SE: ETM - zoom out completly on Y axis - SE crashes

SE: ETM - zoom out completly on Y axis - SE crashes

Description

The zenon Service Engine closed unexpectedly after a zooming out procedure in the ETM screen. The issue was triggered by trying to extend the time range beyond Year 2038, where the traditional 32bit signed integer wraps to -1. The specific zoom cropped the time range before an overflow occured. 
The issue has been addressed and the zoom out works now as expected. 
 
To benefit from this fix: 
  • Update your zenon Software Platform to the latest build of zenon 14 or higher. 


Item ID: 284165
Version: 14.00 Build: 293273
    • Related Articles

    • zenon Changesets CSV

      Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
    • zenon Changesets Excel

      Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
    • ETM: Y-Axis automatic scaling changes value range

      Description In the ETM the Y-axis changed automatically the scaling range, if the value of the variables was changed a few times. This happened because no value change was found and so the default scale of +- 10% of the variable value range was ...
    • "Y Axis From" Setting Didn't work on Extended Trend Screen's Expanded Curvelist in v14

      Description The “Y-Axis from” setting did not work correctly in the Extended curve list of the Extended Trend screen. When setting the "Axis from" value to a value lower than the current "Axis from" value, no change occurred. The issue has been ...
    • Import of zenPG config from SE to ES (decompile) no longer works in zenon 14 - "empty" templates used instead

      Description When importing Service Engine files into the zenon Engineering Studio, zenon Process Gateway configurations were replaced by default templates instead of the actual configuration. The issue has been addressed and the zenPG configuration ...