T5BusIec850s: connection loss during command execution (Operate received but not responded yet) locks next commands
Summary
Issue in the IEC 61850 Server driver in zenon Logic:
if an 850-client disconnects right after requesting Operate and before the IEC 61850 Server sends the response, the state-machine is locked in Control Variable = 199 (or 200). If the 850-client reconnects, the driver refuses all command-write requests to affected object.
Description
Issue in the IEC 61850 Server driver in zenon Logic:
if an 850-client disconnects right after requesting Operate and before the IEC 61850 Server sends the response, the state-machine is locked in Control Variable = 199 (or 200). If the 850-client reconnects, the driver refuses all command-write requests to affected object.
Solution
Now disconnection of the client forces control state reset.
Issue Number: 36739
Fixed on Date: 13.7.2016
Versions: 7.50 0 BUILD 29630