WVS: RGM 1 - Basic recipe value list
Summary
WVS supports screen of type Recipe Group Manager.
Description
The screen of type Recipe Group Manager can be called up in the Web Visualization Service.
The following are supported:
- Recipe value table
With direct editing, except Action column - Read and set values
- Save recipes
- Sending progress
- User rights, but no signature and no eSignature
- Response variables
Item ID: 250018
Version: 12.00 Build: 153415
Related Articles
FAQ: It seems that sometimes not all variables are correctly written to the PLC by the RGM module, although the system driver variable states that the recipe was written successfully and the option "write synchronously" is active. How can this be?
When reading a RGM recipe immediately after writing a RGM recipe, with a driver that has the option "keep update list in memory" active, and recipe variables that have been read previously, it can happen that a read cycle is currently in progress, ...
WVS: RGM recipe resets values to default after language or palette switch
Description In the Web VisualizationService (WVS), the current values of an RGM recipe are reset to the recipe default values after a change of language or color palette. This error has been fixed. The recipe values are retained as expected when ...
WVS: Input misplaced when using RGM in a worldview
Summary In WVS, the input field for values in the worldview screen is placed incorrectly under certain conditions. This has been fixed. Description In WVS, the input field for values in a worldview screen may be positioned incorrectly. In this case, ...
Increment and Decrement RGM specfic keyboard screen functions do not work with the new recipe value list
Summary The keyboard screen allows configration of Recipegroup Manager specific functions for incrementing and decrementing the selected recipe value through the keyboard screen. In the runtime with the new recipe value list, the functions do not ...
FAQ: When I activate the option "write synchronously" for the Recipegroup manager recipe, and I write the recipe, the recipe does not seem to be written properly and also the Service Engine does not close properly. Why is that?
When the option "write synchronously" is active at a recipe, when writing a recipe (sending values to the PLC) for each recipe variable a writing confirmation is requested to the driver. On a successfull write, the driver sends a writing confirmation ...