Service Engine doesn't auto-start Logic service without 'Studio Edition Pro' license
Summary Service Engine doesn't auto-start Logic service without Logic Workbench license Description Service Engine doesn't auto-start Logic service without Logic Workbench license Information We have now updated the urgent license and the customer ...
AccessIec870SL: T00 IOA variable IOA19 / IOA8 are not considered correctly under specific circumstances in version 10 and 11
Summary The variables T00_8 and T00_19 where deleted if necessary in a single function. This function now is split off in to separate functions to achieve precision when one of it must be deleted. Description The variables T00_8 and T00_19 where ...
print of report generator in webclient : png, bmp, jpg, gif are not print
Summary Smart Client cannot print bitmaps in reports of report generator Description Smart Client cannot print bitmaps in reports of report generator Issue Number: 239018 Fixed on Date: 12.1.2022 Versions: 8.20 0 BUILD 94608 | 10 0 BUILD 94554 | 8.10 ...
Inconsistency in Recorded User Data if Signature without Password is used
Summary If you use the "Signature without password" property and login with another user name via the Login Function, there is an Inconsistency in CEL Recordings. If you login two times (one time via the Signature without password Login Dialog and ...
CEL Files from 6.22 not compatible with newer zenon versions > 8.x
Summary CEL files from versions earlier than 6.50 cannot be read in versions 8.00 and higher Description CEL files from versions earlier than 6.50 cannot be read in versions 8.00 and higher Information No Workaround possible Issue Number: 247664 ...
Archive Revision font size change has different behaviour in version > 8.10 than previous
Summary Row height doesn't fit font size in archive revision screen Description Row height doesn't fit font size in archive revision screen Information not found so far Issue Number: 242922 Fixed on Date: 16.12.2021 Versions: 8.20 0 BUILD 94608 | 10 ...
Write set value/change by" property of the "Numerical Value" object does not allow to set a value less than variable measuring range min"
Summary Setting a delta value (change by) is now As youof the "without dialog" activation Description Setting a delta value (change by) is now As youof the "without dialog" activation Information Only worked while "without dialog" was activated. ...
Big performance issues on creating smart object instances (issue related to symbols)
Summary Adding new symbol to symbol library takes very long if library already contains a lot of symbols Description Adding new symbol to symbol library takes very long if library already contains a lot of symbols Issue Number: 244874 Fixed on Date: ...
ETM: Runtime is crashing under certain circumstances when using curve property for auxiliary lines
Summary ETM: Runtime is crashing under certain circumstances when using curve property for auxiliary lines Description ETM: Runtime is crashing under certain circumstances when using curve property for auxiliary lines Issue Number: 244749 Fixed on ...
Reporting Studio: Unexpected close when trying to create a subscription for custom report
Summary The problem was caused by a parameter with an expression-generated default value (TimeSpan parameter) having a dependency to another parameter. In this case there was no expression value available and the dialog was not prepared for that. ...
RT crash after reload - changes made in variables
Summary Sometimes ServiceEngine crashes after reload if archive evacuation fails immediately before the reload Description Sometimes ServiceEngine crashes after reload if archive evacuation fails immediately before the reload Issue Number: 247623 ...
IEC 60870 Process Gateway: support for UTC time
Summary Issue Number: 246335 Fixed on Date: 20.12.2021 Versions: 10 0 BUILD 94554
Symbol with released property (Variable Visibility) does not work properly
Summary If a variable property and range properties based on this variable are exported from symbol the sequence of application of override values in screen is undefined. This leads to unpredictable behavior if variables with different value ...
Batch Control: Master recipe cannot be checked produces a continuous freeze of Service Engine
Summary Fixed performance issue in batch recipe path analysis for specific recipe structures. Description Fixed performance issue in batch recipe path analysis for specific recipe structures. Issue Number: 247609 Fixed on Date: 12.1.2022 Versions: 10 ...
OPCUA32: driver crashes on writing specific array elements with access to arrays on element index disabled
Summary Implemented writing EnumValueType , fixed writing String Type. Description Implemented writing EnumValueType , fixed writing String Type. Issue Number: 247461 Fixed on Date: 10.1.2022 Versions: 10 0 BUILD 94554
AML SQL export function do not export value for LASTING_S (values always 0)
Summary column LASTING_S is always 0 in SQL export of alarms Description column LASTING_S is always 0 in SQL export of alarms Information no workaround Issue Number: 248130 Fixed on Date: 18.1.2022 Versions: 10 0 BUILD 94554
S7TIA communication closes and restarts when for a variable that is not existing on the PLC will be set a value
Summary The S7 TIA driver disconnects after writing a variable with invalid address Description The S7 TIA driver disconnects after writing a variable with invalid address Issue Number: 248999 Fixed on Date: 11.2.2022 Versions: 7.60 0 BUILD 95308 | ...
Incorrect display of combo boxes in world view, when using zoom levels
Summary Combobox and combolist elements now get better resized with world view zoom. Some specific elements (win32 control based) now have correct size and position in world view. Description Combobox and combolist elements now get better resized ...
Active Directory: zenon logon screen does not adopt the configured policies from the AD user group policy
Summary Under specific circumstances locked out users are treated as locked out for longer than configured Description Under specific circumstances locked out users are treated as locked out for longer than configured Information 1- Wait more than 3 ...
OPCUA driver: incorrect value for ConnectionStates variable if connection failure
Summary - Description - Information Connection failure could be checked by checking a invalid flag of a variable. Issue Number: 246722 Fixed on Date: 14.2.2022 Versions: 8.20 0 BUILD 95599 | 10 0 BUILD 97200
T5BusIec850s.dll IEC61850 Server does not set PurgeBuf=False after purging BRCB buffer
Summary Buffer is purged immediately after getting request. Description Buffer is purged immediately after getting request. Issue Number: 248468 Fixed on Date: 14.2.2022 Versions: 8.20 0 BUILD 95599 | 10 0 BUILD 97200
When a linearization is applied, the Write set value/change by" property of the "Numerical Value" object does not allow to set a value within variable measuring range"
Summary - Description - Information - Issue Number: 247713 Fixed on Date: 18.2.2022 Versions: 8.20 0 BUILD 95599 | 10 0 BUILD 97200
In HTML5 Screen Element Numeric Value is not displayed correctly
Summary - Description - Issue Number: 248713 Fixed on Date: 23.2.2022 Versions: 8.20 0 BUILD 95599 | 10 0 BUILD 97200
Evaluation of the reaction matrix of a real variable doesn't work correctly
Summary For specific values of REAL variables a comparison to equaility doent's work as expected in reaction matrix Description For specific values of REAL variables a comparison to equaility doent's work as expected in reaction matrix Information ...
OMRON_EIP, LOGIX_ODVA: High CPU usage performance problem
Summary With this fix CPU consumption is lowered back as expected in previous version. Description With this fix CPU consumption is lowered back as expected in previous version. Issue Number: 248996 Fixed on Date: 2.3.2022 Versions: 8.20 0 BUILD ...
OMRON_EIP: when use block access" is enabled, the values in the first read response are not sent to the Service Engine"
Summary The bug influenced every read request, not just the first one. Now the synchronisation is enhanced and value changes are shown up in the corresponding hardware cycle. Description The bug influenced every read request, not just the first one. ...
Process Gateway IEC 60870-5-101 slave does not send a correct response when an unsupported ASDU is received
Summary When an unsupported ASDU is received the 870 101 slave did not correctly send a link layer confirmation, causing a communication interruption Description When an unsupported ASDU is received the 870 101 slave did not correctly send a link ...
Incorrect representation of the &" character in user group name during runtime"
Summary MDI touch listbox does draw '&' correctly . Description MDI touch listbox does draw '&' correctly . Information not available Issue Number: 249447 Fixed on Date: 4.3.2022 Versions: 8.20 0 BUILD 97396 | 8.00 0 BUILD 97572 | 10 0 BUILD 97200 | ...
Save Method in StandardRecipes has a false Name
Summary Method "Save" accidentially is called "DuplicateRecipe" in class StandardRecipes (AddIn-Framework) Description Method "Save" accidentially is called "DuplicateRecipe" in class StandardRecipes (AddIn-Framework) Issue Number: 249646 Fixed on ...
Sometimes decryption of network pakets fails if pre-shared key is enabled
Summary Sometimes decryption of zenon network pakets fails if pre-shared key is enabled Description Sometimes decryption of zenon network pakets fails if pre-shared key is enabled Issue Number: 249774 Fixed on Date: 9.3.2022 Versions: 8.20 0 BUILD ...
A dot in the lot name leads to an incorrectly displayed file name when using the archive export function
Summary File name for archive export does only contain lot name part before last contained dot Description File name for archive export does only contain lot name part before last contained dot Issue Number: 249934 Fixed on Date: 15.3.2022 Versions: ...
MetadataSynchronizer API-Event 'SynchronizationCompleted' sporadically does not trigger
Summary The event is now always triggered correctly. Description The event is now always triggered correctly. Information Crude: Program-which-waits-for-the-event needs a timeout; after the timeout it has to check independently in ...
SIMUL32 tags counted as to be licensed
Summary SIMUL32 variables count as tags to be licensed Description SIMUL32 variables count as tags to be licensed Issue Number: 250166 Fixed on Date: 22.3.2022 Versions: 8.20 0 BUILD 97396 | 10 0 BUILD 97200
S7TCP32: Driver is not able to process fragmented (ISO 8073/X.224) packets, driver does not consider parameter Last data unit""
Summary S7TCP32 driver does not correctly re-assemble fragmented COTP frames Description S7TCP32 driver does not correctly re-assemble fragmented COTP frames Issue Number: 250246 Fixed on Date: 23.3.2022 Versions: 8.20 0 BUILD 97396 | 10 0 BUILD ...
Smart Client to Service Engine connection blocked by SVG-Element after second connection
Summary Sporadically Smart Client cannot connect to server if SVG element is used. Issue Number: 250274 Fixed on Date: 24.3.2022 Versions: 8.20 0 BUILD 97396 | 10 0 BUILD 97200
Comtrade viewer WPF element can't read files where the date/time stamp is not zero padded
Summary - Description - Issue Number: 249678 Fixed on Date: 11.4.2022 Versions: 8.20 0 BUILD 97396 | 10 0 BUILD 97200 | 10 0 BUILD 98635 | 8.20 0 BUILD 99641
RGM: Recipe Group Export wont work in regions with a / in the date-time
Summary - Description - Issue Number: 249744 Fixed on Date: 1.4.2022 Versions: 8.20 0 BUILD 97396 | 8.00 0 BUILD 97572 | 10 0 BUILD 97200 | 8.10 0 BUILD 99638
Screens containing SVG element crashes on opening
Summary Crash is resolved now Description Crash is resolved now Information Remove element from project/screen. Issue Number: 247444 Fixed on Date: 20.12.2021 Versions: 10 0 BUILD 97200
Metadata synchronizer has problems with multiple projects that define languags
Summary The project data synchronisation process in the Report Engine was fixed and now follows these steps (compare to predecessor bug): First, those items are synchronised in parallel with one task per item: alarm/event classes alarm/event group ...
Exception in Smart Objects get_ReleasedPropertyCollection by APIs
Summary Now there are no Exceptions like mentioned in BUG. Still you will get Remas released property value to NULL because the other bug is still in progress. Description Now there are no Exceptions like mentioned in BUG. Still you will get Remas ...