T70 and T105 cannot be mapped in the IEC60870S and IEC60870S2 Profiles

T70 and T105 cannot be mapped in the IEC60870S and IEC60870S2 Profiles

Summary

TID 70 and TID 105 is missing in selection

Description

TID 70 and TID 105 is missing in selection

Information

Simply add the two Following lines in the IEC60870.prf and IEC60870S2.prf files (folder where zenon Logic is installed and ..\HwDef\Standard)

<< 70 = (70) End Of Initialization >>
<< 105 = (105) Reset Process Command >>



Issue Number: 157450
Fixed on Date: 16.11.2018
Versions: 8.00 0 BUILD 53129