Straton process crash when unplugging a ProfiNET sub-module

Straton process crash when unplugging a ProfiNET sub-module

Description

An issue in the ProfiNET alarm management function block PNIOGETALARM sporadically caused the zenon Logic service process to terminate, e.g when unplugging a ProfiNET I/O sub-module. The process restarted automatically and communication was restored when the module was re-plugged.
The issue has been addressed and the behavior is now as expected. 

 

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 15 or higher.


Item ID: 310039
Version: 16.00 Build: 650097
Version: 15.00 Build: 646946