SYSDRV variable ‘Alarm Message List active/inactive’ value is TRUE while AML is deactivated via zenon function.
Summary
The System Driver variable ‘Alarm Message List active/inactive’ has value TRUE, also while the AML is deactivated via zenon function ‘Activate/deactivate Alarm Message List, alarm/event groups/classes’ - configured to toggle/deactivate the ‘Total Alarm Message List’.
When the AML is deactivated already in Editor, the variable is FALSE correctly.
Description
The System Driver variable ‘Alarm Message List active/inactive’ has value TRUE, also while the AML is deactivated via zenon function ‘Activate/deactivate Alarm Message List, alarm/event groups/classes’ - configured to toggle/deactivate the ‘Total Alarm Message List’.
When the AML is deactivated already in Editor, the variable is FALSE correctly.
Solution
Issue addressed in function execution.
Issue Number: 35409
Fixed on Date: 13.11.2015
Versions: 7.60 0 BUILD 36068