Bitfields and ENUMs with Chinese type names are not reloaded - TEST BY TRIO
Description In a particular project, although Windows was configured for the Chinese region, bitfields and ENUMs with Chinese type names were not reloaded into Workbench. The issue has been addressed and bitfields and ENUMs with Chinese characters ...
CNetDrv: heartbeat timeout times out too soon on connection establishment
Description The CNetDrv driver attempted to connect to the MPU, but closed the TCP connection approximately 30ms after it was established with a log entry, that the heartbeat timeout of 1500 had expired. The issue has been addressed and the heartbeat ...
slave IEC60870 - timestamp sent on UTC when values are sent in local mode
Description The IEC60870 Slave fieldbus driver sends the time tag CP56Time2a in ASDUs as UTC time instead of local time. The issue has been addressed and the timestamp is sent now in the correct time zone. To benefit from this fix: Update your zenon ...
It should not be possible to create a POU with more than 128 characters
Description It is possible to create a program unit (main, subprogram, UDFB) with the name longer as 128 characters, but this results in unexpected behavior. The issue has been addressed and the POUs' names are limited now to 128 characters. To ...
Logic service sporadically crashes after stopping application if zenonRT logic driver is used
Description The Logic Service closed unexpectedly after the application was closed, when a Logic Service to Service Engine connection driver was used. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update ...
"Y Axis From" Setting Didn't work on Extended Trend Screen's Expanded Curvelist in v14
Description The “Y-Axis from” setting did not work correctly in the Extended curve list of the Extended Trend screen. When setting the "Axis from" value to a value lower than the current "Axis from" value, no change occurred. The issue has been ...
zenon 14 Smart Client: Invalid path when exporting a Trend
Description If a Smart Client on which the Engineering Studio was not installed was used to export a trend, an invalid path occurred. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon ...
API method RenameEx does not work correctly with names in braces
Description The API method RenameEx did not work correctly with names in braces. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or ...
S7TCP32: wrong behavior of ConnectionStates variable
Description The S7TCP32 variable ConnectionStates returned incorrect values and could not be used to monitor the connection status. The issue has been addressed and the value of the ConnectionStates variable now only changes when a change in the ...
Instance Name is missing for logic variables in logic fdb program referenced in 3rd level
Description The Instance Prefix for the name for zenon logic variables got lost in the zenon logic FBD program. The issue has been addressed and the Instance Prefix is available now. To benefit from this fix: Update your zenon Software Platform to ...
DNP3- The runtime t5x64 v14 crashes when downloading the t5.cod on a Ubuntu server 64bit
Description The Logic Service on an Ubuntu 64bit interface closed unexpectedly, when a zenon Logic project with DNP3 configuration (Master and Slave) was downloaded. The issue has been addressed and the Logic Service works now as expected after the ...
WVS "page acknowledge" and "page confirm acknowledge" are broken in the AML
Description The control elements Acknowledge page and Confirm acknowledgment page did not work anymore in the Web Visualisation Service. The issue has been addressed and the behavior of the control elements is now as expected. To benefit from this ...
Client Crash: 0xc0000409 = STATUS_STACK_BUFFER_OVERRUN
Description If a client sets a ‘Screen active’ variable that transmits its value to the server, the network requests and CEL alignments could cause the client's Service Engine to be terminated by the operating system (Windows event log exception code ...
sporadically S5TCP32 crashes
Description The S5TCP32 driver closed sporadically unexpectedly. The issue has been addressed and the driver communication is now stable. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or higher. Item ...
Engineering Studio crashes by changing of variables
Description The Engineering Studio closed unexpectedly when variable changes were made and afterwards a right-click on another variable was performed, before the changes were confirmed with Enter. The issue has been addressed and the behavior is now ...
AML - When a new alarm is added into descendingly sorted list with multiple selected lines, a new line is added to selection unintended
Description When a new alarm was added to a descending sorted list with multiple selected rows, a new row was unintentionally added to the selection. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update ...
Logic Studio: Importing a Library in a Logic project takes very long time
Description Importing a library into a zenon logic project took a lot of time. The issue has been addressed and the import time has been reduced. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 11 or higher. ...
SOT instance variables get unassigned from "SOT" variables after deleting any logic program
Description The SOT instance variables got unassigned from the SOT instance after deletion of any zenon logic program in the project. The variable properties were editable in the variable list after deletion of any logic program in the project. The ...
Unexpected error when compiling a FFLD program
Description While compiling a particular FFLD program the zenon Logic Studio reports mistakenly compiling errors. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the ...
Cannot export graphics for the X5Wiewer
Description In zenon Logic Studio the export of graphics for the X5Wiewer did not work properly because the *.ZIP file was not stored in the destination directory. The issue has been addressed and the file is stored at the desired directory now. To ...
Fieldbus Configurations - Compiler does not return an error when an array member's bit is used as a TAG/variable
Description In the zenon Logic Studio the compiler does not return an error when an array member bit is used as a TAG/variable. Only the zenon Logic Service refuses correctly to run the mistaken project. This issue has been addressed and the build ...
OPCUA State Variable Response During Ethernet Disconnection
Description In case of an Ethernet communication loss the OPC UA client state variable remained unchanged and did not provide information about the lost connection with an OPC UA server. The issue has been addressed and the OPC UA client state ...
Distributed Engineering: Changes in zenon Logic project cause all Services to be checked out
Description In the Distributed Engineering since zenon version 14 all services had to be checked out to make changes on an existing zenon logic project. The issue has been addressed and a check-out is not required anymore. To benefit from this fix: ...
CANbus - should not use the term "STRATON" in configurator dialogs
Description The term “STRATON” was used in the SSDO property name of the CAN bus driver. The “by STRATON” has been removed from the property name. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or ...
opcua processgateway - adding field in .ini breaks the gateway
Description When the “SERVER_URL=” field was added to the *.ini configuration of an OPC UA Process Gateway, the gateway did not open any listening ports anymore. The issue has been addressed and the behavior is now as expected. To benefit from this ...
Editor - combo of the parity on the communication setting for the serial communication
Description When Serial link has been selected in the Communication Settings dialog, the Parity drop-down list was empty. The issue has been addressed and the Parity drop-down list works now as expected. To benefit from this fix: Update your zenon ...
Active Directory: Not possible to change user password when password expires (e.g. User has to change password on next login) - The password could not be changed.
Description The user password could not be changed in Active Directory when it expired. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 10 or ...
AccessOPCUA: zenProcGateway.exe crashes under specific circumstances
Description zenon Process Gateway OPC UA Server may close unexpectedly when deleting a monitored item from an active OPC UA Subscription. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon ...
[MSI Interface] Changing the authorization level causes other fields to be modified in the appsettings.json file
Description Changing the authorization level in the MSI Interface caused other fields to be modified in the appsettings.json file. The issue has been addressed and other fields are no longer changed in case of authorization level changes. To benefit ...
CNetDrv: Sequence number in acknowledge message should be the same as the sequence number in the SOE response
Description In the CNetDrv driver the Sequence number in the acknowledge message was not the same as the Sequence number in the SOE response. The issue has been addressed and the Sequence number is now the same in the acknowledge message and the SOE ...
Azure TLS connections do not follow Operating System standards with regard to the TLS version
Description The TLS connections were not following the Operating System defaults and were using an older TLS version. The issue has been addressed and the TLS connections now follow the Operating System defaults and use the current TLS version. To ...
Reload of the historian module is performed concurrently with the historian recording thread
Description The reloading of the historian was done at the same time as the historian recording thread and sometimes resulted in an unexpected closure. The issue has been addressed and the historian will now shut down when the reloading begins. To ...
[MSI Interface] Number format from the Operating System configuration, not supported by the MSI, prevents message from being sent correctly
Description The number format from the operating system configuration which is not supported by the MSI Interface, prevented the message from being sent correctly. The issue has been addressed and the message is sent now correctly. To benefit from ...
Released Properties disapear when "History of changes is active" in the Project
Description The released properties disappeared when "History of changes is active" was activated in the project. The issue has been addressed and the released properties are no longer lost. To benefit from this fix: Update your zenon Software ...
CANbus - No message when we can't import DBC file with bad syntax
Description If an import of a DBC file with a bad syntax failed, no message was displayed. The issue has been addressed and an error message is shown now. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 ...
SOT : crash when creating a new SOT
Description The creation of a new SOT via the Equipment Group led to an unexpected closure after a switch between projects. The issue has been addressed and the behavior is now as expected. To benefit from this fix: Update your zenon Software ...
[MSI Interface]Too many Exception Messages are sent
Description If the “Alarm acknowledged” option was used for alarm-based exception messages, a message was sent incorrectly when the alarm occurred. The issue has been addressed and wrong shipments are no longer executed. To benefit from this fix: ...
EUROMAP63: In specific scenario when a machine is providing a .DAT file which has the header located in the middle of the file this results in reading in an endless loop by the driver which also leads to a huge amount of log entries in the diag viewer
Description Issue in the EUROMAP63 driver when parsing a DAT file provided by a device, where the header is not in line 0, but in some lines in the middle (e.g. line 9). The driver reads the file in an endless loop, resulting in a large number of ...
Coloring FBD lines - Lines in UDFB Instance are sometimes not correctly colored
Description The UDFB lines were sometimes not colored correctly (remain grey). The issue has been addressed and the coloring is now as expected. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 14 or higher. ...
eSignature CEL entries are not logged when setting values via RGM
Description When setting values in the RGM directly from the SETVALUEKBD keyboard (via the control element Write set value), the eSignature dialogue appeared but the CEL entries were missing. This issue has been addressed and the CEL entries are now ...