7.20
invalid variables of IEC870_103 driver have no value when readvised
Summary issue when IEC870_103 driver has no connection with PLC: after variable(s) with status INVALID was unadvised (e.g. screen with variables was closed or other screen opened based on the same frame) - the re-advised variable has neither value ...
The COM tab of the driver dialog should support a selection from 1 - 256 serial interfaces.
Summary In the COM tab of the driver dialog it should be possible to select between 1 - 256 serial interfaces. DescriptionIn the COM tab of the driver dialog it should be possible to select between 1 - 256 serial interfaces. Solution This issue has ...
The "time of last change" field of a Recipegroup Manager recipe is not correctly updated in the runtime under specific circumstances
Summary When using the Recipegroup Manager screen in the runtime with the new recipe value table, saving the recipe after making changes, does not correctly update the "time of last change" field. In the following situations, the "time of last ...
zenon Editor – language table. Opening the language table could cause a memory leak.
Summary When opening the language table at the zenon Editor it may occur a memory leak of approximately 10 kb for each opening of the language table. Not reproducible with an empty zenon project. DescriptionWhen opening the language table at the ...
The runtime splashscreen elements may be displayed incorrectly.
Summary When starting the CE runtime under a specific OEM the module information may be displayed in a wrong position. DescriptionWhen starting the CE runtime under a specific OEM the module information may be displayed in a wrong position. Solution ...
The Industrial Performance Analyzer (IPA) may apply an incorrect time filter when "today", "yesterday" or "day before yesterday" is selected.
Summary When "today", "yesterday" or "day before yesterday" are selected in the tine filter of the IPA then it may happen that the displayed alarms actually don´t match with the filter. This is when the "with time" checkbox is activated. ...
Predefined scripts may appear in the unused scripts window in the Editor.
Summary Predefined scripts, e.g. AUTOSTART, may appear in the unused scripts window in the Editor despite those are executed correctly and automatically in the Runtime. DescriptionPredefined scripts, e.g. AUTOSTART, may appear in the unused scripts ...
Optional check for not existing variables in dataset in zenon Process Gateway ICCP-TASE.2 as client.
Summary Port to 7.20 solutions introduced in 7.60 for zenon Process Gateway ICCP-TASE.2 as ICCP-client: - client may initiate communication with remote ICCP server. - client may check if all configured variables are present on remote server. If not – ...
The Editor may close unexpectedly when importing a context menu via XML import.
Summary The Editor may close unexpectedly when importing a context menu from a XML file if this contains a menu already present in the project. DescriptionThe Editor may close unexpectedly when importing a context menu from a XML file if this ...
The Editor may stop responding when editing the Scheduler module.
Summary The Editor may freeze when the Scheduler view is opened. DescriptionThe Editor may freeze when the Scheduler view is opened. Solution The issue has been resolved. Issue Number: 36935 Fixed on Date: 11.8.2016 Versions: 7.20 0 BUILD 31040
Copy/paste function of Time filter for Extended Trend does not work for trends
Summary When a screen switch to ETM was executed where the filter was replaced by an own designed filter picture, the diagram was not refreshed, so the time axis scaling was not correct. You manually had to refresh the diagram. DescriptionWhen a ...
Azure archivequeue can't be created with Azure configuration package
Summary With older configuration package it is not possible, to create an Azure Archive Worker properly, because the archivequeue in the Servicebus does not get created. DescriptionWith older configuration package it is not possible, to create an ...
The XML Import of a Keyboard screen type locks a specific property of the alphanumeric button control elements in the Editor.
Summary After XML Import of a Keyboard screen type the property “change text depending on control keys” of the alphanumeric button control elements is greyed out and it cannot be activated in the Editor. DescriptionAfter XML Import of a Keyboard ...
Tools – System Information Collector (SIC). Additional characters were displayed when opening a UTF8 file.
Summary When including a UTF8 coded file into the SIC file, it will be begin with " ï » ¿ " characters. These characters will be not displayed, if opening the file with a text editor. DescriptionWhen including a UTF8 coded file into the SIC file, it ...
Tools – System Information Collector (SIC). Information about attachments (yes/no) is incorrect.
Summary The information whether a file is attached to the SIC file is not working proper, nevertheless if it is the front page or directly on a subfolder of the SIC. DescriptionThe information whether a file is attached to the SIC file is not working ...
In Watchdog timer 'none' and SBO the command action resets PROGRESS bit first when COT_actterm (10) comes or action timeout is elapsed.
Summary Command Processing by Watchdog timer 'none' sets the PROGRESS status bit of response variable (RV) after Select confirmation and keeps until PLC responds with Execute activation termination - COT_actterm (10). The PROGRESS bit should gone ...
When PLC is not responding the Select command the action is not breaking by ‘Timeout for SBO activation’ and keeps waiting on Select response.
Summary Issue in Command Processing blocking the response variable (RV) when a faulty or too busy IED does not react on Select command. In 7.11 the command actions were using for SBO the same 'Timeout' period like configured in action for 'Watchdog ...
While a command action waits on Select response from PLC another actions - for other RV - can be executed only once - then NET_SEL stays and locks.
Summary Issue in Command Processing blocking another response variables (RV) when a faulty or too busy IED does not react on Select command for a RV. When a device does not respond Select command, another commands - for another RV - can be executed ...
Command screen on network client can cause temporally blockage in values distribution if the user clicks a button while screen is refreshing.
Summary Executing a command on a zenon Network client / webclient may result in a timeout of the response variable (RV) from Watchdog timer, even though the command itself was successfully executed in the PLC and the RV value was received correctly ...
zenPG ICCP: disturbed connection start/stop frames may result in unexpected behavior.
Summary zenon Process Gateway ICCP-TASE.2: malformed frames while connection start/stop with remote ICCP communication partners can lead to unexpected behavior in AccessICCP.dll. Descriptionzenon Process Gateway ICCP-TASE.2: malformed frames while ...
Recipe variables in the recipe value table in the Recipegroup Manager screen are not always correctly set invisible
Summary It can happen that Recipegroup Manager recipe variables are still displayed in the recipe value table in the Recipegroup Manager screen in the runtime, although the linked visiblity variable have an active limit with the invisible attribute ...
Runtime may close unexpectedly with rated redundancy under specific circumstances
Summary The zenon runtime on the primary server may close unexpectedly in a configuration where a project uses rated redundancy with a (internal) variable used in the calculation for the rating, when changes to the variable limit or reaction matrix ...
The XML export of screens may not include the objects linked to the released properties of symbols.
Summary The XML export of a screen may not include the variables or functions linked to a released property of symbols. DescriptionThe XML export of a screen may not include the variables or functions linked to a released property of symbols. ...
The XML export of screens may not contain the objects linked to symbols by substitution.
Summary The XML export of screens does not include the variables or functions that are linked to symbols by substitution. DescriptionThe XML export of screens does not include the variables or functions that are linked to symbols by substitution. ...
Historian on open alpha files should not write the end-timestamp into the archive header.
Summary Via Programming Interface or Archedit should not write the end-timestamp into the archive header of open XX.ARX files as sometimes the end-timestamp in the header is getting invalid when creating archive entries. DescriptionVia Programming ...
Printer Settings-> Header/Footer/Comment Buttons no respond over with the mouse action.
Summary Printer settings for Extended trend no respond over the mouse action on the Buttons. Header and footer, heandling and comment (%DATUM%; %ZEIT%; %DIAGRAMMNAME%; %SEITE%) are doesn't possible set via Button. DescriptionPrinter settings for ...
Filter settings Position "% of the width of the Y-Axis" in tab X-Axis is not configurable from -100 up to +100.
Summary If you move down/up the X-Axis on the Diagram Window - trend display control, below/above allowed range, he will then see "message" on filter settings as long as he will not adapt it to the range 0-100. Without that, he cannot "save" ...
If lot-filter is active, with scrolling filter is changed in the future after a short random time period.
Summary If you filter the Extended trend screen on a relative time period and on a lot the time filter is changed in the after a short random time period. DescriptionIf you filter the Extended trend screen on a relative time period and on a lot the ...
Opening a Batch Control Screen may take very long if many recipes exist
Summary When opening a Batch Control screen, properties of existing recipes are loaded in order to display this information in the list. Depending on the number of existing recipes and configuration of the screen switch function this may take a while ...
Screen objects should not be listed in the Worldview object list if the element is not currently visible.
Summary The object list of the Worldview screen type should not list screen elements that are not visible in the current zoom step in the Runtime. DescriptionThe object list of the Worldview screen type should not list screen elements that are not ...
zenon Runtime compatibility for older zenon versions did not work properly with dynamic texts.
Summary When using a new property ‘display text’ for dynamic texts and use the zenon Runtime downwards compatibility e.g.: ‘creates RT files for...’ <7.50, the element shows different content on Server and Runtime. DescriptionWhen using a new ...
Interlocking conditions in actions are only considered with Topology Module license.
Summary When using user-defined interlocking conditions in actions of Command Processing, the conditions are not considered with Energy Edition license. They are only working if you have licensed the Topology-Module (advanced ALC) too. ...
Process Gateway ICCP TASE.2 application sporadically stops working.
Summary Under unclear circumstances the zenon Process Gateway ICCP TASE.2 application sporadically stops working. Access violation with fault address: 75F62EAB 01:00012EAB C:\windows\syswow64\RPCRT4.dll. DescriptionUnder unclear circumstances the ...
IEC850 driver should support driver command for switching to secondary IP address.
Summary IEC61850 (Client) driver should support driver command for switching TCP communication from the use of primary IP address to the secondary IP address (and vice versa). DescriptionIEC61850 (Client) driver should support driver command for ...
The space (blank) chars at the beginning and end of the name of command group are removed.
Summary When a user creates a command group in zenon Editor then the leading space chars (and additional blanks at the end) are removed. The creating command groups via XML import, or VBA/VSTA, or modifying existing via context menu allows blanks in ...
While response variable has INVALID status bit in context menu also actions which should be allowed are disabled.
Summary Since introduction of new action type 'forced command' when in the Runtime the Command Processing shall be called via context menu and the response variable has INVALID status bit then all other actions in menu are disabled, even 'replace'. ...
Under specific circumstances the Editor closes unexpectedly when importing screens from a XML file.
Summary The Editor may close unexpectedly when importing a XML file containing screens that are currently open. DescriptionThe Editor may close unexpectedly when importing a XML file containing screens that are currently open. Solution The issue has ...
The Recipegroup Manager function with the parameter "read recipe" does not correctly consider unit switching which may result in an error and a recipe that is not saved
Summary When using the Recipegroup Manager function with the parameter "read recipe", the scaled value through unit switching is used and validated against the min. / max. boundaries of the raw value stored in the recipe. This may result in a value ...
It may not be possible to import RGM recipes from the Runtime in the Editor.
Summary It may not be possible to import Recipegroup Manager recipes from a remote Runtime in the Editor if the path of the workspace contains "." (dots). DescriptionIt may not be possible to import Recipegroup Manager recipes from a remote Runtime ...
A LD-ADS user may be able to change the password without entering the old password in the Runtime.
Summary The old password field can be left empty in the Edit User screen when changing a user password of a LD-LDS user in the Runtime. DescriptionThe old password field can be left empty in the Edit User screen when changing a user password of a ...