8.00
When using DNP3_TG driver with UDP as channel mode and unsolicited responses in the outstation are not allowed, the sending of a SBO command after a restart of the outstation leads to the case that no more commands can be sent afterwards.
Summary No more commands can be sent from the DNP3_TG driver to the outstation after a restart of the outstation is followed by a SBO command of the DNP3_TG driver if UDP is configured as channel mode and unsolicited responses are not allowed in the ...
When a zenon driver behaves unexpectedly, the dialog saying that a dump file is written including the location of it is sporadically not shown.
Summary The dialog saying that a dump file is written including the location of it is sporadically not shown when a zenon driver behaves unexpectedly. DescriptionThe dialog saying that a dump file is written including the location of it is ...
After reloading a sub project under specific circumstances the runtime on the standby server may close unexpectedly
Summary With an integration project and a sub project as redundant network projects with same server / standby server, the runtime on the standby server may close unexpectedly after transferring the runtime files to the primary server and reloading ...
Editing values in the new recipe value list in the Recipegroup Manager screen in the runtime is possible without available authorization
Summary When the new recipe value list is used in the Recipegroup Manager screen in the runtime, the authorization level of the user logged in is not validated and it is possible to change values although the authorization level for editing the ...
WPF elements may not be displayed correctly when converting a project to 7.60 version.
Summary The introduction of "transparency" for the WPF Element caused windows-based controls to not be rendered in the Editor/Runtime. DescriptionThe introduction of "transparency" for the WPF Element caused windows-based controls to not be rendered ...
Variable may not be deleted in Variable Diagnosis screen in the Runtime.
Summary Variable Diagnosis screen does not delete a variable by pressing DEL key in the Runtime. DescriptionVariable Diagnosis screen does not delete a variable by pressing DEL key in the Runtime. Solution The issue has been resolved. Information ...
Misleading error messages may appear in the output window when building the runtime files in the Editor.
Summary Converted projects may cause the presence of misleading error messages in the output window in the Editor when building the runtime files of screens. DescriptionConverted projects may cause the presence of misleading error messages in the ...
Vertical scroll bar may be rendered incorrectly in the Editor and Runtime.
Summary Alarm Message List vertical scroll bar may display a graphical artifact in the Editor and Runtime when using graphic files as display style. DescriptionAlarm Message List vertical scroll bar may display a graphical artifact in the Editor and ...
Variable write requests may not be routed to the primary server Runtime.
Summary Write request to non-local variables initiated from the standby server shall be routed to primary server disregard the “Read from Standby Server only” setting. DescriptionWrite request to non-local variables initiated from the standby server ...
Property window may not update in specific circumstances in the Editor.
Summary Property window is not updated when switching between different project symbols and the export properties list is focused in the Editor. DescriptionProperty window is not updated when switching between different project symbols and the export ...
Language files that have umlauts in their names are empty after project conversion from zenon 6.51 to any higher version.
Summary When a project is converted from zenon 6.51 to any higher version, language files that have names with umlauts (ä, ö, ü) are loaded in the language table but all their entries get lost. DescriptionWhen a project is converted from zenon 6.51 ...
The variable identification in the archive revision filter dialog is not translated by the language switch function.
Summary If you use a language switch function the keyword used in the variable identification in the archive revision filter dialog is not considered and therefore not translated. DescriptionIf you use a language switch function the keyword used in ...
zenon Editor - “Create style…“ should be greyed out when more than one element is selected.
Summary It is possible to select more than one element and extract the style, but only one style is extracted. DescriptionIt is possible to select more than one element and extract the style, but only one style is extracted. Information The “Create ...
Right-clicking a function inside a script opens the wrong context menu.
Summary Right-clicking a function inside a script opens the wrong context menu. DescriptionRight-clicking a function inside a script opens the wrong context menu. Solution The appropriate context menu opens now on right-clicking a function inside a ...
Automatic function execution does not perform a reload.
Summary If a reload function is executed automatically the reload is not performed until the runtime is restarted. DescriptionIf a reload function is executed automatically the reload is not performed until the runtime is restarted. Solution An issue ...
Variables marked as deleted are considered during the compilation of the command input.
Summary Variables with a linked command input, that are marked as deleted, are considered by the variable substitution of the command input compiler. The output windows shows an error message that the feedback variable is missing. ...
At the creation of a project backup some color palette colors of the global project are replaces by violet and black.
Summary During the creation of a project backup it can happen that the colors of the global color palette are exchanged by violet and black. Opening a new screen afterwards can lead to an unexpected termination of the zenon editor. DescriptionDuring ...
After XML import of an exported RGM function the parameter “Overwrite existing file“ is inverted.
Summary The parameter “Overwrite existing file“ is inverted after importing the XML of a RGM function. DescriptionThe parameter “Overwrite existing file“ is inverted after importing the XML of a RGM function. Solution The parameter is now correctly ...
The system text of the “Print current value“ function is not translated.
Summary In the variable function “Print current value“ the system text is not translated. DescriptionIn the variable function “Print current value“ the system text is not translated. Solution Now the shown progress bar is translated. Issue Number: ...
Interlocking property window may not be displayed after changing focus in the Editor.
Summary When returning to Interlockings from a previous selected item, the interlocking property window is not displayed in the Editor. DescriptionWhen returning to Interlockings from a previous selected item, the interlocking property window is not ...
XML Import of a user group results in multiple user groups with the same GUID in the Editor.
Summary After renaming a previously XML exported group in the Editor and importing the XML file again it will exist two user groups in the Editor with the same GUID. DescriptionAfter renaming a previously XML exported group in the Editor and ...
It should not be possible to set a password longer than 20 characters in Editor and Runtime.
Summary In Edit User screen and at Change Password dialog it is possible to set a password with more than 20 characters. DescriptionIn Edit User screen and at Change Password dialog it is possible to set a password with more than 20 characters. ...
Text color dynamic of bar display does not work in the Runtime.
Summary When using dynamic text color the text of bar display element is not adapted in the Runtime. DescriptionWhen using dynamic text color the text of bar display element is not adapted in the Runtime. Solution The issue was resolved so that Text ...
Button enters the "pressed state" even if needed rights are missing
Summary Needed rights are checked before the button enters the pressed state now. Description Needed rights are checked before the button enters the pressed state now. Issue Number: 125429 Fixed on Date: 10.1.2018 Versions: 7.60 0 BUILD 44685 | 8.00 ...
Add-In: EventLog entry/crash after closing the zenon Runtime where an Add-In has been executed
Summary This issue has been resolved, the RT no longer crashes. Description This issue has been resolved, the RT no longer crashes. Issue Number: 108635 Fixed on Date: 8.3.2018 Versions: 8.00 0 BUILD 57280 | 7.60 0 BUILD 57804
When setting a value on a string variable of the MITSUBISHI_FX32 driver which is longer than 127 characters (> 127), the value will not be set.
Summary - Description - Issue Number: 133889 Fixed on Date: 19.4.2018 Versions: 7.20 0 BUILD 47903 | 8.00 0 BUILD 48821 | 7.60 0 BUILD 49005 | 7.50 0 BUILD 46879
When setting an empty string (length 0) to a string variable of the MITSUBISHI_FX32 driver, the driver does not send a write request
Summary - Description - Issue Number: 134003 Fixed on Date: 19.4.2018 Versions: 7.20 0 BUILD 47903 | 8.00 0 BUILD 48821 | 7.50 0 BUILD 46879 | 7.60 0 BUILD 49005
scrollbar does not scroll to the last entry in CEL & AML
Summary scrollbar is updated correctly after adding new entries Description scrollbar is updated correctly after adding new entries Issue Number: 125709 Fixed on Date: 4.5.2018 Versions: 8.00 0 BUILD 48821 | 7.60 0 BUILD 49005
iec870Slave (zenPG and Logic) is losing spontaneus value changes during GI
Summary The spontaneous values received when the GI is in progress are now transferred when the GI is finish. Description The spontaneous values received when the GI is in progress are now transferred when the GI is finish. Information Possible ...
After XML Export and Import the Filter Parameters not correct
Summary If the filter "Linked screens" was used in a screen switch function to a faceplate and a picture of a picture container was linked then this was not properly stored with an xml export. The information which is needed to identify the picture ...
AML Screen with word wrap function
Summary Correctly insert item before the first and only one Description Correctly insert item before the first and only one Issue Number: 108670 Fixed on Date: 24.4.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
COLOR_ACKN_MARKER overlay the whole AML entry
Summary Symbol for Acknolegement is only drawn in the first column Description Symbol for Acknolegement is only drawn in the first column Issue Number: 125684 Fixed on Date: 24.4.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
Different behaviour for display of decimal values: Numerical Element - AML
Summary rounding of floating point number before formatting to string is done exactly the same in all modules Description rounding of floating point number before formatting to string is done exactly the same in all modules Information No direct ...
invalid control strategies after import
Summary Control strategies are imported correctly and therefor can be renamed Description Control strategies are imported correctly and therefor can be renamed Issue Number: 130873 Fixed on Date: 16.4.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD ...
New driver Hekatron ISP-IP
Summary Issue Number: 125422 Fixed on Date: 9.4.2018 Versions: 7.60 0 BUILD 49005 | 8.00 0 BUILD 48821
RT crash during CEL print with a multiproject.
Summary Entries in list are not deleted while printing is done Description Entries in list are not deleted while printing is done Issue Number: 140586 Fixed on Date: 3.7.2018 Versions: 7.20 0 BUILD 49308 | 8.00 0 BUILD 50155 | 7.50 0 BUILD 49034 | ...
Move Frame via Mouse is suppressed although dynamic elements are moved away
Summary Move frame via mouse did not correctly consider the scroll distance in the window. Therefore clicking in the area did not't work correctly. Now the scrolling position is correctly considered and the area under the mouse cursor is used ...
Driver Configuration through API: deactivating global update time has no effect
Summary When configuring the driver through the API and setting the global update time to false, always the "normal" priority group is used, regardless what is configured at the variable. Description When configuring the driver through the API and ...
Driver Crash 3S_V3.exe has stopped working" when switching to mode hardware and writing values"
Summary When switching the driver to hardware mode while continuously writing values the driver may crash if it has been run in hardware mode before. Description When switching the driver to hardware mode while continuously writing values the driver ...
S7TCP32 driver lost compatibility to higher versions runtimes
Summary When running a 7.60 Project in Version 8.00 or higher Runtime, the S7 TCP Driver does not communicate. Description When running a 7.60 Project in Version 8.00 or higher Runtime, the S7 TCP Driver does not communicate. Information from ...
Next page