The OpenDCS function blocks (TIA, zenon Logic and Rockwell)
AnaDrv and
MonAnaDrv incorrectly set the drive to maximum speed when “Safe Position” was triggered and “SafePos” was set to
1.
The issue has been addressed and the function block behavior is now as expected.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 14 or higher.