway closes unexpectedly. Description When the AccessModbus Process Gateway receives a specific invalid modbus request, the process gateway ...
zenon Setup removes valid license from top position in license.ini
Summary - Description - Issue Number: 187940 Fixed on Date: 4.7.2019 Versions: 8.10 0 BUILD 59911
OPCUA32: Information on StructureTypeNodeId and ParentNodeId for addressing of extension objects is stored in the incorrect fields in the .plccache file
Summary Information on StructureTypeNodeId and ParentNodeId for addressing of extension objects is stored in the incorrect fields in the .plccache file. The information that should be in the ParentNodeId field is listed in the StructureTypeNodeId and ...
IProject::NetSend when used with arrays runtime stops working
Summary - Description - Issue Number: 181329 Fixed on Date: 24.6.2019 Versions: 8.10 0 BUILD 59911
AddInFramework calls with return array with null values throw ArgumentException: Value cannot be null
Summary QueryBlock and QueryBlockEx throw an exception when used in AddIn and result set is empty Description QueryBlock and QueryBlockEx throw an exception when used in AddIn and result set is empty Information Bypass the AddInFramework by making ...
Service Hub - Enable secure control layer for client authentication and authorization in a first version
Summary Issue Number: 148161 Fixed on Date: 17.6.2019 Versions: 8.10 0 BUILD 59911
the editor crashes after importing and then deleting phases with leading spaces in thier names
Summary Importing phases works as expected. Units where affected as well. Leading spaces had no effect on that problem. Description Importing phases works as expected. Units where affected as well. Leading spaces had no effect on that problem. Issue ...
zenrt32: runtime on the runtime server with specific project closes unexpectedly after a client connects when 7.60 compiled runtime files are used
Summary Server runtime crashes when receiving outdated client advise command from clients of version 7.60 or below. Description Server runtime crashes when receiving outdated client advise command from clients of version 7.60 or below. Issue Number: ...
incorrect values are written to variables by inherited reactions
Summary When using reactions to write values to tags in phases of unit classes, it may happen that incorrect values are written. This issue has been resolved. Description When using reactions to write values to tags in phases of unit classes, it may ...
AddInFramework calls with enum array out parameters throw exception: Object cannot be stored in an array of this type.
Summary The following api methods now work correctly in the Addin Framework: - IRuntimeArchiveFilter.QueryBlock(out string[] projectName, out int[] ids, out AggregationType[] aggregationTypes, out object[] values) - ...
DATEI32v2 driver: Reading binary v2 file fails - message unknown datatype
Summary - Description - Information - Issue Number: 192545 Fixed on Date: 27.8.2019 Versions: 8.00 0 BUILD 60081 | 8.10 0 BUILD 60592
Energy: Driver Simulation Wizard does not compile Logic code & creates too big programs
Summary The wizard did not compile the program cause he missed writing the variables in use to the appli.k5p file. In addition the wizard now splitts the programs into chunks of 100 variables, per simulation. Description The wizard did not compile ...
Communication with IEC870 driver in serial mode (101) is no longer possible to devices which do not support RTS_CONTROL_TOGGLE
Summary Serial interface is initialized with RTS_CONTROL_TOGGLE flag Description Serial interface is initialized with RTS_CONTROL_TOGGLE flag Issue Number: 192664 Fixed on Date: 26.8.2019 Versions: 8.00 0 BUILD 60081 | 8.10 0 BUILD 60592
move symbol" element does not move "line" elements inside the symbol"
Summary "Move Symbol" screen element doesn't move lines Description "Move Symbol" screen element doesn't move lines Information Don't use the outdated "move Symbol" element. Use e.g. movement properties inside the Symbols itself. Issue Number: 195547 ...
The max. amount of connections the EthernetIP Scanner can establish to EthernetIP Adapters is fixed at 30
Summary The EthernetIP Scanner in zenon Logic can open 30 Connections to EthernetIP Adapters max. Suggestion is to increase this Limit of 64 Connections. Description The EthernetIP Scanner in zenon Logic can open 30 Connections to EthernetIP Adapters ...
The Ethernet IP I/O Scanner does not reconnect properly if several Adapters are connected and rebooted
Summary In case of a network loss or Ethernet IP adapter is unpowered, it could happen in installations >3 Ethernet IP adater that some of the adapters are not reconnecting properly. Description In case of a network loss or Ethernet IP adapter is ...
Process Gateway SNMP: AccessSNMP.dll is missing or misconfigured
Summary Due to a wrong dependency specification, the SNMP process gateway dll "AccessSNMP.dll" could not be loaded by the Windows SNMP service. The dependency is now specified correctly and the process gateway works as expected. Description Due to a ...
Next page