zenon Setup fail during CodeMeter installation on windows 10.
Summary
On specific system constellation – Windows 10 Build 1511 and/or 1607 - it could be that the zenon setup cancel with ‘Service, CodeMeter Runtime Server failed to start. Verify that you have sufficient privileges to start system services.’
Description
On specific system constellation – Windows 10 Build 1511 and/or 1607 - it could be that the zenon setup cancel with ‘Service, CodeMeter Runtime Server failed to start. Verify that you have sufficient privileges to start system services.’
Solution
An issue was addressed at the CodeMeter services on specific system constellation.
Workaround for 7.50 -> install CodeMeter version high then 6.40.
zenon 7.60 setup will be including automatically an higher version of the CodeMeter services.
Information
Workaround:
Install the latest CodeMeter Runtime version for example: 6.40.2396.500, which can be downloaded from Wibu System directly, before installing zenon 7.50.
Issue Number: 37491
Fixed on Date: 15.12.2016
Versions: 7.60 0 BUILD 36068
Related Articles
Checklist: Software Platform installation fails
Time estimate: 30 minutes Please go through all the items in the following checklist. If necessary, confirm any information you cannot verify with the IT department before contacting your local COPA-DATA representative. Checklist usage: #. [Quick ...
zenon Changesets Excel
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
FAQ: Does zenon support silent setup installation/uninstallation?
For silent-installation and uninstallation of zenon components consult this documentation topic.
zenon Changesets CSV
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
Wibu-Systems - CodeMeter Control Center for Windows version - security vulnerabilities addressed WIBU-100120
COPA-DATA has been informed by Wibu-Systems about a security vulnerability in the Wibu-Systems CodeMeter Control Center for Windows software with the following CVSS 3.1 base score: CVE-2025-47809 – base score 7.7 - vector ...