7.00
zenon-straton integrated solution on IEC61850: wrong handling of variables for file transfer
Summary In zenon-straton integrated solution basing on IEC61850 communication the zenon variables with special driver object types are not handled correctly in straton program; e.g. variables for File Transfer or State Info. Description In ...
The AML displays name of alarm class or group only when project property 'Alarm/event class color' has value "as text color"
Summary The Alarm Message List does not displays name of alarm class or alarm group when the project 'Alarm/event class color' is set not to default value "as text color". Description The Alarm Message List does not displays name of alarm class or ...
Variable name linked in action in command group cannot exceed 100 chars
Summary When in command group an action has command variable name longer as 100 chars the compiler in Editor hangs or even crashes. In zenon, in general a variable name can be 128 chars long. Description When in command group an action has command ...
On WEB Client in the Command screen the field 'Edit' are not supported when the screen has Title
Summary When command screen has activated Title then on WEB Client the fields for value editing do not show value nor can be edited. Workaround is to disable Title and design the look by your-self. Description When command screen has activated Title ...
In command screen the two-hands actions do not work with default settings
Summary In command screen the two-hands actions do not work anymore (up 7.0) - pressing CTRL activates display of "Execute2" button and it changes look by first click on, but then when you release the button it does not execute the action. It happens ...
When wrong configured Profinet driver stops the zenon Logic Runtime, the IEC61850 Server driver hangs
Summary Circumstances under which this can happen: zenon Logic (straton) project has Profinet driver and IEC61850 Server driver the Profinet does not have correct Adapter identification so cannot start the iec850 server has all settings OK. Issue ...
The IEC61850 Server does not handle correctly some combinations of TrgOps events arising in single Data Object
Summary The IEC61850 Server driver in zenon Logic (straton) should correctly handle all combinations of Trigger Options (TrgOps): dchg, qchg and dupd based also on each Data Attribute definition in the SCL, not only on RCB setting. In SCL-file there ...
Dynamic text color from a variable does not work in certain cases when variable limit uses palette colors
Summary When a numerical value and dynamic text element use text color from a variable limit which itself uses a color palette for limit color definition, the color is not set correctly. However when the color is set static, the colors are taken from ...
If an object is exported with the XML export and a different file extension than *.xml is used, no XML is being created
Summary It is possible to set different file extensions than *.xml in the XML export dialog. However, no file is being created if this is done. Description It is possible to set different file extensions than *.xml in the XML export dialog. However, ...
DNP332 driver with multiple serial stations configured stops communicating to further slaves when the first slave fails
Summary When in the DNP332 driver multiple DNP3 slaves are configured for a single serial bus, and the connection to the first slave fails, the DNP332 driver constantly attempts to reconnect to the first slave, and no longer tries to communicate to ...
DNP332 driver sequence of events is not correctly considered
Summary If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime. Description If multiple values are received by the DNP332 from an ...
linear value adjustment confgured at the variable is not correctly considered in RGM
Summary When a linear value adjustment is configured at a variable, this is not correctly considered in all circumstances in the Recipe Groups Manager. At reading and writing shadow variables and recipes, the adjusted range is not considered, and a ...
Access to the "Filter" dynproperty for Recipe Groups Manager groups through the programming interface returns no valid value
Summary The DynProperty "Filter" for Recipe Variables returns random characters in the programming interface, when no filter is defined for the recipe variable. Description The DynProperty "Filter" for Recipe Variables returns random characters in ...
The webclient closes unexpectedly under specific circumstances in the RGM screen
Summary Performing specific actions in the RGM screen on the webclient, like double click, or two clicks on the action for the recipe variable, or in the value column, can cause the webclient to close unexpectedly. Description Performing specific ...
ETM - Gantt chart is invisible with standard settings
Summary When you activate the Gantt chart in the extended trend and you leave the default setting for "Line width" (=0), then the Gantt chart isn't displayed. The problem is, that the standard setting = 0 and this setting is treated different in the ...
ETM: gantt curve is not lengthen if values are "on changed recorded"
Summary If you display archive data with type of scan "on change recording" the gantt curve will not be lengthen until a value change has been performed. Gantt curve will be lengthen if: Type of scan is "cyclic scanning" Gantt curve will not be ...
Variable links in RGM are lost on "Workspace save as" when using binary storage
Summary When using RGM with binary storage and variables linked at the recipe groups from different projects, the Project links are not correctly updated after executing a "Workspace save as", or after executing "replace project links". With Access ...
RGM function with Option "Duplicate" and "Duplicate and read" are not correctly converted
Summary When converting a 6.5x Project to Version 7.00, functions of the type "recipegroupmanager" with the Parameters "duplicate" and "duplicate and read" are incorrect after project conversion, when at the originating function a static recipe Group ...
IEC62056: if address is suffix of another address of the meter thevariable in zenon displays wrong data
Summary Meter value addresses are like 1.2.1 but if you put only address 2.1 in the address field you got also the value for 1.2.1, but you would have possibly also get value for 2.2.1 if it is the first in row. That means the driver only take into ...
VSTA code is no longer executed in the runtime in project copies created through the "Workspace save as..." function
Summary After creating a copy of the workspace and all its projects using the function "workspace save as.." the VSTA code in the project copies is no longer executed in the runtime. The VSTA code in the original projects is still executed correctly ...
XML-Import of an existing datatype: separated limit properties (i.e. limit text) are overwritten at the variable
Summary When an existing datatype is overwritten through XML import, limit properties at the variables that are based on this datatype, which were edited locally at the variable, are overwritten and are linked to the datatype again. Description When ...
The build setup does not install a required file for the IEC62056 driver
Summary The build setup does not install the IEC62056V.DLL file. This file is required by the IEC62056 driver in the editor, to allow configuration of the the IEC62065 address, as an alternative to the variable name, and in order to configure the ...
Limit value display in GANTT chart in extended trend is not correct when using a reaction matrix for the limit
Summary An incorrect value (1.797 e+308) is displayed as text in the GANTT chart in the extended trend when the variable for the GANTT chart uses a reaction matrix rather than a limit. Description An incorrect value (1.797 e+308) is displayed as text ...
Messages are not sent properly when using "Following Call" and user group name from string variable
Summary If desired user group name for "Send Message" function is taken from a variable, the first user receives a message. If this message is not acknowledged, the next user does not receive a message and the following CEL entry is created: "End of ...
XY Trend: the option read back the archive from the Backup folder is not considered
Summary For the XY Trend view it is not possible to read back data from backup folder. The setting / option 'Use archives from read-back folder' ist not considered. Description For the XY Trend view it is not possible to read back data from backup ...
Variable xml export/import does not consider parameters BACnetPropertyID and BACnetWritePriority for variables created on BACnetNG driver
Summary BACnetNG driver: the variable xml export/import in the editor does not consider the parameters BACnetPropertyID and BACnetWritePriority Description BACnetNG driver: the variable xml export/import in the editor does not consider the parameters ...
Driver Phoenix: connect to PLC ProConOS initialisation / timing problem
Summary When connecting to a PLC the driver sends REC_DATA telegram (without data) although it is not connected or logged in to the PLC. This leads to wrong and not working communication conditions that could even bring down PLC. Description When ...
The curve name in extended trend is cut if longer than the defined colum size
Summary In the screen switch function for an extended trend when adding a curve with the name like: 'MPLC.TSMU/AscentSys.VacuumPumps.P1.ACP_Inverter.Cmd.test' it will be cut to 'MPLC.TSMU/AscentSys.VacuumPum' Description In the screen switch function ...
The system driver variable "Invalid user Identification" only works with standard login dialog
Summary The system driver variable "Invalid user Identification" does not work if the screen type login for individual login screens is used. It works only with the standard login picture. It should be set always in case of input of wrong user or ...
LOGIX_ODVA driver: Unhandled Exception when using a variable with "Block array size" >2
Summary Allen-Bradley ODVA Treiber: Unhandled Exception when in the project there is a variable with "Block array size" >2 created on the Logix_ODVA driver. Description Allen-Bradley ODVA Treiber: Unhandled Exception when in the project there is a ...
Modbus Energy driver: When the set setpoint value is deactivated the driver does not read any events anymore
Summary When using the deactivate set setpoint value function for preventing write value commands the driver does not receive events anymore. When the set setpoint is deactivated although only the writing mechanism should be deactivated. Description ...
Driver BuR41xx32: connection lose occur after some hours runtime
Summary When the runtime runs for a longer time (some hours) the connection is lost. The diagnoseviewer logs following message: CBuR41xxObj::ParseString: Wrong Sequence Number (expected, is) Description When the runtime runs for a longer time (some ...
Screen switch function to Trend with option set: "show header in scan window in compatibility mode" do not show all curves
Summary When enable the settings "show header in scan window in compatibility mode" in the screen switch function to an extended trend screen, the first Curve is overwritten with the header in the scan window. Description When enable the settings ...
BeckhNG driver: RDA archive recording is started at runtimestart without trigger
Summary RDA archive recording is started at runtimestart without trigger. The memory usage of the driver goes up until its maximum and above, ending with unhandled exception. Description RDA archive recording is started at runtimestart without ...
BuRPVI driver: all Driver variables have invalid (I-Bit) status
Summary All variables from object type Driver variable of the BuRPVI driver get an invalid status. No error in the diagnosis viewer logged. Description All variables from object type Driver variable of the BuRPVI driver get an invalid status. No ...
MATSUTCP32 driver increases process handles when do a reconnect
Summary MATSUTCP32 driver reconnection increases handles in driver process. Could be seen in windows task manager, showing the process handles for the driver process MATSUTCP32.exe. The handles count up every time the driver tries to reconnect. It ...
graphics for switch elements are not displayed or display an incorrect value in the runtime
Summary Sporadically the graphics for switch elements may not display correctly or display the incorrect value DescriptionSporadically the graphics for switch elements may not display correctly or display the incorrect value Solution An issue has ...
Project information for functions in a script from different projects is not stored in the XML export of the script
Summary When a script contains functions from different projects, the project information is not saves when XML exporting the script. On XML Import, the functions from the sub projects are no longer linked DescriptionWhen a script contains functions ...
In the web client the archives in the historian of sub projecs cannot be accessed via the programming interface.
Summary When using the programming interface in the webclient, the archives in the historian from sub projects cannot be accessed DescriptionWhen using the programming interface in the webclient, the archives in the historian from sub projects cannot ...
Build setup installs incorrect Windows CE runtime executable causing RGM, Historian and Trend to fail on Windows CE 6
Summary The zenon 7.0 build setups up to build 5 install an incorrect zenon CE rutnime for Windows CE 6.0. As a result, after installing this build on a PC and updating a runtime on a Windows CE device, certain functionality is no longer available. ...