In the version 1800 of the stratonNG driver string variables cannot be read anymore. An Element from type dynamic text stays empty. In diagnosis viewer (deep debug) you can see that the driver gets the value from zenon Logic runtime, but then does not deliver to zenonRT
In the version 1800 of the stratonNG driver string variables cannot be read anymore. An Element from type dynamic text stays empty. In diagnosis viewer (deep debug) you can see that the driver gets the value from zenon Logic runtime, but then does not deliver to zenonRT
corrected the assignment of string variables.
Fixed on 18.07.2012 with driver version 1902 available from 7.00 SP0 Build 2