8.00
VACO stops working after a while
Summary Avoid overflows on timer Description Avoid overflows on timer Issue Number: 158507 Fixed on Date: 12.12.2018 Versions: 7.60 0 BUILD 55240 | 7.50 0 BUILD 55804 | 8.00 0 BUILD 55271
Scheduler in compatibility mode isnt working
Summary Server with old version can create schedules that are recognized on newer client. Description Server with old version can create schedules that are recognized on newer client. Information None Issue Number: 156468 Fixed on Date: 20.11.2018 ...
Time filter screen: RT crash when in the screen switch is defined Relative Period with >31 days and Interval period filter applicated
Summary If the time filter type is changed only in some cases the defined date and time fits to the new time filter type. Because the different time filter types do share their time filter controls some of them now have invalid values. Now we changed ...
ETM: Timefilter option is greyed out after project conversion 7.50 -> 8.00
Summary On project conversion, the correct setting for not displaying the filter dialog for the timeperiod is set now Description On project conversion, the correct setting for not displaying the filter dialog for the timeperiod is set now ...
T70 and T105 cannot be mapped in the IEC60870S and IEC60870S2 Profiles
Summary TID 70 and TID 105 is missing in selection Description TID 70 and TID 105 is missing in selection Information Simply add the two Following lines in the IEC60870.prf and IEC60870S2.prf files (folder where zenon Logic is installed and ...
SNMP Trap Service opens wrong listening port
Summary The trap service now opens the correct port and the SNMP V3 driver connects to the trap service and receives traps. Description The trap service now opens the correct port and the SNMP V3 driver connects to the trap service and receives ...
WebClientStarter: Scrollbars appear in Fullscreen option, even though zenon screen-size and monitor resolution are equal
Summary scrollbars aren't hidden correctly Description scrollbars aren't hidden correctly Information Use "Zoom" or decrease framesize/screensize Issue Number: 142532 Fixed on Date: 6.11.2018 Versions: 8.00 0 BUILD 53129
DNP3-SG gateway: Wrong output length for converted multibyte strings in point items
Summary - Description - Issue Number: 154990 Fixed on Date: 25.10.2018 Versions: 8.00 0 BUILD 53129
Empty timestamp columns were only hidden in positive timezones
Summary Information Create "if" statements in the report definition files to catch such a behavior Issue Number: 146375 Fixed on Date: 5.12.2018 Versions: 7.20 0 BUILD 53457 | 8.00 0 BUILD 53974 | 7.50 0 BUILD 54309 | 7.60 0 BUILD 54483
Strings are cut if it contains chinese characters
Summary Strings shared via logic to SCADA Connection are cut if chinese characters are used in the string. Description Strings shared via logic to SCADA Connection are cut if chinese characters are used in the string. Issue Number: 172674 Fixed on ...
AddinFramework Bug (Packing of zip files)
Summary The timeout of building a scadaAddIn package is now set to 30sek (former 8Sek). If this timeout is exceeded a error message is shown and the build fails. (former an invalid package was created) Description The timeout of building a scadaAddIn ...
Transparency in freely defineable frame shapes is not always given
Summary under special circumstances free template shape of global templates is not compiled correctly Description under special circumstances free template shape of global templates is not compiled correctly Information Create all RT Files. Doesn't ...
API: No option to add archive variables to aggregated archive with more than one and less than all aggregation types
Summary it was not possible to programmatically add another aggregations of a variable to an archive if any aggregation of this variable is already in Description it was not possible to programmatically add another aggregations of a variable to an ...
- DATEI32: driver does not send all value / status changes for one variable to the runtime
Summary - Description - Issue Number: 157231 Fixed on Date: 5.12.2018 Versions: 7.60 0 BUILD 54483 | 8.00 0 BUILD 53974
DATEI32: driver only reads a single file per update cycle, potentially resulting in a backlog that cannot be cleared
Summary - Description - Issue Number: 157244 Fixed on Date: 5.12.2018 Versions: 7.60 0 BUILD 54483 | 8.00 0 BUILD 53974
empty files were not included into project backup
Summary Issue Number: 172612 Fixed on Date: 21.1.2019 Versions: 7.20 0 BUILD 54555 | 7.50 0 BUILD 55804 | 8.00 0 BUILD 55271
Since 8.00 scrolling by touch does not run properly
Summary Scrolling via touch in supporting lists was not following touch movement. Description Scrolling via touch in supporting lists was not following touch movement. Issue Number: 171405 Fixed on Date: 19.12.2018 Versions: 8.00 0 BUILD 53974
LOGIX_ODVA driver crashes during variable import witch customer file
Summary Unexpected behaviour during variable import Description Unexpected behaviour during variable import Issue Number: 160015 Fixed on Date: 18.12.2018 Versions: 8.00 0 BUILD 53974
IEC870 Spontaneous values are sometimes sent without any reasons
Summary -. Description -. Information After checking the code (VMStackApi.cpp) and adding a lot of traces (in the CVMStackApi::Exchange() function), it seems that sometimes we enter in a condition indicating the timestamp has been updated. Then we ...
ETM: cursor-window is not updated correctly when the visiblity of trend curves is taken from a variable
Summary . Description . Information deactivate and activate the cursor again after curves have been added or removed Issue Number: 160602 Fixed on Date: 14.12.2018 Versions: 8.00 0 BUILD 53974
Number can not be entered before the decimal place
Summary Validation corrected - numbers before the comma are allowed now even if the numbers behind the comma already fit to the constraints. Description Validation corrected - numbers before the comma are allowed now even if the numbers behind the ...
zenon doesn't start - Windows CryptoAPI access fails with NTE_TEMPORARY_PROFILE error on a specific Server 2012 R2
Summary zenon doesn't work with mandatory profiles (read-only profiles) on terminal server Description zenon doesn't work with mandatory profiles (read-only profiles) on terminal server Information A Microsoft blog article shows some Workarounds: ...
Runtime freezes if you execute a right click on a combi element where the linked variable has no status in the RT
Summary When the feedback data point is already advised (e.g. used in the screen element where the manu should be opened) but without value, alle menu entries except command force are disabled. If the feedback data point is not advise (e.g. command ...
3S_V3 RDA type 3: wrong calculation of size
Summary Processing of RDA Type 2 and RDA Type 3 does not work. Log-Message: "RDA Count (X) x Datatype-Size (Y) doesn't match RDA Blocksize (Z)." Description Processing of RDA Type 2 and RDA Type 3 does not work. Log-Message: "RDA Count (X) x ...
Description Tooltip in GIS Integration Tool does not works
Summary In the runtime the gis control shows at mouse over a tooltip containing the text set in the description of the marker. Description In the runtime the gis control shows at mouse over a tooltip containing the text set in the description of the ...
Possibility to access the system in KeyBlock Runtime via Printing Reports on a Touchscreen
Summary The default .Net printing status dialog with count of pages and [Cancel] button was nice to have, but as a managed, topmost object it overrides the keyblock. No other printing process from Zenon uses such a dialog, so removing it also ...
driver simulation project is no longer available after compiling the zenon project
Summary Packing/Unpacking of Driver simulations Project did not work Description Packing/Unpacking of Driver simulations Project did not work Issue Number: 174904 Fixed on Date: 14.2.2019 Versions: 7.60 0 BUILD 55240 | 7.50 0 BUILD 55804 | 8.00 0 ...
Driver Simulation Project is not created properly.
Summary Packing/Unpacking of Driver simulations Project did not work Description Packing/Unpacking of Driver simulations Project did not work Issue Number: 175346 Fixed on Date: 14.2.2019 Versions: 7.60 0 BUILD 55240 | 7.50 0 BUILD 55804 | 8.00 0 ...
Default names do not work for Time/lot, Alarm Message list and Chronologic Event list filter picture
Summary In 7.20 it was possible to define Default screens for filtering AML or CEL. They were indicated through their special name. You can select the name by opening the combobox of the "name" field in the screen properties. When it was done like ...
AcccessICCP: no reinit of communication after Settings change
Summary The ICCP Process gateway does not apply configuration changes after closing settings dialog with OK. Description The ICCP Process gateway does not apply configuration changes after closing settings dialog with OK. Information restart gateway ...
Driver Simulation Wizard: Simulation project is not createad when there are variables with umlauts
Summary The Driver Simulation Wizard supported IEC 61131-3 compliant characters (standard letters, numbers, and underscore "_"). Variables with non-ASCII characters weren't encoded with correct codepage. The wizard did not set â Accept non IEC ...
PRP Service Not Working On Win 10 Version 1803 - OS Changes In Registry Entries For Network Bridge Configuration
Summary PRP service not working with Windows 10 1803 update. Description PRP service not working with Windows 10 1803 update. Issue Number: 177681 Fixed on Date: 7.3.2019 Versions: 7.50 0 BUILD 55804 | 7.60 0 BUILD 56016 | 8.00 0 BUILD 56563
Screenswitch to a Batch Control screen will always open the filter dialog
Summary . Description . Issue Number: 176232 Fixed on Date: 22.2.2019 Versions: 8.00 0 BUILD 55271
zenon Logic: structures which are created in zenonED are not loaded correctly in the Logic Workbench.
Summary structures with items using structures are loaded on first opening of logic workbench project correctly. Description structures with items using structures are loaded on first opening of logic workbench project correctly. Information Reopen ...
sporadic crash of the runtime after accessing cel data
Summary CEL entries with dynamic limit text could crash CEL list if originally linked variable was deleted. Description CEL entries with dynamic limit text could crash CEL list if originally linked variable was deleted. Issue Number: 175781 Fixed on ...
IEC61850: Static RCB is deleted when no dataset is linked
Summary Error message for empty linked dataset was missing. Description Error message for empty linked dataset was missing. Information If IED is available, do online import of RCBs. You can edit driver config TXT directly - when you know the proper ...
The function Replace text in limit values" dont work within arrays."
Summary Texts in items in arrays can be replaced as well. Description Texts in items in arrays can be replaced as well. Information Customer needs a fix in 8.0, because there is no comfortable workaround for customer Issue Number: 174310 Fixed on ...
XML Import of ETM picture switch function lose some informations
Summary Export works now as expected and exports styles linked to the ETM. Description Export works now as expected and exports styles linked to the ETM. Information no workaround Issue Number: 151691 Fixed on Date: 29.1.2019 Versions: 8.00 0 BUILD ...
COMTRADE Viewer WPF does not recognize Runtime EE license
Summary COMTRADE viewer does not recognize license in runtime DescriptionCOMTRADE viewer does not recognize license in runtime Information Add EE license entry to zenon6.ini on target system, e.g. demo SERIAL7=0.9cfbf6f.0.0.17c00bf ACTIVATIONKEY7= ...
Editor crashed during RT files creation
Summary Information Kein Work around möglich! Issue Number: 173789 Fixed on Date: 29.1.2019 Versions: 8.00 0 BUILD 55271