zenonLogic Profinet IO driver (master) does not start when reconnecting special device

zenonLogic Profinet IO driver (master) does not start when reconnecting special device

Summary

With some profinet devices (in this case phoenix Contact Interbus / Profibus Gateway) there is a problem with the reconnect of the profinet driver. The Gateway sends a mismatch of modules to point on existing diagnosis messages. But it further sends a module description that fits to the projected one. The profinet driver stops the connection when it recives a mismatch, even if it receives a module description that fits to the existing project.

Description

With some profinet devices (in this case phoenix Contact Interbus / Profibus Gateway) there is a problem with the reconnect of the profinet driver. The Gateway sends a mismatch of modules to point on existing diagnosis messages. But it further sends a module description that fits to the projected one. The profinet driver stops the connection when it recives a mismatch, even if it receives a module description that fits to the existing project.

Solution

The configuration is now evaluated at connection initialization. Only if the state of a module or submodule is invalid the connect attempt is trated as unsuccessful.

Information

Fixed on 08.11.2012 with driver version 2404 available from 7.00 SP0 Build 4



Issue Number: 28905
Fixed on Date: 8.11.2012
Versions: 7.00 0 BUILD 4