7.10
IEC61850 Client cannot import variables from SCL-file having new bTypes introduced by Edition 2 of the Standard.
Summary EC61850 Client driver in zenon and the I/O driver in zenon Logic cannot import variables from SCL-file for the Data Attributes which have new bTypes - introduced by Edition 2 of the IEC61859 Standard. In addition the driver in zenon Logic ...
Process Gateway ICCP cannot create data set when the request contains optional objects like Transfer_Set_Name
Summary In ICCP Standard it is defined that the data set can be created with optional items like e.g. Transfer_Set_Name, DSCondition_Detected. The ICCP Server in zenon Process Gateway refuses to create such data set. It makes not possible to ...
Process Gateway ICCP does not start when its Client is configured to not request any variables
Summary The zenon Process Gateway ICCP refuses to start when its ICCP Client configuration - variable list - is empty. In such case the ICCP session should start and Client only read Bilateral Table. Description The zenon Process Gateway ICCP refuses ...
Process Gateway IEC870Slave should map status bit ALT_VAL of variable to flag 'Substituted'
Summary When zenon variable has ALT_VAL status bit (bit 27) the Process Gateway iec870Slave sends value changes in ASDU with quality descriptor flag IV ('invalid') or NT ('not topical'). It should send, in quality descriptor in ASDU, the flag SB - ...
When using a format file from the Report Generator (*.xrs) for the display of the recipe table in the Recipegroup Manager screen, hidden cells are not filled.
Summary When displaying a Recipegroup Manager recipe in the Recipegroup Manager screen in the runtime, it is possible to display the recipe table using a format file from the report generator, in order to have a custom design table. In version 6.50, ...
Error message "The data of the Batch module of project '...' were edited with version (7.00 SP0). and cannot be loaded here!" when starting a client / webclient in the version 7.10 with a server running version 7.00
Summary When starting a client or webclient in version 7.10 with a server runtime running version 7.00, where a license for Batch Control is used, the runtime shows an error message on startup. "The data of the Batch module of project '...' were ...
The OPCUA client driver stops sending service requests for a subscription when no variables are needed in the runtime and attempts to reuse the no longer existing subscription when a variable is needed again.
Summary When momentarily no variables are used in the runtime from a connection in the OPCUA client driver, the OPCUA client driver no longer sends service requests for the subscribtion that was previously created for these variables. The OPCUA ...
When a variable in the OPCUA server has a bad quality (no value), the OPCUA client driver does not offer this variable in the list of variables after online import in the editor.
Summary After online import in the editor for the OPCUA client driver, the list of variables does not contain variables that have bad quality and no value. When the variable value has a valid, the online import does correctly offer the variable in ...
OPC UA client driver cyclically sends a createmonitoreditem request with node ID "0" for variables that do not exist on the server
Summary When the browsename for variable of the OPCUA client driver is incorrect or does not match an item in the OPCUA server, the TranslateBrowseNameToNodeId request of the OPCUA client driver in the runtime results in an invalid NodeId "0" ...
The CPU usage of the OPCUA client driver in the runtime gradually increases over time
Summary The CPU usage of the OPCUA client driver in the runtime gradually increases over time. When using multiple OPCUA client drivers, the system may eventually stop responding when all CPU cores are running on full load. Description The CPU usage ...
The OPCUA client driver sets variables INVALID in the runtime after 20 seconds with specific settings for publishing interval and MaxKeepAliveCount and no value changes in the OPCUA server.
Summary When the OPCUA client driver uses settings with a publishing interval and a MaxKeepAliveCount that result in a value of more than 20 seconds, and the OPCUA server sends no value changes (publish responses) for all the variables in the ...
The OPCUA server in the process gateway can only access variables from the startup project.
Summary The OPCUA server in the process gateway is limted to variables of the startup project. The OPCUA server in the process gateway should be enhanced to support multi-project environments. Description The OPCUA server in the process gateway is ...
Variables from the OPCUA client driver that have a bad statuscode on startup will never get a value.
Summary If the value of a OPC UA variable has a bad status code when OPCUA client driver starts, the variable will never get a valid value in the runtime, even when variable gets a good statuscode in the OPCUA server. Description If the value of a ...
Variables of the OPCUA client driver do not have the the INVALID status set when the OPCUA server returns a value with a bad quality.
Summary When a variable of the OPCUA client driver gets a bad status code, the zenon variable does not set the INVALID status bit for this variable in the runtime. Description When a variable of the OPCUA client driver gets a bad status code, the ...
The OPCUA client driver does not properly evaluate a timeout response from the OPCUA server and logs an error regarding a malformed telegram.
Summary When a server has timeout - cannot issue requested Publish on time - the OPCUA server sends a telegram with the error message instead of the publish response. The OPCUA client driver does not correctly parse the received telegram and logs an ...
Zenon Runtime closed unexpectedly if supplementary DirectX Hardware was connected.
Summary When a created project includes one screen with many symbols and when the graphic quality was set to DirectX Hardware the effect occur. DescriptionWhen a created project includes one screen with many symbols and when the graphic quality was ...
Under specific circumstance the zenon Editor closed with unhandled exception.
Summary The zenon Editor closed with an unhandled exception when undo a specific configuration of numerical elements. DescriptionThe zenon Editor closed with an unhandled exception when undo a specific configuration of numerical elements. Solution An ...
An improvement regarding variable unit at the combi element was implemented.
Summary The combined element should have an option to display for example the identification of a variable as text. DescriptionThe combined element should have an option to display for example the identification of a variable as text. Solution Now, ...
An improvement regarding the login screen was implemented.
Summary The MDI control "Current user" with the ID: 10001 sever as a headline. This should be removed from the control MDI list of the editor. DescriptionThe MDI control "Current user" with the ID: 10001 sever as a headline. This should be removed ...
Under specific circumstance the zenon Editor closed with unhandled exception.
Summary The zenon Editor closed with unhandled exception. The zenon WPF Elements has an issue with the zenon Object at the WPF control. DescriptionThe zenon Editor closed with unhandled exception. The zenon WPF Elements has an issue with the zenon ...
Under specific circumstance the MDI element is not working correctly.
Summary When a project was created and the flashing of the MDI element "Set value input" was not working properly. DescriptionWhen a project was created and the flashing of the MDI element "Set value input" was not working properly. Solution An ...
Under specific circumstance at the zenon Runtime the screen type function doesn't work correctly.
Summary When you change at the zenon Runtime some specific filter like the time filter, the Runtime doesn't act on these settings. DescriptionWhen you change at the zenon Runtime some specific filter like the time filter, the Runtime doesn't act on ...
Under specific circumstance the zenon Editor freeze and the CPU consumption rises up.
Summary When opening a context menu at the zenon Editor and a short time later the screen saver turns on, the zenon Editor freezes and the CPU consumption rises up. DescriptionWhen opening a context menu at the zenon Editor and a short time later the ...
Under specific circumstance the zenon Editor closes unexpectedly.
Summary When history of changes is active and a screen is imported via XML but there already existed a screen of this or with this name and the user click "NO" to not replace the existing screen, the zenon Editor closes unexpectedly. DescriptionWhen ...
Under specific circumstance the zenon Editor closes unexpectedly.
Summary When clicking into a color palette grid cell and back to another project tree the zenon Editor could close unexpectedly. This behavior was only reproducibly when multi touch monitor and when Windows 8 as operation system was used. ...
Under specific circumstance sporadic access violation at a zenon-driver when a variable is removed or deleted and a reload is performed.
Summary When a variable from a process driver was moved to another driver or delete the variable and reloaded afterwards, than sometimes the driver was blocked and all variables were frozen. DescriptionWhen a variable from a process driver was moved ...
Under specific circumstance the zenon Runtime lasso on worldview was displayed on a wrong position.
Summary When a user has opened the zenon Runtime and pulls the open Runtime lasso on worldview the rectangle was not correctly displayed. DescriptionWhen a user has opened the zenon Runtime and pulls the open Runtime lasso on worldview the rectangle ...
An improvement regarding the time zone was implemented. The zenon Runtime should directly react on the change of the time zone in the operating system.
Summary A restart of the zenon Runtime was needed in order to have the changed the time zone reflected in zenon. DescriptionA restart of the zenon Runtime was needed in order to have the changed the time zone reflected in zenon. Solution Now, after ...
Under specific circumstance the update from pictures in zenon Editor does not work correctly when using a bitmap in the template.
Summary When a user creates a template with a bitmap as background and then a second template, without a bitmap in the background, was created and also a new picture was created. Automatically the first created template was used. The screen was ...
IEC60870 Slave handles the 'Reset process' command correctly but responds to a master with PN-bit (negative confirmation)
Summary Issue when a master sends to IEC60870 Slave (zenon Process Gateway or I/O driver in Logic) the 'Reset process' command - C_RP_NA_1 (T105) with COT=6 (activation): the Slave transfers to the Runtime the received value of QRP correctly, but it ...
"Description" property isn't copied from the source to the target datatype when this is created in editor via copy-paste action.
Summary When a datatype is inserted in editor via copy-paste action, its "Description" property is reset to the datatype default text ("Simple datatype"), not taking the text previously defined by the user in the source datatype. ...
Security Vulnerability: Improper validation of telegrams received by the DNP3_NG driver may allow an attacker to affect the system stability
Summary Tests conducted with the DNP3_NG driver have uncovered an issue with the validation of received telegrams in the DNP3_NG driver. Further information can be found here DescriptionTests conducted with the DNP3_NG driver have uncovered an issue ...
Security Vulnerability: Improper validation of telegrams received by the DNP3 process gateway may allow an attacker to cause an instability of the system.
Summary Tests conducted with the DNP3 process gateway have uncovered an issue with the validation of received telegrams in the DNP3 Process Gateway. Further information can be found here Description Tests conducted with the DNP3 process gateway have ...
The 3S_V3 driver is not included for Windows CE platforms in the zenon 7.11 setup and that may result in an error on updating the CE device.
Summary An error message is displayed when attempting to update a Windows CE device with version 7.11 with all drivers selected: "Files not found: ..\3S_V3.dll - Your CE Runtime files are not complete. Make sure that the path exists and contains all ...
Secure communication between an OPCUA client and the OPCUA process gateway using a self-signed certificate does not work correctly.
Summary An OPCUA client can no longer establish a secure connection to the OPCUA server when a self-signed certificate is used. When using an application instance certificate that is signed by a Certifiate Authority, with a matching .crl file in the ...
The OPCUA client driver continues to send a publish request for a subscription even though the OPCUA server reports that the subscription is no longer valid.
Summary The OPCUA client driver sends publish requests for a subscription even though the 3rd party OPCUA server reports that this subscription is no longer valid. (0x80280000, BadSubscriptionIdInvalid, teh subscription id is not valid) Variables of ...
The OPCUA client driver should be able to represent special values in the runtime
Summary The special values NaN, NULL, +infinity and -infinity that variables in an OPCUA server can have, currently cannot be represented in the runtime. Description The special values NaN, NULL, +infinity and -infinity that variables in an OPCUA ...
Writing empty strings using Blockwrite and the setting "CHAR without header" with the S7TCP32 driver does not work correctly
Summary When using the S7TCP32 driver with blockwrite active, writing empty "CHAR without header" strings using e.g. recipe group manager, writes the empty string variables with the last used non-empty string value. Description When using the S7TCP32 ...
Columns no in the recipe table in the Recipe Group Manager screen no longer work correctly after disabling the right-most column
Summary After disabling the right most column for the recipe table for the Recipe Group Manager screen in the runtime through the filter settings, the other columns no longer behave as expected. The order of the columns is no longer correct and ...
Runtime closes unexpectedly when executing SAP function with parameter of unsupported datatype
Summary SAP RFCs might have input parameters with structures containing datatypes INT1 or INT2, even though these datatypes are not supported in ABAP4. When using such RFCs in zenon (SAP Interface), the runtime might close unexpectedly when executing ...