7.50
The API property "Admin" for the user administration should not be read-only in the runtime.
Summary The property "Admin" in the programming interfaces for the user administration is read-only in the runtime, but it should be possible to change it. DescriptionThe property "Admin" in the programming interfaces for the user administration is ...
Driver ALLENDF1 does not send all recipe values to PLC
Summary It is not possible to send all recipe values to PLC using ALLENDF1 driver. PLC type in this specific case MicroLogix Allen-Bradley Standard recipe / Recipe Group Manager: When send action ('write all values' screen specific functions) is ...
It is not possible to send messages with the Azure Process Gateway to the eventhub when the format JSON is used.
Summary There is a version conflict concerning the Newtonsoft-JSON.dll which is used in the zenon webengine as well as in the zenon Azure Process Gateway. When trying to send Messages via the Azure Process Gateway to the Azure eventhub in the JSON ...
Created report viewer *.rdl file from zenon Editor fails when using specific OS languages.
Summary If creating a new Report Viewer *.rdl file from zenon Editor in OS using Chinese layout keyboard, the inputs fails as the *.rdl file created has bad characters at the beginning and at the end of the file. DescriptionIf creating a new Report ...
The zenon Runtime closes unexpectedly during moving axis at the Extended Trend.
Summary It may occur that the zenon Runtime close unexpectedly by moving vertical axis at the Extended Trend Screen. DescriptionIt may occur that the zenon Runtime close unexpectedly by moving vertical axis at the Extended Trend Screen. Solution ...
The symbolic address length should be expanded.
Summary The S7TIA driver may require very long symbolic names to address variables in group and subgroups, so that the symbolic address length should be expanded. DescriptionThe S7TIA driver may require very long symbolic names to address variables ...
Under specific circumstances it is shown a message when reloading a project in the runtime.
Summary If a project contains mathematical variables, it may be thrown an error message (“Encountered an improper argument.”) after rebuilding the variables.cmp file in the editor and reload the runtime. DescriptionIf a project contains mathematical ...
Under specific circumstances it is possible to type text characters in numerical variables in the runtime.
Summary The recipegroup manager may allow to enter text characters in numerical recipe value in the runtime. DescriptionThe recipegroup manager may allow to enter text characters in numerical recipe value in the runtime. Solution An issue has been ...
Under specific circumstances the faceplate containers are not correctly linked to the corresponding filter in the editor.
Summary It may occur that a duplicated faceplate filter cannot be applied to a faceplate screen container, so that the container is actually linked to the original filter. DescriptionIt may occur that a duplicated faceplate filter cannot be applied ...
The files DNP3_TG.dll and MtoM32.dll are missing for windows CE
Summary The files DNP3_TG.dll and MtoM32.dll are not available in the Windows CE-folder. There is an error message when using Update Windows CE Runtime when having DNP3_TG and MtoM32 selected. DescriptionThe files DNP3_TG.dll and MtoM32.dll are not ...
Under specific circumstances it is not possible to remove a variable from a multi-user project in the editor.
Summary It may be not possible in multi-user projects to undo newly created variables so that these are not removed from the variable list in the editor. DescriptionIt may be not possible in multi-user projects to undo newly created variables so that ...
It should not be possible to set the same start and end time for switching points in the scheduler.
Summary Though it is not permitted to set for newly created switching points (on/off) the same start and end time or duration to 00:00:00, it is possible to set this configuration for already existent switching points in the scheduler. ...
IEC62056 driver increases memory usage when running for a longer period of time.
Summary The memory usage of the IEC62056 driver increases over time. DescriptionThe memory usage of the IEC62056 driver increases over time. Solution This issue was fixed by improving the way the request object gets deleted. Information The faster ...
S7TCP32 driver, after a communication loss alarm_8p variable is not initialized
Summary If an Alarm (communicated as Alarm_8P) occours during communication loss to the PLC this alarm is not shown in the runtime if the communication continues again. Neither the PLC is reconnected after few minutes. This means the alarm is ...
zenon installation without provided zenon Demo-Workspace causes undefined state of the zenon Editor.
Summary If the zenon setup was carried out without the provided Demo-Workspace and the zenon Editor was started afterwards, it may occur that the zenon Editor is in an undefined state. This appears, if a workspace was loaded. In fact the issue arises ...
Multi-Touch issue of dynamic elements.
Summary When a Tap&Hold gesture will be carried out it may occur that it is well recognized but the finger was already moved afterwards. Dynamic elements: Tap&Hold on a button where a context menu is configured for Tap&Hold. Wait until the Tap&Hold ...
Creating new metering points with automatic value calculation is not possible. The output window displays the error "zenon logic project can´t be opened"
Summary With the released version of zenon 7.50, in the 64bit editor, it is not possible to create new metering points with automatic value calculation. Instead, an error message is displayed, saying that the zenon logic project can´t be opened. ...
zenon Logic IEC61850 Server: TCP Port should be configurable
Summary TCP Listener port of the zenon Logic I/O driver 'IEC61850 Server' is fix 102 (as defined in the Standard). Thus you can run only one instance per PC. To easy demonstrate that zenon iec850 driver (Client) is able to communicate to a large ...
The Batch Control Recipe Editor opens without reipe lists even though recipe lists were activated in a previous session
Summary When using the Batch Control Recipe Editor it is possible to configure a special layout with the three available recipe lists. This layout should be remembered and applied again, when the Batch Control screen is opened the next time. In zenon ...
Runtime shuts down unexpectedly with a project that runs a Batch Control recipe and provides data for external processes.
Summary It may happen in rare cases that the runtime shuts down unexpectedly when a Batch Control recipe is being executed and the Runtime is accessed by an external program, e.g. the OPCUA process gateway DescriptionIt may happen in rare cases that ...
When deleting a HMI device in zenon logic the corresponding variable of type hmiManager still exists.
Summary When adding a HMI device to your zenon logic project a variable of type hmiManager is automatically created. When deleting the HMI device afterwards the corresponding variable of type hmiManager still persists. DescriptionWhen adding a HMI ...
Digital sampling trace in zenon Logic Editor. Clicking on the Radio button Each cycle in the settings of the digital sampling trace leads to an error message when no value was entered in the lower TextBox and then trying to change a tab in the dialog.
Summary When no value is entered for the sampling period in the settings of the digital sampling trace and then clicking on the Each cycle radiobutton, an error message appears when trying to change to an other tab in the dialog. DescriptionWhen no ...
The zenon logic Real Time Extension (RTK) for Win 8.1 & 10 should be available in zenon 7.50.
Summary The zenon logic Real Time Extension (RTK) for Win 8.1 & 10 should also be available in zenon 7.50. DescriptionThe zenon logic Real Time Extension (RTK) for Win 8.1 & 10 should also be available in zenon 7.50. Solution The zenon logic Real ...
It should be possible to create RT files for the current build of zenon 7.20
Summary Additional to the possibility to create RT files for 7.20 it should be possible to create RT files for the current build of zenon 7.20 DescriptionAdditional to the possibility to create RT files for 7.20 it should be possible to create RT ...
If the Wibukey Software is not installed (when using a soft license), the zenon logic workbench won`t start.
Summary When using a soft license (no Wibukey Software installed), the zenon logic workbench won`t start. DescriptionWhen using a soft license (no Wibukey Software installed), the zenon logic workbench won`t start. Solution This issue was addressed ...
The Editor may close unexpectedly when configuring a string reaction matrix.
Summary When configuring a string reaction matrix having a state value with more than 99 characters the Editor closes unexpectedly after closing the reaction matrix window by pressing the OK button. DescriptionWhen configuring a string reaction ...
The variable list may not display the name of the reaction matrix linked in the Editor.
Summary The variable list detail view "reaction matrix" column does not show the name of the reaction matrix linked to a variable but instead an ID-number so that it is not possible to filter for variables using a reaction matrix name. DescriptionThe ...
When using a Driver in mode Simulation - programmed variables of type UDINT are not supporting values where the highest bit is set.
Summary When using a Driver in mode Simulation - programmed and setting a value bigger than 2147483647 (7FFFFFFFh) on a variable of type UDINT in the zenon runtime the value will always be 2147483648 (80000000h). DescriptionWhen using a Driver in ...
The substitute messages sent with zenon message control sending method: SMS GSM modem, SMS gateway and SMTP mail are not sent correctly and the CEL entries for that messages are not logged correctly.
Summary The sending of messages to substitute persons dont't work correctly because only the first person get the message and after the waiting time for an acknowledge for that user expired the substituted user dont't recive a substitute message. ...
If several messages are sent at the same time via message control, runtime is not responsive to user actions for some seconds.
Summary On some machines it can happen that the runtime is not responsive to user actions for some seconds if the message control engine is sending lot of messages a the same time. DescriptionOn some machines it can happen that the runtime is not ...
The driver Name "Driver for ABB 07KT94” of the CS31_32 Driver contains two spaces between "for" and "ABB".
Summary There are two spaces in the Driver Name "Driver for ABB 07KT94” of the CS31_32 Driver between "for" and "ABB". DescriptionThere are two spaces in the Driver Name "Driver for ABB 07KT94” of the CS31_32 Driver between "for" and "ABB". ...
zenon Documentation Download Tool did not recognize all installed zenon products.
Summary It may occur that the zenon Documentation Download Tool could not distinguish all installed zenon version respectively zenon products. For example, when the zenon Webserver was installed successfully and work as well not all installed other ...
Under Settings->Client configuration of the Diagnosis Viewer the Remote Runtime Driver Shows up twice.
Summary The Remote Runtime Driver shows up twice under Settings->Client configuration in the Diagnosis Viewer. DescriptionThe Remote Runtime Driver shows up twice under Settings->Client configuration in the Diagnosis Viewer. Solution This issue was ...
When writing a value to a STRING variable of MODBUS_ENERGY Driver with more than 64 characters, only 64 characters including null termination are written.
Summary When writing more than 64 characters to a STRING variable of MODBUS_ENERGY Driver, only 64 characters including null Termination are written. DescriptionWhen writing more than 64 characters to a STRING variable of MODBUS_ENERGY Driver, only ...
Process Gateway closes after acknowledging the error message "Memfile not large enough!" which appears immediately after startup of the Process Gateway.
Summary When the zenProcGateway.INI file is empty the Process Gateway closes after acknowledging the error message "Memfile not large enough!" which appears immediately after startup of the Process Gateway. DescriptionWhen the zenProcGateway.INI file ...
There is no default configuration file created in the Settings tab of the ALLENDF1 Driver. This results in an error message with text "Wrong Name for the file!" when trying to finish the driver configuration by pressing OK.
Summary In the Settings tab of the ALLENDF1 Driver there is no Default configuration file created. Therefore an error message with text "Wrong Name for the file!" appears when trying to finish the driver configuration by pressing OK. DescriptionIn ...
Process Gateway IEC870Slave is not handling correctly DPI-mapping for zenon variable configured to be more as one IOA
Summary Issue in zenon Process Gateway IEC 60870 Slave by DPI/DCS mapping when one zenon variable is configured in a sector many times. If you create in a sector two or more IOs as 'double point information' - type id. <3>, <4> or <31> - and link ...
It is not possible to send a SMS after GSM modem restart or power interruption happened.
Summary If the GSM modem is restarted the connection between GSM modem and zenon runtime is interrupted. DescriptionIf the GSM modem is restarted the connection between GSM modem and zenon runtime is interrupted. Solution The GSM dispatcher can now ...
Retry sending message via GSM SMS or SMTP mail have not correct try count and last send try timestamp.
Summary When sending a message via the GSM SMS dispatcher or the SMTP mail dispatcher fails due a hardware failure (no modem connected, no network connection, wrong phone number or email), the last send try timestamp and the send try count are not ...
The active-status of message control is not synchronised properly betweed server and standby server.
Summary If the active-status of message control is changed via function, the active-status is not synchronised properly between standby server and server after reactivation of primary server in a server-standby server architecture with dominant ...