SAP maintenance reports don´t work
Summary
In the module SAP interface it is possible to define maintenance reports. They actually use the SAP function blocks
ALM_PM_MAINTNOT_CREATE
ALM_PM_MAINTNOT_SAVE
ALM_PM_MAINTNOT_MODIFY_DATA
These are, however, not remote enabled with a standard SAP setup. Therefor the SAP administrator would have to modify the configuration of these function blocks. Without a modification, zenon is not able to call these function blocks.
Description
In the module SAP interface it is possible to define maintenance reports. They actually use the SAP function blocks
ALM_PM_MAINTNOT_CREATE
ALM_PM_MAINTNOT_SAVE
ALM_PM_MAINTNOT_MODIFY_DATA
These are, however, not remote enabled with a standard SAP setup. Therefor the SAP administrator would have to modify the configuration of these function blocks. Without a modification, zenon is not able to call these function blocks.
Solution
The used function bocks have been replaced. Now
BAPI_ALM_NOTIF_CREATE
BAPI_ALM_NOTIF_SAVE
BAPI_ALM_NOTIF_DATA_MODIFY
are used to create maintenance reports. These are remote enabled by default.
Issue Number: 35213
Fixed on Date: 2.12.2015
Versions: 7.60 0 BUILD 36068
Related Articles
Checklist: SAP Interface does not work
Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick ...
occasional unexpected shutdown of the zenon runtime when executing SAP maintenance reports
Summary In rare cases it happens that the zenon runtime closes unexpectedly after sending a maintenance report to a SAP system. This is especially the case if a redundancy switch has been performed ealier. Description In rare cases it happens that ...
No logging for failed maintenance messages
Summary When maintenance reports are used at the SAP Interface but creating the maintenance report in SAP fails (e.g. because of incorrect configuration), the log file does not provide information about this. Description When maintenance reports are ...
Deactivate a user via user list with signature active on the button don´t work correct
Summary The users will be deactivated correctly . Description The users will be deactivated correctly . Issue Number: 197314 Fixed on Date: 20.9.2019 Versions: 8.00 0 BUILD 61597 | 8.10 0 BUILD 61858
Checklist: Smart Client does not work