Set value uses wrong range for variable with linear range adjustment using the element input field of the dynamic text

Set value uses wrong range for variable with linear range adjustment using the element input field of the dynamic text

Description

When writing the set value for a variable with a linear range adjustment via a text field, the signal range is offered instead of the configured value range. When the set value is entered via the set value dialog or a numeric value element, the configured range is correctly taken into account.

This behavior has been modified. Input via a text field now resembles input via a numeric value element.

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 11 or higher.


Item ID: 246047
Version: 11.00 Build: 104641