The active-status of message control is not synchronised properly betweed server and standby server.

The active-status of message control is not synchronised properly betweed server and standby server.

Summary

If the active-status of message control is changed via function, the active-status is not synchronised properly between standby server and server after reactivation of primary server in a server-standby server architecture with dominant software redundancy.

Description

If the active-status of message control is changed via function, the active-status is not synchronised properly between standby server and server after reactivation of primary server in a server-standby server architecture with dominant software redundancy.

Solution

The active-status will now be exchanged between standby server and server at startup of primary server to ensure the correct active-status after switching from standby server to server.

Issue Number: 36197
Fixed on Date: 14.4.2016
Versions: 7.20 0 BUILD 27570 | 7.50 0 BUILD 27465