10
zenon logic service version 10 for raspberry pi does not start on current buster (debian 10) distribution
Summary zenon Logic service uses some functions from GLIBC 2.29 which is not available on Raspbian Description zenon Logic service uses some functions from GLIBC 2.29 which is not available on Raspbian Issue Number: 239641 Fixed on Date: 13.4.2021 ...
OPCUA32 crash: Reloading â Symbolic Addressâ or â Browse nameâ changes
Summary Fixed a possible crash if the monitored items from a suspension could not be correctly unsubscribed when reloading. Description Fixed a possible crash if the monitored items from a suspension could not be correctly unsubscribed when ...
Korea Bank Holiday is missing in the Feiertage.txt.
Summary Feiertage.txt is located in C:\ProgramData\COPA-DATA\zenon820 Description Feiertage.txt is located in C:\ProgramData\COPA-DATA\zenon820 Information It is discovered by customer. They don't use calendar automatically. They need to edit the ...
Feiertage.txt is not complete
Summary - Description - Information manual extension Issue Number: 239627 Fixed on Date: 13.4.2021 Versions: 8.20 0 BUILD 82266 | 10 0 BUILD 83962
Selecting colours live Updates is not working for color gradient fill" (all Elements), "color border" (Button Element) and "fill color (Combined element)"
Summary The color live updates will be processed correctly . Description The color live updates will be processed correctly . Issue Number: 240837 Fixed on Date: 11.5.2021 Versions: 8.20 0 BUILD 83630 | 10 0 BUILD 83962 | zenon Analyzer 3.40 0 BUILD ...
Implement New Code Signing certificate 2021
Summary Issue Number: 240494 Fixed on Date: 11.5.2021 Versions: 8.20 0 BUILD 83630 | 7.60 0 BUILD 83995 | 10 0 BUILD 83962 | 8.20 0 BUILD 84627 | 8.10 0 BUILD 84784 | 8.00 0 BUILD 84785 | zenon Analyzer 3.40 0 BUILD 87645
T5BusProfNetIO: stratonrt closes unexpectedly when receiving invalid ProfiNet DCP frames (mulitple issues)
Summary An issue has been resolved where invalid ProfiNet DCP frames could lead to the unexpected stop of the ProfiNet IO Device and ProfiNet IO Controller driver. Description An issue has been resolved where invalid ProfiNet DCP frames could lead to ...
active directory : user lock after connection attempt, wrong number
Summary Wrong password is counted twice if foreign domain is used Description Wrong password is counted twice if foreign domain is used Issue Number: 240377 Fixed on Date: 3.5.2021 Versions: 8.20 0 BUILD 83630 | 10 0 BUILD 83962 | zenon Analyzer 3.40 ...
Selecting colors is not working fine for the screen elements on ES
Summary liveUpdates are in the game again . Description liveUpdates are in the game again . Issue Number: 239838 Fixed on Date: 11.5.2021 Versions: 8.20 0 BUILD 83630 | 10 0 BUILD 83962
Incorrect IP Address is configured for IEDs in IEC850 Driver Configuration Wizard from Specific SCD file
Summary Incorrect IP Address is configured for IEDs in IEC850 Driver Configuration Wizard from Specific SCD file Description Incorrect IP Address is configured for IEDs in IEC850 Driver Configuration Wizard from Specific SCD file Issue Number: 210972 ...
zenon Logic redundancy: using DNP3 fieldbus, Logic crashes after switching Logic redundancy
Summary _. Description _. Issue Number: 240120 Fixed on Date: 29.4.2021 Versions: 8.20 0 BUILD 83630 | 8.10 0 BUILD 83099 | 10 0 BUILD 83962 | 8.00 0 BUILD 84785
Editor crashes when deleting an element
Summary Engineering studio sporadically crashes if screen element is deleted which was found by "find element" first Description Engineering studio sporadically crashes if screen element is deleted which was found by "find element" first Issue ...
Command Processing: NET_SEL Statusbit gets stuck sporadically
Summary Under rare timing situations the command screen was switched to invisible but never closed. Description Under rare timing situations the command screen was switched to invisible but never closed. Issue Number: 239702 Fixed on Date: 22.4.2021 ...
Engineering Studio crashes when instancing SOT
Summary Under certain circumstances, the Engineering Studio closes unexpectedly when creating an instance of or updating a Smart object template. Description Under certain circumstances, the Engineering Studio closes unexpectedly when creating an ...
SPRECON870 driver: If the setting internal connection" is active commands will no longer be provided to the OEM.dll"
Summary - Description - Issue Number: 240903 Fixed on Date: 20.5.2021 Versions: 7.60 0 BUILD 83995 | 10 0 BUILD 83962 | 8.20 0 BUILD 84627 | 8.10 0 BUILD 84784 | 8.00 0 BUILD 84785 | zenon Analyzer 3.40 0 BUILD 87645
OPCUA32: interoperability issue with empty arrays when calling a method without InputArguments
Summary - Description - Issue Number: 241018 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
The function â Export CELâ incremental to SQL donâ t works with converted zenon projects in V10.
Summary Incremental CEL export into SQL doesn't work if project property for maximum CEL text length has a value different to 128. Description Incremental CEL export into SQL doesn't work if project property for maximum CEL text length has a value ...
OPCUA32: Variable is not included in background import result, when the quality returned in the read request for the value is not good
Summary - Description - Issue Number: 238464 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
CTI driver not communicating in zenon 10
Summary CTI driver communication error after update to zenon version 10. Description CTI driver communication error after update to zenon version 10. Issue Number: 240386 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Creating Tables for AML/CEL continous SQL export and external storage does not work on SQL Server versions older than 2019
Summary The problematic option was removed from the create table command. Creating the tables is now supported for Microsoft SQL Server 2008 and above. Description The problematic option was removed from the create table command. Creating the tables ...
GIS ActiveX is crashing after load the XML file the first time...
Summary - Description - Information not found so far. Issue Number: 240659 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Released property group of a symbol is not available / writeable via zenon API
Summary Issue Number: 240698 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
SIC - Attempted to access an unnamed file past its end" when opening a SIC file"
Summary The description fields were truncated. Else the text was overflowing, when the zip file was opened. Description The description fields were truncated. Else the text was overflowing, when the zip file was opened. Issue Number: 240628 Fixed on ...
Security with TLS in MQTT client
Summary Issue Number: 237040 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Service Engine can no longer be reloaded via Remote Transport
Summary Service Engine isn't reloading if reload is triggered via Remote Transport Description Service Engine isn't reloading if reload is triggered via Remote Transport Issue Number: 240617 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0
Summary Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0 Description Symbols contained within SOT Combined elements created in zenon 8.20, are not displayed correctly in zenon 10.0 Issue ...
Driver programmed simulation - strings do not work (all strings contain 1" as text) "
Summary When using simulation programmed, all strings contain the value "1". Description When using simulation programmed, all strings contain the value "1". Information no workaround Issue Number: 240334 Fixed on Date: 0.0.0 Versions: 10 0 BUILD ...
Service Engine crashes with data storage evacuation and SG API query
Summary Variable count was not set when reading archive data from Data Storage. This led to arithmetic underflow when decrementing the counter (inside CSGGHistorianRequest::AddArchive2Payload), which in turn led to a memory exception due to ...
SIC: Out of memory Exception, when large files are available in Log folder
Summary The Lines to be displayed on screen were capped to 1000 Description The Lines to be displayed on screen were capped to 1000 Issue Number: 240066 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
System Information Collector (SIC): Does not include installation logs of zenon 10 (software platform)
Summary Software platform setup logs are now collected. Description Software platform setup logs are now collected. Issue Number: 239758 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
Setup zenon Software Platform 10 don't installed Engineering Studio via Customize Egde Serices option
Summary Engineering Studio is installed as expected. Description Engineering Studio is installed as expected. Issue Number: 239993 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
system time change CEL entry only contains new time
Summary CEL entry created by function "Read time from variable" is wrong Description CEL entry created by function "Read time from variable" is wrong Issue Number: 239678 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
IEC850 Driver Configuration Wizard: does not work and has unhandled exception
Summary IEC850 Driver Configuration Wizard: does not work and has unhandled exception Description IEC850 Driver Configuration Wizard: does not work and has unhandled exception Issue Number: 239094 Fixed on Date: 0.0.0 Versions: 10 0 BUILD 83962
The AccessDNP3_SG DNP3 Outstation does not correctly set the value of the variable linked for a binary output with control model activation and deactivated command routing
Summary With the AccessDNP3_SG DNP3 Process Gateway and a binary output, configured for the control model "activation" and command routing deactivated, the process gateway sets the value to "0" and does not build a pulse when the master performs a ...
The OPC UA client driver does not allow configuration of the queuesize. A queuesize of 1 is always used, which may result in loss of value changes coming from the OPC UA server
Summary The OPC UA client driver uses a fixed queuesize of 1, which may result in a loss of value changes coming from the OPC UA server. Description The OPC UA client driver uses a fixed queuesize of 1, which may result in a loss of value changes ...
service engine crashes randomly by AD login (while process gateway is active)
Summary ServiceEngine sometimes crashes while processing CEL API event containing user name of AD user Description ServiceEngine sometimes crashes while processing CEL API event containing user name of AD user Information No Workaround. With a ...
SNMPNG: SNMPv3 (Authentication + Encryption) lost communication after device power off
Summary SnmpNg32-V3: Communication is lost and can't be re-established after a device power loss, if Snmp V3 (Authentication + Encryption) is active. Description SnmpNg32-V3: Communication is lost and can't be re-established after a device power ...
IEC850: Sporadic crash when using remote paths for File Transfer
Summary An error message is written, when the file could not be written. Description An error message is written, when the file could not be written. Information To use local paths only and use File Operations function to move the files later. Issue ...
Report viewer: the shift filter will be not applied, if you select Absolute time period" or "Realtive time period""
Summary Internal time filters of a report filter will be validated correctly . Description Internal time filters of a report filter will be validated correctly . Issue Number: 242181 Fixed on Date: 2.7.2021 Versions: 8.20 0 BUILD 85568 | 10 0 BUILD ...
Windows 10 20H2 Update breaks Keyboard Screen
Summary The keyboard will be rendered correctly . Description The keyboard will be rendered correctly . Information Move the Dialog Window, then everything gets rendered correctly Issue Number: 240972 Fixed on Date: 1.7.2021 Versions: 8.20 0 BUILD ...
Next page