7.10
The login mask for login and for providing the electronic signature does not appear on the correct monitor
Summary In a multi-monitor configuration, the login mask for login and for providing credentals for a digital sigature may not appear on the same monitor where the action was initiated that required the login or the digital signature. The login mask ...
Creating or restoring a project backup on zenon 7.11 may fail and lead editor to close suddenly under specific circumstances.
Summary When a project contains invalid variable limit definitions, e.g. a Boolean variable with the same maximum/minimum values, is not possible to create a backup or restore it in zenon 7.11 causing the editor to close unexpectedly with an ...
Occasionally, it is not possible to import a S7 project in the zenon 7.10 editor.
Summary In the Import S7 project wizard it might happen that the step Select variables does not display any columns to show and select variables to be imported in the editor. Description In the Import S7 project wizard it might happen that the step ...
The name of the authorization level should be displayed in the Recipegroup Manager recipe authorization combobox instead of the number
Summary The combobox for setting the authorization level of a recipe should show the name of the authorization level instead of the number of the authorization level Description The combobox for setting the authorization level of a recipe should show ...
Exporting a Recipegroup Manager recipe in ASCII in the runtime does not add the extension ".txt" in all cases
Summary If a Recipegroup manager recipe is exported in ASCII in the runtime using the Recipegroup manager screen specific function, and specifying the desktop for the file destination, under specific circumstances the file extension ".txt" may not be ...
The zenon editor may stop responding in a specific circumstance when inserting an existing project in the workspace.
Summary When searching for an inexistent computer on Project selection dialogue the zenon editor may stop responding if the progress bar is moved. Description When searching for an inexistent computer on Project selection dialogue the zenon editor ...
Warning when importing a DBF file
Summary Warning message when importing variables via DBF file. Import warning: "SIMUL Information" - Variable kann nicht umbenannt werden und wird neu angelegt Import warning: "SubNavigation_MDI_2" - Variable kann nicht umbenannt werden und wird neu ...
Report viewer screens are not working if dataset is not defined (correctly) in screen switch function - Invalid .rdl file
Summary Message shown is when build Runtime files: System.ArgumentNullException: 'dataType' argument cannot be null.~~Parameter name: dataType~~ at System.Data.DataColumn..ctor(String columnName, Type dataType, String expr, MappingType type)~~ at ...
When using model with aggregation of archives, variables can not be selected from the mother archive
Summary When select a model of aggregation it is not possible to select variables from mother archive but the list of variables of the project. If add one or 2 variables, they appear in the tree of the archive at the same level of other archives ... ...
Report Viewer: Create file does not work on x64 version
Summary In the x64 bit version new report definition files can not be created because the 64 bit editor does not find/search the template files in the x86 directory. Description In the x64 bit version new report definition files can not be created ...
S7TCP32 driver stops if you read DATE AND TIME variable with wrong time values
Summary The S7TCP32 driver stops if it reads a DATE AND TIME variable with a wrong time value. That means one of the following Byte values is out of range: Byte 3 - hour - crash with value 30 or higher Byte 4 - minute - crash with a value 90 or ...
Hydrometer driver: Bowsing of "new receivers" is not possible
Summary When try to browse a just befor added "new receiver" -> progressbar appears and closes without any message -> Logentry: "Send: WaitForAnswer failed" and "Browse: SecondarySelect failed" Description When try to browse a just befor added "new ...
MODRTU32 driver stops with more than one plc on a serial connection under certain conditions
Summary zenon 7.10 RT is connected to 2 Modbus slaves PLC with address 1 and 2 via RS485 (serial connection), but MODRTU32.exe seem to stop working in some specifc project and in certain conditions. Especially if only second PLC is active connected. ...
zenon Logic COM port number higher 9 is not supported
Summary If you want to use in SERIO function block in zenon Logic with COM ports with a number higher than 9. This is limited by the OS, so the specification only works using "//./COMxx", but unfortunately zenon Logic doesn't support this. Only COMx. ...
Numeric values ignored in the Report in 64bit editor/runtime
Summary When entering numeric values to a report in the runtime, these values seem to be ignored and replaced by "0.00" in 64 bit editor. Example: => Cell A1 should have the numeric value 5 => When entering the value 5 directly in cell A1, the value ...
IEC62056-21 driver, variable with datatype 'Date and Time' lead to driver stop if timestamp is invalid.
Summary A variable with the datatype 'Date and Time' and set the IEC62056 address to 96.70 - the driver will stop as soon as the RT is started. On this device it seem the timestamp for this address is invalid. Description A variable with the datatype ...
OMR_FINS Read/Write strings wrong from all memory areas
Summary OMR_FINS Read/Write strings in wrong byteorder from all memory areas. It seems as the bytes are switched incorrectly. For example, see the following table: zenon displays PLC displays davis adiv test etts etts test var av av var Description ...
Bachmann M1 driver: Communication loss is not recognized at all when using callback mode
Summary When switching the Bachmann M1 driver into "callback" mode it does not react on a communication loss. When having the driver not in callback mode it recognizes communication loss proper and does a reconnect when cable is plugged in again. ...
zenon Logic fieldbus driver => Hilscher cifX Profibusœ doesn't work under Windows 7 Embedded Standard OS
Summary The zenon Logic fieldbus driver => Hilscher cifX Profibusœ can not be used propperly under the operating system Windows 7 Embedded Standard. Description The zenon Logic fieldbus driver => Hilscher cifX Profibusœ can not be used propperly ...
zenon Logic fieldbus driver => Hilscher cifX Profibusœ. It isn't possible to use more than one profibus slave.
Summary The Hilscher cifX Profibus driver for zenon Logic cannot communicate with two different profibus slaves (e.g. From two different manufacturers) with one card. Description The Hilscher cifX Profibus driver for zenon Logic cannot communicate ...
zenon Logic Fieldbus => Hilscher cifX Profibus: Diagnose Variables (Master/Slave) are not updated properly
Summary zenon Logic Fieldbus => Hilscher cifX Profibus: Diagnose Variables (Master/Slave) are not updated correctly. it isn't possible to check/recognize, if a slave is ok or not ok, because the SlaveState Bit is always 0! => e.g disconnect the ...
Possibility of flashing of lines in the AML depending on the state of the Alarm - not acknowledged / acknowledged
Summary The possibility to have a flashing of lines in the AML dependent on the state of the Alarm - not acknowledged/ acknowledged - is missing There is no way of doing this, also not via API workarounds. Description The possibility to have a ...
zenon Runtime hangs when CEL or AML file reaches size of 4GB.
Summary zenon Runtime hangs when CEL or AML file reaches size of 4GB. Description zenon Runtime hangs when CEL or AML file reaches size of 4GB. Solution Issue was addressed in index of entry position in CEL and AML files larger then 2GB. Now files ...
The Unit of "new value" entry in the CEL is not translated
Summary The Unit in CEL entry about new value of the variable is not translated. Description The Unit in CEL entry about new value of the variable is not translated. Solution Now Unit with '@' is translated correctly Issue Number: 31297 Fixed on ...
zenon IEC870 driver does not set T_STD bit (bit 30) at zenon variables
Summary The zenon IEC60870 driver does not set the status bit T_STD ("Standard time", e.g. winter time in Europe) - bit 30 - at the variable in zenon. Description The zenon IEC60870 driver does not set the status bit T_STD ("Standard time", e.g. ...
IEC61850 Server resets EntryID by any purge of BRCB
Summary The IEC61850 Server - I/O driver in zenon Logic - resets EntryID to 0 when received purge for BRCB - when client writes */PurgeBuf[BR]=true in this BRCB. It causes that when client purges buffer frequently the Server uses for new Reports the ...
the IEC61850 driver (Client) does not act according the negotiated MMS max outstanding requests
Summary At the beginning of IEC61850 communication, in MMS.InitiateRequest and MMS.InitiateResponce the client and server are exchanging information also about maximal number of outstanding MMS requests (typically it affects number of outstanding ...
Alarm list: the comment of alarms with dynamic limit text is displayed and can be edited, changing the comment changes the alarm text
Summary zenon uses the comment field of AML and CEL entries to store the values used in dynamic limit texts. In the Alarm List the comment edit box should be disabled for such alarms. However a random value comment is displayed for alarms with ...
IEC870 driver (Master) and zenPG IEC870Sl should support file transfer also in control direction.
Summary We will introduce for 7.20 and we already successfully tested a new functionality in our IEC60870-5-101/104 products - file transfer in control direction. This means transfer in "reverse direction" - from Master to Slave. We need this feature ...
In command screen the field 'Value response' takes the additional limit text from reaction matrix of action variable
Summary Issue since implementation of new feature (see KB Article #172219): the text introduced by the feature in the field for response variable is taken from action variable, which for most actions are the command variable and not the response. ...
access violation caused by Command input in the set-point action when 'Cancel' of SBO
Summary The set-point input actions in Command Input module are supporting Select Before Operate like switching commands do. When action has two stages the Select can be canceled - button 'Cancel' sends deactivation to the device. Since version 7.11 ...
IEC61850 Server driver has wrong reaction on MMS.Read request with the flag "SpecificationWithResult" set to TRUE
Summary The support of the flag "SpecificationWithResult" in MMS.Read is theoretical mandatory but seldom in use - thus not requested by clients. Issue found during tests for certification: The IEC61850 Server supports it only if the read request did ...
Empty 'variable name' column in CEL for messages from RGM
Summary The Recipe Group Manager, when writes a recipe, creates in the Chronological Event List entries where 'text' contains name of the recipe, new and old values of the variables and names of the variable. But the column 'variable name' of such ...
Under specific circumstances the login dialog screen is displayed cut in the zenon runtime.
Summary For some configured screen resolutions the login dialog screen might be shown cut in the zenon runtime not allowing the user to enter properly the login credentials. Description For some configured screen resolutions the login dialog screen ...
Under specific circumstances the zenon runtime buttons do not adjust their look according to the current user logged in authorization level.
Summary It may occur that when a user logs in the zenon runtime its authorization level is not acquired correctly by the screen buttons not looking these accordingly. The buttons appearance is only adjusted if the zenon runtime is reloaded online. ...
The webclient is always set to use English language after installation.
Summary The webclient displays English as default language, not considering the language used during the installation setup. Description The webclient displays English as default language, not considering the language used during the installation ...
Memory is not correctly released after closing the Active Directory user administration screen in runtime.
Summary The Active Directory user administration screen allocates memory when loading the AD structure but does not release it after causing a large memory usage increase. Description The Active Directory user administration screen allocates memory ...
In specific circumstances the user login in the Active Directory takes an unreasonable long time to be executed.
Summary When the Active directory has a large and complex user's structure the user login can take an unreasonable long time to be executed. Description When the Active directory has a large and complex user's structure the user login can take an ...
The Production & Facility Scheduler module displays some icons mistakenly in the editor.
Summary When opening a schedule from the calendar in the table view the icons copy, cut and paste are not suitable for operation and the show next element, show previous element and help icons are wrong. Description When opening a schedule from the ...
Under specific circumstances the Production & Facility Scheduler module in the editor cannot be configured correctly.
Summary When it is used structured schedulers in Production & Facility Scheduler and it is edited the time and offset of a scheduler this also produces changes in the parent schedulers. Description When it is used structured schedulers in Production ...