When using the OMR_FINS driver and having option "First character is lo-byte" deactivated, when writing a string variable the OMR_FINS driver sends char null instead of last character.

When using the OMR_FINS driver and having option "First character is lo-byte" deactivated, when writing a string variable the OMR_FINS driver sends char null instead of last character.

Summary

The OMR_FINS driver sends char null instead of last character of a string when the option "First character is lo-byte" is deactivated. When having e. g. a string variable of the OMR_FINS driver with String length 10, when writing a string to this variable, the OMR_FINS driver sends only 9 characters + null termination.    

Description

The OMR_FINS driver sends char null instead of last character of a string when the option "First character is lo-byte" is deactivated. When having e. g. a string variable of the OMR_FINS driver with String length 10, when writing a string to this variable, the OMR_FINS driver sends only 9 characters + null termination.    

Solution

This issue has been addressed by improving the behaviour the OMR_FINS driver writes string values.

Issue Number: 38291
Fixed on Date: 29.5.2017
Versions: 7.50 0 BUILD 39729