zenWebClientStarter: Closing the application does not terminate the process

zenWebClientStarter: Closing the application does not terminate the process

Description

When closing the Smart Client Starter (ZenWebClientStarter.exe ) by clicking the X button or using the Alt+F4 key combination, an attempt is made to close the application. However, the associated process is not terminated. An empty thread blocks the closing of the Smart Client Starter process. 

If in the zenon6.ini in the section [ServiceGridGateway] the entry Version=LAST is deactivated (commented out by ;), the closing works.

This behavior has been changed. The Smart Client Starter is now closed correctly by clicking the X button or using the Alt+F4 key combination.

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 10 or higher.


Item ID: 258637
Version: 11.00 Build: 115310
Version: 10.00 Build: 116257
    • Related Articles

    • Checklist: Process closes unexpectedly (***Reproducible***)

      Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Process closes unexpectedly (***Non-reproducible***)

      Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Process Gateway cannot start

      Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Process is not responding

      Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Process Gateway cannot establish a reliable communication

      Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...