Under specific circumstances the function linked to a reaction matrix state is not executed in the runtime.
Summary
The function linked to a reaction matrix state may not be executed if the "call via button in screen alarm message list" option is ticked but greyed out in the Editor.
Description
The function linked to a reaction matrix state may not be executed if the "call via button in screen alarm message list" option is ticked but greyed out in the Editor.
Solution
An issue has been resolved so that the "call via button in screen alarm message list" is only considered when the option "in alarm message list" is activated in the reaction matrix configuration dialog.
Workaround: To deselect the "call via button in screen alarm message list" option by enabling/disabling the "alarm message list" property in the reaction matrix state.
Issue Number: 35415
Fixed on Date: 18.11.2015
Versions: 7.60 0 BUILD 36068