The zenon Process Gateway AccessDNP3 saved its configuration from memory to the file when the zenon Service Engine was closed,
reloaded, or the Process Gateway itself was closed directly. This could overwrite a new configuration which was transferred from the Engineering Studio. For example, added variables could get removed from the configuration.
The issue has been addressed and the configuration is no longer reverted back when the Process Gateway closes or reloads.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 10 or higher.
Item ID: 297114