7.00
straton driver IEC61850 Server by import form SCL file: the Enum attributes get wrong data type INT, not SINT as it should.
Summary The straton driver IEC61850 Server by import of variables from SCL-file creates Enum attributes as variables of data type INT. It should use SINT like the Standard defines and zenon iec850 driver uses. For example the common-in-use attributes ...
zenon Logic Runtime does not start when for driver IEC61850 Server an Enum attribute was created as INT and not SINT
Summary Because of issue #26867, in some existing straton programs, the variables for Enum attributes, e.g. ctlModel were created with data type INT, not SIN as they should. Thus the old program cannot be used on new zenon Logic Runtime. The IEC61850 ...
The DNP3 driver may stop communicating under specific timing conditions after 49 days
Summary Under specific timing conditions the DNP3 driver may stop communicating after 49 days of continuous operation. A runtime restart is required to initiate the communication again. Description Under specific timing conditions the DNP3 driver may ...
The tree in the editor for the RGM module is not properly initialized under specific circumstances
Summary Under specific cirumstances the tree for the RGM module in the editor is not properly initialized. The tree is expanded but recipes are not visible. Instead an entry "..." is shown. When interacting with the tree in this state, the editor may ...
The editor closes unexpectedly when adding a block array variable to a RGM group again, after index 0 was deleted
Summary When using block array variables at a RGM recipe group, and deleting the block array variable with index 0 from the group, and adding the block array variable again, the editor closes with an unhandled exception. Description When using block ...
XML export of a standard recipe exports the wrong value when linear value adjustment is used
Summary When a variable used in a standard recipe uses linear value adjustment, e.g. PLC value 0-255 and zenon value 0-2.55, a value "1" in the recipe is incorrectly saved as a value "0.01" in the XML file when the recipe is XML exported. Description ...
The system variable "Online printing on/off" has invalid status at start of runtime
Summary The status of the system variable shows invalid until the switch online printing on/off is actually switched Description The status of the system variable shows invalid until the switch online printing on/off is actually switched Solution The ...
New keyword in ALARM.FRM and BTB.FRM file for "Resource label"
Summary In formatting files ALARM.FRM and BTB.FRM the possibility to use keyword for "Resource label" is missing. Thus this variable property cannot be printed the Alarm and Chronologic Event List. The Resource label property is used in projects ...
IEC870 driver over serial (101) cannot handle single control character 0xE5
Summary The IEC60870-101 Master driver cannot handle single control character 0xE5; when received it the driver stops to communicate. All variables get I-Bit until restart. Description The IEC60870-101 Master driver cannot handle single control ...
IEC61850 Server does not trigger report when value of an array element changes
Summary In straton/zenon Logic driver IEC61850 Server when a reported Data Object contains an array attribute, the value change of an array element does not trigger any Report. Description In straton/zenon Logic driver IEC61850 Server when a reported ...
IEC61850 Server refuses connection from Relab software client
Summary The IEC61850 Client from Relab software cannot connect to straton/zenon Logic driver IEC61850 Server. Description The IEC61850 Client from Relab software cannot connect to straton/zenon Logic driver IEC61850 Server. Solution The driver now ...
IEC61850 Server fails to import SCL-file with excessive xml-tags
Summary When a SCL-file contains an unsupported xml-tag - e.g. - in beside correct definition DAI, the straton/zenon Logic driver IEC61850 Server stops import the file. The error message does not have any details why the import failed and the tree ...
Editor stops responding with 100% CPU load when deleting an entry from the language table
Summary When an entry from the language table is deleted, a progress bar is shown and the editor stops responding. Description When an entry from the language table is deleted, a progress bar is shown and the editor stops responding. Solution An ...
API method UnloadedProjects() doesn't return unloaded sub projects
Summary When the API method UnloadedProjects() is used to return all unloaded projects from the workspace, unloaded projects that are included in a different project are not returned by the method. Description When the API method UnloadedProjects() ...
Messages that are created before runtime is exited can't be ackknowledged properly after runtime is restarted
Summary When a message is created by Message Control, the runtime is exited and restarted again, the message can't be acknowledged properly in certain circumstances. Description When a message is created by Message Control, the runtime is exited and ...
Message Control sending method Following Call and Endless Call do not work properly
Summary When the sending method Following Call and Endless Call are used in a Message Control Send Message function, the group is not run through. The Message Control MDI screen reports that an error during sending has occurred, although a message ...
Message Control message can't be acknowledged with PIN / NA code set in the Send Message function
Summary The projected PIN and NA code in the Send Message function should have higher priority that the ones set in the user administration. Although the correct PIN / NA code is entered in the acknowledgement, Message Control reports that the wrong ...
System Information Collector quits unexpectedly when Unicode text files are read
Summary The System Information Collector quits unexpectedly when it is trying to read Unicode text files. Description The System Information Collector quits unexpectedly when it is trying to read Unicode text files. Solution An issue was addressed in ...
Web Client closes unexpectedly when network encryption is enabled on the client but not on the server
Summary When there is an unencrypted communication projected on the server and a web client tries to connect which has encryption enabled, the web client closes unexpectedly. Description When there is an unencrypted communication projected on the ...
Web Client closes unexpectedly when attempting to execute functions without sufficient user permission
Summary When trying to execute a function without having the necessary permissions on a web client, the client closes unexpectedly with an unhandled exception. Description When trying to execute a function without having the necessary permissions on ...
Message Control does not communicate with certain GSM modem
Summary To check the availability of the modem, Message Control sends the "AT+ CPIN" command to check if the modem is ready for sending. Several GSM modems have a different answer to the "AT+ CPIN" command to which the Message Control did not react ...
When project is started with "adjust to monitor resolution" and the resolution differs from the projected one, rotated elements are not displayed properly
Summary When rotated elements are used in a screen, elements look like in the editor when the runtime is started in the present resolution. If "adjust to monitor resolution" is used, the same elements are not displayed correctly anymore. ...
Initializing voice modem for Message Control fails although configuration is done correctly
Summary Initializing modem for TextToSpeech and Audio sending method fails although configuration is done correctly. Description Initializing modem for TextToSpeech and Audio sending method fails although configuration is done correctly. Solution An ...
zenon Editor with operator license behaves unexpectedly when creating a second zenon logic project for one driver, when attempting to open the "created" project
Summary When licensed for zenon operator and trying to create a second zenon logic program for a driver that already exists in the project, the editor closes unexpectedly. Description When licensed for zenon operator and trying to create a second ...
straton IEC61850 Server does not start GOOSE because IdInst are empty in K5BusIec850s_GO.SCL
Summary When the driver's configurator ( K5* ) creates from particular SCLfile the file with GOOSE reception data model - the original ldInst became part of IED name. Then the driver does not start and the straton Runtime writes error message ...
The runtime server closes unexpectedly when editing a phase in specific circumstances
Summary When a batch recipe is running and a phase that is not yet active in this batch recipe is edited on the client in the phase edit dialog, the runtime on the server can close unexpectedly when the phase becomes active. Description When a batch ...
Performance of the stratonNG driver getting the event queue is slower than with the straton32 driver
Summary Not all value changes that take place in the straton runtime are communicated into the zenon runtime, there is also a significant performance issue with the StratonNG driver. The StratonNG driver taking 9ms longer to complete the same tasks ...
Zenon system drivers missing from the editor list
Summary If more than the one system driver (Sim32 , and MathDR)need adding after project creation the driver list does not allow for additional instances to be added to the project. Description If more than the one system driver (Sim32 , and ...
Profinet device I/O driver T5BusPNIODev.dll In Straton does not start (#26720)
Summary When loading certain projects with Profinet IO drivers in the system reports that slot x, sub slot x referenced cannot be found in configuration. This is due to some dll's needing updating. Description When loading certain projects with ...
HTTP tunnelling is not working properly when using IPv6
Summary If IPv6 is used in the network settings, no connection can be established when trying to connect over HTTP tunnelling. Description If IPv6 is used in the network settings, no connection can be established when trying to connect over HTTP ...
Runtime sometimes exits unexpectedly when trying to change substitute person for Message Control user
Summary When trying to change the substitute person for a Message Control user, the runtime sometimes quits unexpectedly. The frequency of this differs with the users trying to set as substitute person. Description When trying to change the ...
Message Control does not send message to substitute person if message was acknowledged with N/A code
Summary Message Control does not send message to substitute person if message was acknowledged with N/A code although a CEL entry says the message is sent. In the Message Control queue screen, the message is shown to be sent but in the Diagnosis ...
NaN values should be suppressed during SQL evacuation
Summary NaN values should be suppressed during SQL evacuation, since NaN values cannot be represented in SQL. Description NaN values should be suppressed during SQL evacuation, since NaN values cannot be represented in SQL. Solution The evacuation ...
When trying to open a screen from a converted 5.50 project in version 7.00, errors appear when opening a screen with symbols in it
Summary When a project that was created with version 5.50 is converted to version 7.00, errors appear when trying to open a screen that contains symbols. A message is displayed that the file xxx.sym could not be loaded. Description When a project ...
Editor exits unexpectedly when clicking in a cell in a Report Generator screen that uses a ComboBox
Summary Editor stops working when clicking in a cell in a Report Generator screen that uses a ComboBox element. This effect is very rare and hard to reproduce. Description Editor stops working when clicking in a cell in a Report Generator screen that ...
Editor stops working when using Drag&Drop on a structured data type element
Summary Editor exits unexpectedly when trying to to select an element of a structured data type and drag it somewhere. Description Editor exits unexpectedly when trying to to select an element of a structured data type and drag it somewhere. Solution ...
Message Control engine suppression for equipment modelling is not working properly
Summary A variable with equipment model RootNode.ChildNode is projected to send a message. If suppression is done for RootNode, suppressing messages seems to work (although this behaviour is faulty). If suppression is done for RootNode.ChildNode, ...
Send Message function fails if a user group projected in the global project is used
Summary Send Message function fails if a user group projected in the global project is used. The CEL shows following entry: "A Send Message function was executed for a group which does not contain any Message Control users!" DescriptionSend Message ...
Send Group, Following Call and Endless Following Call messages don't recognize MC users
Summary Message Control Send Message function does not work for user groups in the runtime properly. Also see #26855. Description Message Control Send Message function does not work for user groups in the runtime properly. Also see #26855. Solution ...
Switching point (on/off) in the scheduler is still active although it is set to inactive
Summary If a switching point is set to inactive in the scheduler, it is still active and the settings look like before. Description If a switching point is set to inactive in the scheduler, it is still active and the settings look like before. ...