The 3S_V3 driver is not included for Windows CE platforms in the zenon 7.11 setup and that may result in an error on updating the CE device.

The 3S_V3 driver is not included for Windows CE platforms in the zenon 7.11 setup and that may result in an error on updating the CE device.

Summary

An error message is displayed when attempting to update a Windows CE device with version 7.11 with all drivers selected: "Files not found: ..\3S_V3.dll - Your CE Runtime files are not complete. Make sure that the path exists and contains all runtime files as defined in the updatece.ini! Please refer to the online help for additional information." The reason for the error message is that the 3S_V3 driver is included in the list of drivers but was not installed with the setup.  

Description

An error message is displayed when attempting to update a Windows CE device with version 7.11 with all drivers selected: "Files not found: ..\3S_V3.dll - Your CE Runtime files are not complete. Make sure that the path exists and contains all runtime files as defined in the updatece.ini! Please refer to the online help for additional information." The reason for the error message is that the 3S_V3 driver is included in the list of drivers but was not installed with the setup.  

Solution

The build setup has been enhanced to install the 3S_V3.dll file for CE platforms. Now the CE Runtime updated can be completed correctly with all drivers selected and the 3S_V3.dll driver is also transferred.

As a workaround, the 3S_V3.dll can be unselected in the Files tab of files to be updated. The runtime can then be updated correctly.



Issue Number: 31716
Fixed on Date: 4.4.2014
Versions: 7.11 0 BUILD 11882