The zenon OPC UA server incorrectly sends an initial PublishResponse with a DataChange notification instead of an EventNotificationList when an OPC UA client subscribes for events

The zenon OPC UA server incorrectly sends an initial PublishResponse with a DataChange notification instead of an EventNotificationList when an OPC UA client subscribes for events

Summary

When an OPC UA client subscribes for events in a subscription (CreateMonitoredItems, Attribute 12) the zenon OPC UA server incorrectly sends a PublishResponse with a DataChange notification instead of a EventNotificationList. The incorrectly sent DataChange notification may cause an exception in OPC UA clients

Description

When an OPC UA client subscribes for events in a subscription (CreateMonitoredItems, Attribute 12) the zenon OPC UA server incorrectly sends a PublishResponse with a DataChange notification instead of a EventNotificationList. The incorrectly sent DataChange notification may cause an exception in OPC UA clients

Solution

An issue has been addressed in the zenon OPC UA server where a DataChange notification in the first PublishResponse was sent rather than a EventNotificationList.

Issue Number: 34684
Fixed on Date: 23.11.2015
Versions: 7.60 0 BUILD 36068