Server is not responding to user actions if SMS gateway method is used in a redundant system

Server is not responding to user actions if SMS gateway method is used in a redundant system

Summary

If a redundant system is used in combination with Message Controls SMS gateway dispatching method, after some time the runtime on the server is no longer responding.

Description

If a redundant system is used in combination with Message Controls SMS gateway dispatching method, after some time the runtime on the server is no longer responding.

Solution

An issue has been addressed where Message Control could run into a deadlock when synchronizing a message with the standby that has been sent successfully. Now, the message is just locked until changes to the message object are performed so the server can send the information about the sent message to the standby without waiting for the lock to be removed.

Information




Issue Number: 32092
Fixed on Date: 30.6.2014
Versions: 7.10 0 BUILD 13311 | 7.11 0 BUILD 13121
    • Related Articles

    • Redundant License Configuration

      Starting from zenon version 8.00 it is possible to share each license over the CodeMeter network. This allows you to have a dedicated license server. The license server can be any PC or virtual machine which runs CodeMeter. One license for two ...
    • Checklist: Process Gateway cannot start

      Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: OPCDA Server

      Time estimate: 20 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Do NOT use DCOM in combination ...
    • FAQ: What are Installation and Security considerations of the zenon Smart Server and Smart Client?

      The attached document (English only) describes in some detail the specifics of the zenon Smart Server Application and the zenon Smart Client Application. Also a short explanation of security features and components is given. More information about ...
    • Checklist: Process Gateway cannot establish a reliable communication

      Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...