When using the Service Engine Version 11 in combination with IIoT Services (Service Grid) version 11.2 or later, communication problems occur when utilizing the Service Node Configuration Tool (SNCT) to retrieve certificate bundles from the Hub Controller.
Cause:
When using IIoT Services (Service Grid) Version 11.2 or later with a Service Node Configuration Tool (SNCT) prior Build 11.0..0.111841, the SNCT does not support the communication with the Hub Controller via the Proxy Service. The Proxy Service was introduced with IIoT Services (Service Grid) 11.2.
The former fields for Port and Hostname have been merged into the URL field. This requires an additional path specification for the Hub Controller.
Solution: