straton IEC61850 Server does not start GOOSE because IdInst are empty in K5BusIec850s_GO.SCL

straton IEC61850 Server does not start GOOSE because IdInst are empty in K5BusIec850s_GO.SCL

Summary

When the driver's configurator ( K5* ) creates from particular SCLfile the file with GOOSE reception data model - the original ldInst became part of IED name. Then the driver does not start and the straton Runtime writes error message "Attribute 'ldInst' is empty or missing ...". Workaround is to manual correct in Custom\K5*_GO.SCL the IED name and idInst.

Description

When the driver's configurator ( K5* ) creates from particular SCLfile the file with GOOSE reception data model - the original ldInst became part of IED name. Then the driver does not start and the straton Runtime writes error message "Attribute 'ldInst' is empty or missing ...". Workaround is to manual correct in Custom\K5*_GO.SCL the IED name and idInst.

Solution

The issue was addressed in function parsing SCL-file for GOOSE subscription. The driver now does not build own IED names but always left given prefix and suffix.

Information

Fixed on 06.07.2012 in version 6200 of T5BusIec850s.dll; available from 7.00 SP0 Build 2; available from 6.51 SP0 Build 15.



Issue Number: 27286
Fixed on Date: 6.7.2012
Versions: 6.51 0 BUILD 15 | 7.00 0 BUILD 2