zenPG AccessIEC870Sl in 870-104 redundancy mode immediately closes one connection when redundant master opens second connection
Summary
The zenon Process Gateway AccessIEC870Sl does not support properly the IEC 60870-5-104 Edition 2.0 redundancy mode of Data Link correctly since the extension for IPv6 support.
Description
The zenon IEC60870-5-104 Process Gateway does not work correctly
in redundancy mode according to IEC 60870-5-104_ed2.0_b - section 10. It closes the first Data Link when the master establishes the second. The issue was introduced by changes to add support of IPv6 and affects IPv4.
This issue has been fixed. Redundancy now works as
defined in IEC 60870-5-104_ed2.0_b - section 10.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 10 or
higher.
Item ID: 271096
Version: 12.00 Build: 180966
Version: 11.00 Build: 182164
Version: 10.00 Build: 195250
Related Articles
Redundant License Configuration
Starting from zenon version 8.00 it is possible to share each license over the CodeMeter network. This allows you to have a dedicated license server. The license server can be any PC or virtual machine which runs CodeMeter. One license for two ...
zenon Changesets CSV
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
zenon Changesets Excel
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
IEC60870-5-104 drivers (master and slave) are loosing redundant connection because of errors in START/STOP procedure implementations
Summary When triggering a manual redundancy switch the IEC60870-5-104 master acknowledges outstanding dl-frames after sending STOPDT. This may cause the slave to ignore the ack or even close the master connection. Description When triggering a manual ...
straton stops working when executing frequent redundancy switches
Description zenon Logic stops working unexpectedly in version 12 in redundancy mode in case of frequent server switches. This error has been fixed. Redundancy mode works as expected again. To benefit from this fix: Update your zenon Software Platform ...