7.10
The OPC UA server in the process gateway does not correctly check the certificate revocation lists.
Summary When using a CA signed certificate for a OPC UA client, it is possible to place the CA root and any intermediate CA signing certificates, in the certificate trust list folder for the OPC UA process gateway. When using CA signed certificates, ...
Sometimes an unhandled exception occur when a deleted interlocking from the project analysis and when accessing an invalid pointer.
Summary If you have created an interlocking and connected it to a variable, select the variable at the variable list and search for all uses of variable. Then if you delete the interlocking and try to jump the project analysis view to the no longer ...
In a MultiUser - Project the client ID should be recycled.
Summary When a client was deleted and afterwards reconnected the client ID rolls over rather early causing negative variable IDs. DescriptionWhen a client was deleted and afterwards reconnected the client ID rolls over rather early causing negative ...
At the CEL display properties the graphics file and circle symbol were not correctly changed via language switch function.
Summary Under specific circumstances the CEL column settings Alarm/event class symbol and Alarm/event group symbol Display property it was not possible to change the language using the language switch function. Description Under specific ...
in strong meshed topology the calculation of ALC blocks Runtime
Summary In strong meshed topology, even by bearable quantity of switches, the ALC calculation can block Runtime (CPU load 100%) for significant time. Description In strong meshed topology, even by bearable quantity of switches, the ALC calculation ...
on network client the status bit NET_SEL is sporadically not set when the command input screen has MDI-element 'Lock list'
Summary Issue in zenon network on client: when user opens command screen via context menu and this screen includes MDI-element 'Lock list' then sometimes the status bit NET_SEL is not set. Then as the bit is not set the buttons in the command screen ...
IEC61850 Server: no handling for malformed Abort service request in TPAA association
Summary When during TPAA association a client uses Abort service request which is malformed the zenon Logic I/O driver IEC61850 Server does not response on service. Description When during TPAA association a client uses Abort service request which is ...
IEC61850 Server should refuse write to Resv when the URCB is enabled or already reserved by other client
Summary zenon Logic I/O driver IEC61850 Server should refuse any write to data attribute Resv (Reserved) in URCB (Unbuffered Report Control Block), when Resv is TRUE or RCB is enabled (RptEna=TRUE) by other client. Description zenon Logic I/O driver ...
In zenon network on client the command input called via context menu can cause an unhandled exception.
Summary The Runtime on the zenon network client can terminate with an unhandled exception when attempting a command input via the context menu. On the network server or in standalone project the command input works correctly. Description The Runtime ...
The iec870 driver does not set T_EXTERN status bit when receives IO with external real-timestamp
Summary Issue only in 7.10: the IEC60870 Master driver does not set T_EXTERN status bit when receives IO with external time stamp. Thus values with external time have correct timestamp (as sent by PLC) but no status bit T_EXTERN (nor T_INTERN). ...
Possible infinite loop in the zenon Logic Runtime when IEC61850 Server receives many Select commands
Summary Under circumstances the zenon Logic I/O driver IEC61850 Server can cause an infinite loop in the Logic Runtime when receives sequence of many Select commands. Description Under circumstances the zenon Logic I/O driver IEC61850 Server can ...
IEC61850 Client driver in zenon Logic stores received strings without termination null
Summary The zenon Logic I/O driver IEC61850 Client stores received strings in Logic database without termination null. These can cause problem in other drivers. Description The zenon Logic I/O driver IEC61850 Client stores received strings in Logic ...
IEC61850 Client driver uses GetDataValues service with multiple objects (Edition 1 of the Standard) but should use single object like introduced by tissue 854 to Edition 2
Summary The driver IEC61850 Client should use final solution from tissue 854, not from Edition 1 anymore. Description The driver IEC61850 Client should use final solution from tissue 854, not from Edition 1 anymore. Solution The implementation of ...
IEC61850 Server: a GOOSE messages not matching the definition can cause in Subscriber an infinite loop
Summary By reception of some incorrect GOOSE messages the zenon Logic I/O driver IEC61850 Server can go in infinite loop. Description By reception of some incorrect GOOSE messages the zenon Logic I/O driver IEC61850 Server can go in infinite loop. ...
IEC61850 Server: no buffer-overflow bit after a client sends wrong EntryID
Summary When a client reconnects and sends wrong EntryID as request for buffered reports the IEC61850 Server (zenon Logic I/O driver) logs an error and responses this MMS.Write negative. Then the IEC61850 Server sends all buffered reports - so acts ...
IEC850 Client driver when switches or reconnects and RCB is (still) enabled doesn't send GI nor polls variables
Summary Issue when IEC61850 Client driver (zenon driver or Logic I/O driver) are configured to use redundant IP addresses or by reconnect - when IED does not set free RCBs; when after connection loss, on IED, the RptEna stay TRUE. When previously the ...
The length of the filter text for the recipe filter in the Recipe Group Manager module is limited to 255 characters.
Summary The recipe filter in the Recipe Group Manager module is limited to 255 characters. For some applications this is not sufficient. Description The recipe filter in the Recipe Group Manager module is limited to 255 characters. For some ...
The audit trail entry in the Chronologic Event List for changing a recipe value contains the translated text rather than the keyword.
Summary If the project is configured to use the variable identification for display in the runtime, and a value in a recipe of the Recipe Group Manager is changed, the Chronologic Event List contains the translated text of the identification instead ...
Deleting an interlocking for a recipe variable of the Recipegroup Manager in the variable parameters dialog using the keyboard is not saved persistently.
Summary When deleting an interlocking for a recipe variable in the Recipegroup Manager module using the keyboard "del" key in the "change variable parameters" dialog, the interlocking appears to be deleted, however this is not saved. After closing ...
Changing only the properties "write synchonously" and "write timeout" for a Recipegroup Manager recipe in the editor is not correctly saved.
Summary When changing the properties "write synchonously" and "write timeout" for a Recipegroup Manager recipe in the editor, without making any further changes and then navigate in the project tree to a different module, the changes are not saved. ...
The DNP3 Process Gateway sporadically crash if more than 20 RT variables are added at once to the DNP3 PG in the assignment dialog.
Summary It correlates with the size of the zenon project, respectively with the amount of variables in the zenon project. The more variables the more possible is the effect. Description It correlates with the size of the zenon project, respectively ...
Alarming: flashing acknowledgment only acknowledges the most recent alarm of a variable
Summary If multiple alarms occurred (for example exceeding limit value 1 and then limit value 2, thereafter going back to 0; no alarm), a flashing acknowledgment should acknowledge all alarms, leading to the clear alarm list, the clear alarm bar and ...
IEC61850 Server ignores in SCL-file the trigger option 'gi' (general interrogation) for RCBs
Summary The SCL-file defines trigger options for each RCB; possible TrgOps are: dchg, dupd, qchg, period, gi. The IEC61850 Server (zenon Logic I/O driver) supports all TrgOps but only when configured by an IEC61850 client - when the client enables a ...
IEC61850 Server when an URCB is enabled but all triggers options are disabled than the reports are emitted
Summary Issue in IEC61850 Server (zenon Logic I/O driver): when an URCB is enabled but all triggers options are disabled (test case, has no practical use) than the reports are emitted by dupd (caused by change of timestamp) and Sequence Number is ...
IEC61850 Client driver ignores configuration setting for dynamic data set
Summary The iec850 driver (zenon and Logic) ignores the configuration settings for dynamic data set and enables RCB with the DataSet as it is currently in RCB, so also with empty name. There are no entries in Log about try to use/create dynamic data ...
zenon logic runtime does not start on a CE panel if a variable with profile IEC60870S is created
Summary Project with IEC60870S driver in Fielbus configuration using serial port for communication. Errormessage in output window: Opening bus driver 'T5Bus870Slave' for cold resp. warm start failed. Description Project with IEC60870S driver in ...
zenon logic stops if mobus slave connects to modbus master over serial
Summary zenon logic crashes if mobus slave connects to modbus master over serial. Written error message "Application STRATONRT.exe encounted a serious error and must shut down" Description zenon logic crashes if mobus slave connects to modbus master ...
zenon logic stops when loading a GSD file for Hilscher Profibus CIF driver
Summary zenon logic stops with error while loading a GSD file for Hilscher Profibus CIF driver. Description zenon logic stops with error while loading a GSD file for Hilscher Profibus CIF driver. Solution If names containing a % were used in a GSD ...
zenon Process Gateway ICCP sends zenon and not ICCP name variables
Summary zenon Process Gateway ICCP sends zenon and not ICCP name variables Description zenon Process Gateway ICCP sends zenon and not ICCP name variables Solution Now uses configured ICCP name on communication level. Information A possible ...
stratonrt: stratonrt immediately terminates if GER language is selected and OS language is english
Summary stratonrt immediately terminates if GER language is selected and OS language is english Description stratonrt immediately terminates if GER language is selected and OS language is english Solution Language depended cross references that ...
iec62056 driver stops working at the start of the RT with specific project
Summary iec62056 driver stopped with exception at the start of the RT. Driver settings: Communication over COM Net 1 Device address: 50039065 Enabled the checkbox "Read single registers" Description iec62056 driver stopped with exception at the start ...
Cannot create a CTI variable using driver object type V Memory
Summary In zenon 7.10 Editor (32 & 64 bit), if you have a pre-existing CTI variable, you cannot change its driver object type from K-memory to V-memory. Note: Even with creating a new variable based on CTI driver, V Memory object Type, REAL Datatype, ...
Report Viewer export/print function is not working without license
Summary The "Report Viewer: export / print" function doesn't work without Report module licensed. It is not mandatory to have a licence for the report viewer in Runtime. Description The "Report Viewer: export / print" function doesn't work without ...
Variable Import not possible from Jetter PLC
Summary The format of the *.jde file has changed. This needs to be adapted in the import wizard Description The format of the *.jde file has changed. This needs to be adapted in the import wizard Solution adapted code for import Issue Number: 30228 ...
Value of a variable is set to zero (0) after writing in zenon logic when the variable is from the straton to zenon runtime shared memory driver, and the zenon driver is set to simulation programmed
Summary With a modbus energy driver set to simulation programmed, and a variable of the modbus energy driver set to "externally visible", writing the variable in a zenon logic runtime sets the variable value to zero. The variable can be correctly ...
Straton to zenon Runtime connection handles special characters in variable names wrong (cross effects on name related variables in Runtime)
Summary Straton to zenon Runtime connection handles special characters in variable named wrong (cross effects on name related variables in Runtime) Description Straton to zenon Runtime connection handles special characters in variable named wrong ...
MATHDR32: Undefined variable in formula causes driver stop during Runtime Start
Summary MATHDR32: Undefined variable in formula leads to a stop of the driver when try to initialize the formulas. Description MATHDR32: Undefined variable in formula leads to a stop of the driver when try to initialize the formulas. Solution ...
Report Viewer: a language switch of the units does not work, the keyword is shown instead
Summary In the Report Viewer the language switch of the unit does not work. The keyword is shown instead. In the runtime in the pictures CEL, AML and archive revision and in the dynamic element "numerical value" the language switch of the units ...
If you print a report using the report viewer print function you get an Exeption for ReportViewer module if printer configuration was not correct.
Summary Invalid printer configuration (Copy paste the configured pdfcreator from online printing for all other printing scenarios) -If you print a report using the report viewer print function you get a exception. in Diagviewer you see the message: ...
IEC61850 Server opens TCP socket without activating KEEPALIVE
Summary On some devices, e.g. Windows CE, the IEC61850 Server I/O driver in zenon Logic does not activate KeepAlive by opening the TCP-socket. Thus after connection loss the socket stays open. Description On some devices, e.g. Windows CE, the ...
Next page