zenPG AccessIEC870Sl in 870-104 redundancy mode immediately closes one connection when redundant master opens second connection
Summary
The zenon Process Gateway AccessIEC870Sl does not support properly the IEC 60870-5-104 Edition 2.0 redundancy mode of Data Link correctly since the extension for IPv6 support.
Description
The zenon IEC60870-5-104 Process Gateway does not work correctly
in redundancy mode according to IEC 60870-5-104_ed2.0_b - section 10. It closes the first Data Link when the master establishes the second. The issue was introduced by changes to add support of IPv6 and affects IPv4.
This issue has been fixed. Redundancy now works as
defined in IEC 60870-5-104_ed2.0_b - section 10.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 10 or
higher.
Item ID: 271096
Version: 12.00 Build: 179985
Version: 12.00 Build: 180966
Version: 11.00 Build: 182164