11
Crash Exception 0xC0000005 AccessOPCUA.dll!cs::opcua::server::CSubscription::getSessionId
Description The OPC UA Process Gateway causes Exception 0xC0000005 in some situations when reloading. This has been fixed. The OPC UA Process Gateway routine for Subscription/Session management has been improved, assuring robust reload and reconnect ...
Variable in CEL not correct when using eSignature in Multiproject
Description In an integration project, wrong variables are written to the CEL when using eSignature. Integration project and subproject have variables with the same names. When signing an operator action, the variable from the other project is ...
License Manager always crashes directly when opened
Description When opening the License Manager, it crashes. The log file refers to a locked license.ini file. This error has been fixed. To benefit from this fix: Update your zenon Software Platform to the latest build of zenon 10 or higher. Item ID: ...
All archive files from Server 2 are synched to Server 1 in non dominant redundancy systems because of additional byte in archives.
Description When operating in non-dominant redundancy, all archive files are always synchronized when switching redundancy from server 2 (as standby) to server 1. This means that even those files that have not changed are synchronized. ...
Dynamic text property Write on lost focus is not working for numerical variable
Description In order to write the "Set value" when the "Dynamic text" element loses the focus, the "Write on lost focus" property is used. But with zenon 11 this does not work for numeric variables. The numeric value is not written when the focus is ...
S7TIA: When a datapoint has a specific invalid symbolic address, this datapoint does not have INVALID bit in service Engine, but has SPONT bit although the value which is displayed in the service engine is not the correct one
Description If a S7TIA variable has a certain invalid symbolic address, this variable shows a SPONT bit instead of INVALID in the Service Engine in spite of incorrect symbolic addressing. This occurs mainly if the symbolic address contains ...
Screen container in faceplate screen, changes size when Service Engine title is active
Description For screens of type Faceplate, the screen container in the Service Engine changes its size if a title is selected for the “Service Engine caption” property. In this case, the height of the screen container is increased by the height of ...
IMM Maintanance preview filters show no results
Description In the screen of the Industrial Maintenance Manager (IMM) type, all pending maintenance tasks are displayed in a list. When filtering for certain dates, tasks are not displayed, although they exist. This error has been fixed. Filters are ...
Command Processing: After executing successfully a command it is shown "Timeout for execution"
Description Command Processing shows a "Timeout for execution" after successful execution of a command. The cause is mismatching units of the timer ticks read from PC clock on systems running without PC restarts. The issue could also affect the ...
Write set value via Element only allows as many digits as element is wide when using a numeric variable with Numeric Value or Dynamic Text field - SE
Description If a numeric variable with numeric value and Dynamic Text elements is used for "Write set value via Element", the number of allowed digits is arbitrarily limited. The limit is set in the Service Engine by the actual width of the element. ...
Loss of function call links during a Z10 to Z11 project conversion.
Description When converting a project from version 10 to version 11, linked function calls are lost. The links are present with the buttons. However, they cannot be executed. This error has been fixed. Links to function calls work as expected after ...
Function 'Start/Stop Project Service Extension' - export + import loose start/stop-setting
Description When the function "Start/Stop Project Service Extension" is exported via XML, it loses its configuration. On import, its setting always shows the default value "Stop", regardless of the actual setting before export. This behavior has been ...
OPC-UA Process Gateway crashes if a Client using "OPC-UA Client Driver" disconnects and reconnects again after the Timeout
Description The OPC-UA Process Gateway has issues when losing connection to a Service Engine with OPC-UA Client Driver. If the connection is lost during operation, the Process Gateway crashes with an unhanded exception after reconnecting to the ...
RGM import status doesn't change value on missing file or if the variable value is outside of min max values
Summary RGM import status doesn't change value on missing file or if the variable value is outside of min max values. The absence of a file is now displayed correctly. Values that lie outside a range must still be eliminated by the creator. ...
the comment options for the esignature property are activated after an xml import
Description When importing a screen via XML, the checkboxes for the comments are not set correctly for e signature. Although these properties were inactive on export, they are enabled on import. This affects: Comment for "Perform" required Comment ...
Web Engine Compiler fails with fatal error for SSF EQM
Description In a project, a screen of the type Equipment Modeling is opened. If this project is compiled for the HTML Web Engine, the compiler crashes with a compilation error message. Without this screen the compilation works correctly. This error ...
Runtime Crash when Datafolder Information to a disconected drive.
Description When starting the Service Engine or Smart Client, the data folder configured for the project is not available. The Service Engine or Smart Client crashes as a result. This behavior has been fixed. Service Engine and Smart Client start ...
The Zenrt32.exe can´t be terminated via the Exit Service Engine Function, when the Login with Dialog Function is used
Description When the "Exit Service Engine" function is executed in a screen of the "Login with Dialog" type, the Service Engine crashes. This behavior has been changed. Exiting the Service Engine using a function in the "Login with Dialog" type ...
User who has not defined a lock code can lock and unlock switches
Description In the Command Processing, a user without a defined Lock code can lock and unlock switching operations. This could only be prevented if a Lock code was set for all users. Since often, especially in the Active Directory environment, a ...
Alarmcauselist starts with an expanded contextlist - taking very long to show up (service engine is blocked)
Description Loading the Alarm Causes List takes a long time if the Context List is opened with expanded layers and many entries. In the screen of the Context List type, the state on opening can be defined. If the preconfigured dialog in the Service ...
SmartClient: Functions from Integration projects are not available in Subprojects in first start
Description When a project with subprojects is started for the first time, functions from the integration project are not available for subprojects on the Client. After restarting the Client, the functions are available. This behavior has been ...
Language table wizard corrupts project
Summary Running the Language Table Wizard corrupts the project. This has been fixed. Description The Language Table Wizard causes errors when run with the options "Convert texts into keywords" and "Linked symbols". The entries in the language table ...
Engineering Studio crash: PFS Copy / Paste of corrupted Schedule (error: is linked with invalid variable)
Description A schedule is copied in the PFS that contains missing or invalid variables. During this process, the Engineering Studio crashes. This behavior has been changed. Corrupted schedules no longer cause a crash during copying. While generating ...
S7TCP32: optional support for high-precision-timestamps with Alarm_8P
Description The S7TCP32 driver has been enhanced with optional support for taking over the high-precision timestamp at the alarm 8P variables contained in the associated values provided by certain systems. This feature can be enabled via a new driver ...
WVS crash with specific project
Description The WVS crashes with a certain project immediately after the start. This project has defined an ETM screen or a Login screen as the startup screen, which do not contain screen filters. Starting the Service Engine with these screens is not ...
Archive variable selection in the Service Engine for the extended trend, the selection table is always set to the default state.
Summary In the Service Engine, in the Extended Trend screen, the columns in the table for selecting archive variables are always reset to the default state. This behavior has been adjusted. Description In the Service Engine, the columns in the table ...
AccessDNP3_SG: version 10 integrated gateway configuration is empty after converting the project in version 11 and version 12
Description After converting a project to version 11 or 12, the DNP3 points previously configured in version 10 are not visible. The Process Gateway configuration is empty. This issue has been fixed. To benefit from this fix: Update your zenon ...
Instance Screen does not show graphic files after SO update
Description A Smart Object Template contains graphic files. After updating the template, the graphic files are no longer displayed in the instance screen. This issue has been fixed. To benefit from this fix: Update your zenon Software Platform to the ...
AccessIec870Sl: CEL entries are created for direct execute commands for T00 ASDU types
Description The Process Gateway IEC 60870 slave no longer logs messages for internal ASDU type variables (T00) if the option "Log commands in CEL" is enabled. This behavior has been changed. To benefit from this fix: Update your zenon Software ...
OPCUA32 driver crashes when an incorrect browse name is specified
Description If a wrong or invalid variable browse name is specified for the OPCUA32 driver, the driver crashes when the zenon Service Engine is started. This error has been fixed. The driver does not crash anymore. A list of invalid elements is now ...
3D-Tool: Function execution not properly triggered when clicking on a 3D element that is linked to a function
Summary In the zenon Service Engine 3D-Tool, clicking on an element within the 3D model does not trigger the associated function. This has been fixed. Description In very complex 3D models, rendering can lead to delays if the hardware is ...
AccessIec870Sl: Gateway Closes with exception after receiving an invalid message
Description If in the Process Gateway the IEC870Sl receives a specific invalid message, it is closed with an exception. This behavior has been changed. The IEC870Sl has an improved detection for invalid messages. Invalid messages are ignored. To ...
RGM: Recipe list "User for last change" is cleared after executing a recipe action
Description In the RGM, after an action has been performed in the recipe list, the user who performed this action is not displayed in the "User for last change" column. The corresponding entry is empty. This behavior does not occur with terminal ...
Engineering studio: crash when adding symbol to screen in some circumstances
Description In some cases the zenon Engineering Studio crashes with an unhandled exception when a symbol is linked to a screen. Embedding the same symbol works as expected. This behavior has been changed. Linked symbols behave as expected again. To ...
Service Engine: the maximum amount of archive data read with a 64 bit version is still limited to 4294967295 bytes - (SPEICHER=4295000 appears to result in an overflow)
Description When a higher memory limit than 4GB was configured for loading historical data with a 64 bit Service Engine on a system with sufficient free physical memory, an overflow of the limit value occurres and less memory than 4GB is used. This ...
Internal variables with calculation "Network" as index variable cause performance and consistency problems
Summary Index variables cause long waiting times when replaced on the client. This problem was solved by a cash. Description For internal variables, the Calculation property is set to Network. These variables are used as index variables. During ...
zenon Logic - Import using XMLMERGE of K5B.exe stucks with certain XML
Description When importing a zenon Logic XML file with XMLMERGE via K5B.exe the import does not finish; the process hangs in an endless loop. When using workarounds, the import seems to finish successfully, but not all elements are imported. But the ...
Report Engine connectors return wrong status bits
Summary Report Engine Connectors return incorrect status bits in various constellations. This behavior has been fixed. Now the correct status bit is returned. Description Report Engine connectors return incorrect status bits in various ...
Report Engine SQL connector delivers comment as computer name for events
Description When the SQL Connector for CEL is used with the Service Engine that writes the CEL to SQL memory, an error occurs: In the column Computer Name the comment is displayed instead of the computer name. This behavior has been fixed. Now the ...
AML and CEL continuous export write an empty text for dynamic limit texts that do not use other variables
Description In a zenon project "Long dynamic limit texts" are disabled for AML or CEL. An entry for reaction matrix or a variable limit value uses dynamic content but does not refer to other variables. For example: " $The value is ;%v". The entry has ...