Summary

The zenon logic runtime on Windows CE ARM devices with IEC60870 master may close unexpectedly when receiving floating point values in response to a General Interrogation request. (T36)



Description

The zenon logic runtime on Windows CE ARM devices with IEC60870 master may close unexpectedly when receiving floating point values in response to a General Interrogation request. (T36)



Solution

An issue has been addressed in the zenon logic runtime for Windows CE devies with an ARM processor where floating point values received were not correctly processed.

Information

This issue may also affect the IEC61850 MMS client in the zenon logic runtime on Windows CE on devices with ARM processors



Issue Number: 33310
Fixed on Date: 5.12.2014
Versions: 7.11 0 BUILD 17075